Steinmetz Capacitor: Three-Phase Motor on Single Phase

Size a Steinmetz run capacitor at a chosen load using a motor circuit model. Check starting capacitance, capacitor voltage, winding currents and available power.

#induction-motor #run capacitor #single-phase supply #start capacitor #Steinmetz #symmetrical-components

This Steinmetz capacitor calculator helps engineers and students examine a three-phase induction motor supplied from single phase. It estimates a run capacitor for the chosen load and shows why a fixed “70 µF per kW” answer can disagree with current-based formulas. It also predicts capacitor voltage, winding currents, shaft power and the extra capacitor used briefly during starting.

Start with the motor nameplate. Select delta or isolated wye and enter the rated voltage of one winding, motor nameplate frequency, three-phase line current for that connection, and rated shaft power. A 230/400 V Δ/Y motor normally uses delta on a 230 V single-phase supply; reconnecting a motor whose windings require 400 V does not make them suitable for 230 V operation. Confirm that all required winding leads are accessible.

The detailed model needs stator resistance, rotor resistance referred to the stator, leakage reactances and magnetizing reactance. These normally come from motor tests or an identified equivalent circuit. The reactance test frequency is separate from the motor's rated frequency used for the V/Hz screen. Nameplate power alone cannot determine them. The defaults use published parameters for a 0.75 kW example, with an assumed reconnectable winding arrangement and a separate illustrative 20 W loss allowance. Replace them for your motor.

Choose required shaft power to solve for an operating slip, or enter measured slip directly. The automatic run capacitor size minimizes the backward-to-forward air-gap field ratio at that point. Switch to an entered capacitor to evaluate an available bank. The winding-current table and capacitance sweep reveal tradeoffs: the best field balance is not necessarily the best efficiency, and perfect balance may be impossible. The power-ceiling result is a sampled current/voltage screening estimate, not a continuous-duty thermal rating.

The starting bank is reported as both total capacitance and extra switched capacitance. A loaded-start estimate uses two to three times the run value in total. The extra section needs an appropriate cutout device and motor-start duty rating; acceleration time and repeated-start heating require separate checks. Modeled starting torque uses constant parameters and does not include deep-bar effects or supply sag.

Press play to animate the current phasors and the forward and backward air-gap field vectors. I₁, I₂ and I₃ correspond to the winding-table rows. The field sum traces the dotted ellipse; as the backward component vanishes, this orbit becomes circular.

Mains installation work belongs to a qualified person. Provide isolation, protective earthing, motor overload protection, guarded terminals and safe capacitor discharge. Select AC motor capacitors using their actual RMS voltage, current and duty specifications. Check local grid-operator limits, particularly above about 1.5 kW; this calculator grants no connection approval. For high starting loads or wide load variation, evaluate a correctly rated single-phase-input, three-phase-output drive with the motor supplier.

How it is calculated

Sequence circuit and capacitor sizing

This tool derives its terminal solution from Kirchhoff's laws and symmetrical components. Popescu et al., attached source s2, pp. 1–4, establishes the Steinmetz delta/wye sequence framework; the nodal equations and bounded optimization below are derived here.

All motor impedances are per physical stator winding, rotor values referred to that winding. Reactances scale with supply/test frequency. The winding-voltage ceiling uses a separate motor nameplate frequency, not the frequency at which reactances were identified. The linear T circuit is

Z(s)=Rs+jXs+[jXm∥(Rr′/s+jXr′)].Z(s)=R_s+jX_s+\left[jX_m\parallel(R'_r/s+jX'_r)\right].

Use slips ss and 2−s2-s for the forward and backward circuits. Let a=ej120∘a=e^{j120^\circ} and k=3k=3 for delta, k=1k=1 for isolated wye. Terminal sequence admittances are Y+=k/Z(s)Y_+=k/Z(s) and Y−=k/Z(2−s)Y_-=k/Z(2-s).

