Electric Shock: Body Current and IEC 60479 AC/DC Zones

Estimate voltage-dependent body current, compare AC and DC shock zones, and explore RCD clearing and IT earth-contact transients.

#AC/DC #body impedance #electric shock #IEC 60479-1 #IEC 60479-2 #IT systems #RCD

Caution

A low zone is not a safe touch: a real body's impedance and current path can give a far higher current than any case here. Switch off and verify absence of voltage before touching a conductor.

A 600 V DC rail can drive a dangerous current through a person whenever a return path completes the circuit. The voltage alone does not determine the outcome. Body impedance, the contact surfaces, current path, exposure time and the supply’s connection to earth all matter. This electric shock calculator estimates body current and locates the exposure relative to IEC 60479 time–current boundaries.

Start with the source waveform and voltage. AC voltage is an RMS value; the DC option represents smooth direct current. Enter how long contact could persist, then choose dry, water-wet or saltwater-wet skin and a contact area class. The 5th, 50th and 95th percentiles describe the distribution of impedance. Selecting the 95th percentile does not mean a 95% probability of survival. The voltage sweep shows how lower impedance produces higher current.

For a mains AC comparison, change the source to 230 V or 120 V and select 50 Hz or 60 Hz. The comparison table also evaluates AC and DC at the same entered voltage, contact conditions and impedance percentile. At high touch voltage the impedance estimates converge; DC’s higher long-duration fibrillation boundary does not make a 600 V DC contact benign. The zone result describes the governing modeled exposure, including the subdivisions of zone 4. It is not a prediction of an individual person’s response.

Choose the circuit deliberately. Contact across both poles completes a circuit even when the supply floats. An IT first earth contact is limited by insulation resistance and capacitance; a second fault on the other pole can remove that benefit. The DC IT calculation retains the nonlinear steady current and adds a separate RC circuit using a lower body-resistance bound. The comparison table separates the steady leakage zone from a capacitor-discharge VF screen. That screen uses 3τ and peak/√6 for the decaying component. Impulses outside 0.1–10 ms, or contacts ending before 3τ, remain explicitly unassessed. No overall IEC zone is assigned to the combined impulse and leakage.

The 30 mA RCD option uses published maximum AC clearing times. It does not clamp the shock current to 30 mA. No clearing is credited for smooth DC, balanced two-pole contact or an IT first fault. For a suitably rated protection system, enter verified pickup and clearing data, including downstream stored-energy discharge. A Type B designation alone does not establish that a device can interrupt a 600 V DC rail.

The tool is intended for engineering study, teaching and comparison of fault scenarios. Published curves are implemented as numerical approximations, with the source and edition limitations listed below. It does not cover medical electrodes, immersion, arcs, burns, switching waveforms, repeated pulses or installation compliance. Installation work belongs to a qualified person. Check against the standard in force; use isolation and verification of de-energization before any physical contact.

How it is calculated

The body-impedance calculation follows the framework of IEC 60479-1:2018, edition 1.0. Each percentile has a separate log-domain, shape-preserving cubic representation versus touch voltage. Separate AC dry/wet/saltwater and large/medium/small contact families are retained. Dry large-area DC has its own curve; other DC contacts use the AC estimate described in ETSI TR 102 614 V1.1.1, Annex C, pp.17–18. No standard table or artwork is reproduced.

The hand-to-hand impedance is multiplied by the selected hand-to-feet ratio and sensitivity factor. A bracketed nonlinear root solves body voltage with the external return impedance. Initial resistance R₀ is selected for skin bypass or an entered contact shorter than 10 ms. A verified device configured below 10 ms is evaluated using a separate initial-current candidate: R₀ is applied to the reported exposure only if that candidate actually reaches guaranteed pickup. Otherwise the tabulated model and full contact duration remain in force.

Actual body current is compared with reaction boundary a and muscular boundary b. Only fibrillation uses heart-equivalent current F·I, with F=1 for left hand–feet, 0.8 for right hand–feet and 0.4 for hand–hand. The c₁/c₂/c₃ curves are numerical representations of published graphical positions, interpolated smoothly in log time and current. The upward-DC transition is independently checked at 10, 50, 100, 200 and 500 ms against GOST R 70646.1-2023, Figure A.21. Downward longitudinal DC shifts the continuous-current curves by about two. The national cross-check is not equivalent to IEC 60479-1:2018.

A constant-current exposure is assessed at its actual contact or clearing duration. There is no search over prefix RMS windows. Below 10 ms the short-impulse curve approximation is cⱼ=500j·max[1,(0.004/t)^0.7] mA; the DC continuous-curve extension is joined to its own 10 ms endpoint. Short-impulse VF screening uses the separate, polarity-independent impulse representation from ITU-T K.89 (2012), Figure VI.1.