The supply fixes VA=UV_A=U, VB=0V_B=0. The capacitor connects A to the otherwise floating terminal C. With b=2πfCb=2\pi fC, D=(Y++Y−)/3D=(Y_++Y_-)/3 and H=(aY++a2Y−)/3H=(aY_++a^2Y_-)/3, its KCL equation gives

VC=Ujb−HD+jb,V+=U+a2VC3,V−=U+aVC3.V_C=U\frac{jb-H}{D+jb},\qquad V_+=\frac{U+a^2V_C}{3},\qquad V_-=\frac{U+aV_C}{3}.

Multiply these terminal phase voltages by 1−a21-a^2 and 1−a1-a respectively for delta winding sequence voltages; wye needs no multiplier. The parallel branch voltage gives each air-gap EMF. Their magnitude ratio is the backward/forward flux ratio because both EMFs are at the supply frequency.

For a fixed slip, this ratio differs from ∣V−/V+∣|V_-/V_+| by a constant. The squared voltage ratio is a ratio of quadratics in bb. Evaluate its stationary points and both endpoints within 0≤C≤Cmax⁡0\le C\le C_{\max} to find the global bounded minimum. Full balance requires a positive-sequence impedance angle of 60° for the drawn connection, and is generally unavailable at an arbitrary load.

Power, current and load

Reconstruct the three physical winding currents from their sequences. Capacitor RMS voltage is ∣U−VC∣|U-V_C| and capacitor current is 2πfC∣U−VC∣2\pi f C|U-V_C|. Electrical angular frequency is reported in rad/s; dividing by one radian treats radians as dimensionless when forming scalar capacitor susceptance. If Ir+′I'_{r+} and Ir−′I'_{r-} are the rotor branch currents,

Pg+=3∣Ir+′∣2Rr′/s,Pg−=3∣Ir−′∣2Rr′/(2−s),P_{g+}=3|I'_{r+}|^2R'_r/s,\quad P_{g-}=3|I'_{r-}|^2R'_r/(2-s),
Pshaft=(1−s)(Pg+−Pg−)−Prot.P_{\rm shaft}=(1-s)(P_{g+}-P_{g-})-P_{\rm rot}.

Power mode brackets the first rising crossing of the target on 81 samples over slip 0.0005–0.25, then solves the load equation. The power ceiling is the largest positive sample before the sampled power peak satisfying the rated winding current and a voltage screen of 1.10 Uw,ratedfline/frated1.10\,U_{w,\mathrm{rated}}f_{\mathrm{line}}/f_{\mathrm{rated}}. In automatic mode the curve retunes C at each slip; it is not the torque-speed curve of one fixed capacitor. The ceiling is capped by neither thermal measurements nor a cooling model.

Practical comparisons and starting

TPU Lab 5, source s1, pp. 5–6, gives the approximate 50 Hz current rules CΔ=4800I/UC_{\Delta}=4800I/U and CY=2800I/UC_Y=2800I/U with C in µF, I in A and U in V. Here I is the rated winding current: delta nameplate line current divided by √3, or line current directly for wye. This follows the manual's current definition using three phases and phase voltage; inverse-frequency scaling is an extension based on capacitor susceptance. The separate 70 µF/kW comparison is a 230 V, 50 Hz delta rule and is not extrapolated as a physical motor model.

The starting choice follows TPU p. 6: total bank = run + extra, with 2–3 × run in total as a loaded-start trial. Standstill torque and voltage use the same sequence model at s = 1. These estimates do not determine a cutout time or prove acceleration.

Assumptions

  • Sinusoidal stiff single-phase mains, three identical windings, isolated motor neutral and an ideal lossless capacitor. The diagram is conceptual; protective, switching and discharge equipment is omitted.
  • A single-cage linear T circuit with constant resistances, no core-loss resistance, no saturation, rotor skin effect, harmonics, temperature iteration or mechanical transient. The additional loss allowance is subtracted from converted power.
  • Default R and X values are the SA-ERWCA Machine 4 values in Ćalasan et al., source s3, Table 18, p. 17. The publication reports a 0.75 kW, 380 V, 50 Hz, one-pole-pair motor. Treating those per-phase values as physical windings of a reconnectable 220/380 V motor for the 230 V delta example is an explicit illustrative reconnection assumption, not a manufacturer-approved conversion. The default 1.86 A winding-current limit is an illustrative assumption based on the published s = 0.06 test point, not a reported nameplate rating; its delta line-current equivalent is approximately 3.22 A. The 20 W loss allowance is assumed, not reported by that paper.
  • Replace every equivalent-circuit and nameplate value for your motor. kW, efficiency and power factor alone do not identify a unique motor circuit.
  • Flux vectors use the air-gap EMF divided by jω; the animation normalizes the maximum field envelope to unity. Winding current phasors share a common RMS scale. Electrical angle rotates the picture only and does not rerun sizing.
  • Published checks cover the balanced T circuit at two slips, the TPU starting-bank arithmetic and the TPU delta formula's winding-current convention. They are not measured validation of the complete Steinmetz predictions. Nodal, energy and optimization residual properties provide additional internal verification.

Where it applies

Use for preliminary sizing and teaching with small, reconnectable squirrel-cage motors and an operating slip between 0.0005 and 0.25. Results depend strongly on identified circuit parameters and actual load. Near resonance or saturation, calculated capacitor voltages and currents can be misleading. A minimum backward field is not an optimum-efficiency or minimum-heating guarantee.

The sampled power ceiling can miss a narrow feasible region and underestimates the continuous optimum between samples. Automatic mode permits a different capacitor at each sampled load. It does not certify continuous duty: negative-sequence rotor heating, cooling, hot resistance, starting duty and winding temperature require motor-specific checks. Never increase winding current to match a desired output.

The TPU manual's p. 7 voltage guidance contains inconsistent margins (1.5 and 1.15 times supply) and mixes discussion of AC and DC markings. Neither rule is used as a component rating here. Use the actual continuous AC RMS rating, capacitor current rating and manufacturer's duty/temperature limits. The 15% modeled run-voltage margin is only a screening reminder; include supply tolerance, resonance during acceleration and switching transients separately. A start capacitor must be intended for AC motor starting, with a suitable automatic cutout and discharge provision. Do not leave it connected during normal running.

Installation work belongs to a qualified person. Isolate and verify dead, discharge capacitors safely, provide protective earthing, correct motor overload protection and guarded terminals. Live commissioning and verification of every winding current require qualified personnel and suitable equipment.

No jurisdiction-specific installation or grid-connection rule is implemented. The 1.5 kW reminder is an advisory threshold from the task brief, not a legal limit or connection approval. Check your grid operator's current connection agreement and starting-current limits. Scope statement dated 27 October 2026; check the rules in force.

References

  • Tomsk Polytechnic University, Laboratory Work 5: Single-phase starting of a three-phase induction motor, pp. 5–7. Run-capacitor heuristics, total versus extra starting capacitance and limitations. https://portal.tpu.ru/SHARED/c/CHIA/uchwork/Tab2/%D0%9F%D0%BE%D0%B4%D0%BA%D0%BB%D1%8E%D1%87%D0%B5%D0%BD%D0%B8%D0%B5%20%D1%82%D1%80%D0%B5%D1%85%D1%84%D0%B0%D0%B7%D0%BD%D0%BE%D0%B3%D0%BE%20%D0%B4%D0%B2%D0%B8%D0%B3%D0%B0.pdf
  • Popescu, M., Ionel, D. M., Dellinger, S., Miller, T. J. E. and McGilp, M., Analysis and Design of a Two-Speed Single-Phase Induction Motor with 2 and 18 Pole Special Windings, open author manuscript, pp. 1–4 and 7–9. Steinmetz sequence model and balancing limitations. https://descargas.indielec.com/web/iemdc_2003_imtwospeed.pdf ; journal version DOI: 10.1109/TEC.2004.842396 (bibliographic DOI only).
  • Ćalasan, M. et al. (2020), Parameter Estimation of Induction Machine Single-Cage and Double-Cage Models Using a Hybrid Simulated Annealing–Evaporation Rate Water Cycle Algorithm, Mathematics 8(6), 1024, Tables 17–19, pp. 17–18. DOI: 10.3390/math8061024. Open manuscript: https://bura.brunel.ac.uk/bitstream/2438/21098/2/FullText.pdf