For a symmetric two-pole IT network, the source is half the pole-to-pole voltage and the earth return is [2(1/Rₚ+jωCₚ)]⁻¹. The displayed steady DC current retains the nonlinear body-impedance solve. A separate linear RC screening circuit uses R_floor=min(R₀·k_z, Z(V_available)·k_body), or R₀·k_z in the explicitly initial-resistance state. Since the tabulated impedance decreases with voltage, this is a lower resistance bound over all attainable body voltages. Its steady leakage cannot fall below the nonlinear steady current; this is checked over voltage and impedance percentiles.

The RC screening circuit has C=2Cₚ, R_th=Rₚ/2, R_load=Rₛ+R_floor and τ=C(R_load∥R_th). Its current is I_tail+(I_peak−I_tail)exp(−t/τ). The declining component is assessed separately using tᵢ=3τ and I_equiv=(I_peak−I_tail)/√6, as published in ITU-T K.89, Appendix VI. Two published capacitor examples independently check this conversion. Applicability requires 0.1 ms≤3τ≤10 ms and contact lasting at least 3τ. The table marks other impulses Unassessed. The impulse VF band and the sustained leakage zone are reported separately; no combined IEC zone is assigned. Charge supplied by capacitor release and insulation leakage balances charge through the RC screening circuit analytically.

The 30 mA AC RCD uses maximum times of 300/150/40 ms at ≥1/≥2/≥5 times rated residual current, with no faster interpolation. No trip is credited below guaranteed pickup, for smooth DC, balanced two-pole contact or an IT first fault.

Dalziel's adult lower-tail benchmarks are currents at which 0.5% lost muscular control (99.5% could release); medians correspond to 50%. DC release differs from AC tetanic let-go. These study values do not define a universal duration-independent release threshold. The elapsed-time control moves only the electrical current indication, opening contact and elapsed marker; it never changes the assessed exposure.

Assumptions

Adult external contact, with the selected contact class at both ends. Asymmetric contact areas are not resolved. External series resistance is linear. AC uses the IEC 50/60 Hz body-impedance magnitude as an effective resistance; the IT return retains its complex impedance. Body phase cannot be recovered from magnitude-only data.

The IT supply is symmetric, with equal insulation resistance and capacitance per pole, initially at ±half the rail voltage to earth. Initial imbalance, converters, active insulation-monitor behavior and other earth paths are excluded. An IT first contact receives no automatic clearing credit.

The RC circuit is a lower-resistance screening model, not a simulation of time-varying skin impedance. Its resistance and steady leakage are bounded; its current waveform is not claimed to be a pointwise upper bound for every possible nonlinear or injured-skin response. The impulse calculation applies the published exponential-discharge equivalence to the decaying RC component. The simultaneous DC offset and impulse are not combined into a biological prediction or a formal IEC zone.

The tabulated contact state approximates measurements around 0.1 s. It does not model progressive skin injury, electroporation or exposure-dependent impedance. The sensitivity input explores a reduced impedance without asserting such a time law.

Where it applies

Screening and education, not permission to touch or a protective-device design criterion. Zones 1–3 do not exclude startle, falls, respiratory impairment, burns or other injury. Zone-4 subdivisions and impulse c bands describe conventional approximate VF regions, not individual probabilities. A c₁ ratio below one is not a safety margin.

Source voltage: 25–1000 V. Medium/small contact curves cover 25–200 V across the body. Below 25 V the endpoint is held, generally overestimating current; this is flagged. Contact duration: 0.1 ms–10 s. Pure 50/60 Hz AC and smooth DC only. AC IT switching transients and uncertain body phase require separate assessment.

The IT impulse-equivalence scope is 0.1–10 ms; a completed 3τ discharge must fit inside the contact. Shorter, longer or prematurely interrupted impulses are explicitly unassessed while steady leakage is assessed separately. Even a supported RC impulse band is a screen of the assumed exponential component. It does not establish a combined IEC zone for the superposed impulse and leakage. The comparison table shows the impulse's equivalent RMS current and 3τ, not its peak current or contact duration.

The full licensed IEC 60479-1:2018 text and IEC TS 60479-2:2017 were unavailable for line-by-line verification. Impedances were cross-checked with open ETSI/NHTSA/ASSP material and GOST R 70646.1-2023, which is explicitly not equivalent to IEC 60479-1. The exact 2018 medium/small tables, graphical positions in the original IEC edition and short rectangular-DC polarity corrections remain unverified against those editions. The rebuilt DC transition uses independently read national published positions, with about 6% graphical reading tolerance in its reference cases. The impulse equivalence is verified against ITU worked examples; the current IEC 60479-2:2019 scope confirms the duration limits and supersedes the 2017 TS.