Inputs

InputSymbolUnitDefault
Single-phase supply, RMS
Voltage between the two supply wires; this is not a three-phase voltage output.
U_lineV230
Supply frequency
The reactances below are scaled from their test frequency.
f_lineHz50
Motor nameplate frequency
Rated frequency for the winding voltage above. Used for the V/Hz screen; separate from the reactance test frequency.
f_ratedHz50
Motor winding connection
Use the connection allowed by the nameplate. A 230/400 V motor normally uses delta at 230 V.
connDelta (Δ)
Rated voltage of one winding
Use the lower voltage on a Δ/Y nameplate. Defaults assume a reconnectable 220/380 V version of the published example.
U_w_ratedV220
Rated three-phase line current
Nameplate current for the selected connection, not single-phase supply current. Default is √3 × the source's 1.86 A example.
I_line_ratedA3.22
Rated three-phase shaft power
Used for comparison and the 70 µF/kW rule, not to infer equivalent-circuit parameters.
P_ratedkW0.75
Pole pairs
One pole pair = 2 poles. The source example is a 2-pole motor.
pairs1
Specify operating load by
Power mode finds the first positive-torque solution on the rising low-slip branch, within slip 0.0005…0.25.
load_modeRequired shaft power
Required shaft power
This is shaft load after the entered rotational loss.
P_loadkW0.35
Operating slip (0.04 = 4%)
s = (synchronous speed − measured speed) / synchronous speed.
s_set0.04
Run capacitor selection
The optimum minimizes the backward/forward air-gap field ratio. Exact balance is not always possible.
cap_modeMinimize backward field at this load
Entered run capacitance
Use this mode to evaluate a real capacitor bank, including zero capacitance.
C_manualuF40
Run-capacitance search ceiling
Optimization is bounded between zero and this value; increase it if the result reaches the ceiling.
C_maxuF400
Starting bank estimate
TPU Lab 5, p. 6: total starting capacitance is run plus extra; extra must be disconnected after acceleration. These are trial values, not a start guarantee.
start_dutyLoaded: 2.5 × run, total
Run capacitor AC RMS rating
Enter its continuous AC rating, never a DC voltage marking. Check current rating, duty and manufacturer data separately.
U_cap_ratingV450
Stator resistance per winding
Default: Ćalasan et al., Table 18, Machine 4 SA-ERWCA. Enter hot winding resistance, not terminal-to-terminal resistance.
R_sohm10.094
Rotor resistance, stator-referred
Per physical stator winding. Defaults illustrate a motor; they cannot be inferred uniquely from kW alone.
R_rohm10.238
Stator leakage reactance at test frequency
Per winding, not total stator-plus-rotor leakage.
X_s0ohm9.506
Rotor leakage reactance at test frequency
Stator-referred standstill reactance per winding.
X_r0ohm17.315
Magnetizing reactance at test frequency
Linear unsaturated magnetizing branch. Core-loss resistance is omitted.
X_m0ohm141.961
Equivalent-circuit test frequency
Frequency at which Xs, Xr and Xm are specified; separate from the motor nameplate frequency.
f_testHz50
Rotational and additional loss allowance
Subtracted from converted mechanical power. Default 20 W is an illustrative assumption, not a reported measurement.
P_rotW20
Phasor / field angle
Press ▶ to animate the phasors. The dotted field orbit becomes circular as the backward field vanishes.
theta_animdeg35

Results

With the default inputs above, the calc gives:

ResultValue
Run capacitor at this load38.6 uF
Extra starting capacitor (switched out)58 uF
Total starting bank (run + extra)96.6 uF
Run capacitor RMS voltage236 V
Run capacitor RMS current2.86 A
Predicted shaft power0.35 kW
Sampled power ceiling: current / voltage screen0.503 kW
Backward / forward field ratio0.0138
Highest winding current / rated winding current0.964
Single-phase supply RMS current2.54 A
Operating speed2,911 1/min
Modeled starting torque1.47 N·m
Starting-bank RMS voltage at standstill171 V
Standstill supply RMS current9.97 A
Single-phase input power factor0.793
70 µF/kW comparison (230 V, 50 Hz)52.5 uF
TPU winding-current comparison38.8 uF

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

Published Machine 4: balanced current and power factor at s = 0.06

Source: Ćalasan et al. (2020), doi:10.3390/math8061024, Tables 18–19, pp. 17–18. Independent published SA-ERWCA current/PF with the Table 18 parameters. This validates the balanced three-phase T circuit, not measured Steinmetz performance. Measured current is 1.86 A and PF 0.62; the test uses the more precise published computed values.

Inputs: Specify operating load by = Measured operating slip; Operating slip (0.04 = 4%) = 0.06; Motor winding connection = Wye (Y), isolated neutral; Single-phase supply, RMS = 380 V; Rated voltage of one winding = 219.4 V; Rated three-phase line current = 1.86 A; the others as above.

ResultSourceThis calc
Balanced three-phase line current at the same slip1.859 A1.859 A
Balanced three-phase power factor at the same slip0.62030.6204

Published Machine 4: balanced current and power factor at s = 0.10

Source: Ćalasan et al. (2020), doi:10.3390/math8061024, Tables 18–19, pp. 17–18. Independent published computed current/PF; measured values are 2.39 A and 0.74. Checks the positive-sequence model at a second load; it is not a Steinmetz measurement.

Inputs: Specify operating load by = Measured operating slip; Operating slip (0.04 = 4%) = 0.1; Motor winding connection = Wye (Y), isolated neutral; Single-phase supply, RMS = 380 V; Rated voltage of one winding = 219.4 V; Rated three-phase line current = 1.86 A; the others as above.

ResultSourceThis calc
Balanced three-phase line current at the same slip2.392 A2.392 A
Balanced three-phase power factor at the same slip0.73750.7376

TPU worked example: 80 µF run, 160 µF total start

Source: TPU Lab 5, p. 6, worked 80 µF run example gives 80–160 µF EXTRA and 160–240 µF TOTAL during starting. This tests the lower endpoint of that example, not the optimum run capacitance.

Inputs: Run capacitor selection = Evaluate an entered capacitor; Entered run capacitance = 80 uF; Specify operating load by = Measured operating slip; Starting bank estimate = Loaded: 2 × run, total; the others as above.

ResultSourceThis calc
Extra starting capacitor (switched out)80 uF80 uF
Total starting bank (run + extra)160 uF160 uF

TPU worked example: 80 µF run, 240 µF total start

Source: TPU Lab 5, p. 6, same worked example, upper endpoint. Distinguishes the extra switched capacitor from the total starting bank.

Inputs: Run capacitor selection = Evaluate an entered capacitor; Entered run capacitance = 80 uF; Specify operating load by = Measured operating slip; Starting bank estimate = Loaded: 3 × run, total; the others as above.

ResultSourceThis calc
Extra starting capacitor (switched out)160 uF160 uF
Total starting bank (run + extra)240 uF240 uF

TPU delta comparison: 3 A winding current is not 3 A line current

Source: Formula-transfer regression from TPU Lab 5, p. 5: I = P/(3 U_phase η cosφ) is winding current. For a stated 3 A winding current (√3 × 3 A delta line current), 240 V supply and 50 Hz, the source's delta rule gives 60 µF. This is an arithmetic check of the cited formula and current convention, not measured Steinmetz performance.

Inputs: Rated three-phase line current = 5.196 A; Single-phase supply, RMS = 240 V; Specify operating load by = Measured operating slip; the others as above.

ResultSourceThis calc
Rated winding current3 A3 A
TPU winding-current comparison60 uF60 uF