Graphical fits do not support precision trip settings. Explore at least 15% uncertainty in current; this is not a validated error bound. Check against the standard in force. The 30 mA RCD example follows the cited manufacturer's non-delayed AC envelope, not a current installation-compliance determination. Smooth DC needs compatible detection and DC-rated interruption or a verified system that removes stored energy. Upstream AC interruption can leave the DC bus charged. IT monitoring does not guarantee clearing or harmless capacitive contact.

All RC integrations and equivalence conversions are analytic. The time-curve sample input controls picture resolution only; it no longer controls a clinical window search or a time-stepping solve. Voltage sweeps use 181 solved points by default. Charge balance and resistance/leakage bounds are checked without a transient time grid.

References

  • IEC 60479-1:2018, edition 1.0, Effects of current on human beings and livestock—General aspects. Official scope: https://webstore.iec.ch/en/publication/62980
  • IEC TS 60479-2:2017, edition 4.0; superseded by IEC 60479-2:2019, edition 1.0. Official scope: https://webstore.iec.ch/en/publication/63392
  • ETSI TR 102 614 V1.1.1 (2010-06), Annex C, pp.17–18: https://www.etsi.org/deliver/etsi_tr/102600_102699/102614/01.01.01_60/tr_102614v010101p.pdf
  • Stephens, Stout and Taylor, NHTSA DOT HS 812 134 (2015), §§2.1–2.3: https://www.nhtsa.gov/sites/nhtsa.gov/files/812134-hydrogenfuelcellvehelecprotbaroptfuelsyssfty.pdf
  • Ricketts, The Case of the Fatal Ground Fault, Professional Safety, October 2021, pp.34–36: https://www.assp.org/docs/default-source/psj-articles/mtricketts_1021.pdf?sfvrsn=ba189b47_0
  • Wylex, Lifeline Range RCDs—Technical Data, printed p.47 (PDF p.49), published IEC curves and maximum trip times: https://storage.electrika.com/manu/man-0150/pdftech/0150-dcp-18.pdf
  • Dalziel, Deleterious Effects of Electric Shock (1961), experimental results reproduced with author permission in LBL Electrical Safety, PUB-3029 (1985), p.8-10: https://escholarship.org/content/qt46b4t4zr/qt46b4t4zr.pdf
  • ITU-T K.89 (05/2012), Appendix VI, Figure VI.1 and worked impulse examples, printed p.37: https://www.itu.int/rec/dologin_pub.asp?id=T-REC-K.89-201205-I!!PDF-E&lang=e&type=items
  • Maytum, Shocking Electricity 2, ATIS PEG (2018), IEC TS 60479-2 discussion: https://peg.atis.org/wp-content/uploads/2018/08/Effects_of_Current_on_Human_Beings_and_Livestock-MMaytum.pdf
  • Schneider Electric, Electrical Installation Guide, IT system principle and DC leakage/RCD compatibility (pages updated 2026): https://www.electrical-installation.org/enwiki/IT_system_-_Principle ; https://www.electrical-installation.org/enwiki/RCDs_selection_in_presence_of_DC_earth_leakage_currents
  • GOST R 70646.1-2023, numerical cross-check only; non-equivalent national document based on IEC 60479-1:2018: https://normadocs.ru/gost_r_70646.1-2023

Inputs

InputSymbolUnitDefault
Supply waveformwaveSmooth DC
Source voltage
AC is RMS; an IT source is measured between its two poles.
U_sV600
Contact durationt_contacts1
Circuit and returnsystemEarth-referenced return
Skin conditionskinDry
Contact area class
Both contacts use this class; medium and small curves end at 200 V.
areaLarge, about 10 000 mm²
Body current pathpathLeft hand to feet
Impedance percentile
These are impedance ranks, not survival probabilities.
percentile50th: median
Skin impedance stateskin_stateIEC tabulated contact state
External series resistance
Include source, footwear and any known fault-return resistance.
R_sohm0
Disconnection modelprotectNo automatic clearing
Guaranteed pickup current
Use the guaranteed threshold for this waveform, including DC where relevant.
I_pickmA60
Maximum clearing time
Include detection, opening and removal of downstream stored energy.
t_devices0.3
Insulation resistance per pole
Symmetric pole-to-earth insulation before contact.
R_pohm1000000
Capacitance per pole to earth
Include cables and filters; each pole starts at half the supply voltage.
C_puF0.1
Hand-to-feet impedance ratio
IEC reports a 10–30% reduction from hand-to-hand impedance.
k_path0.8
Impedance sensitivity factor
Explore impedance reduction with exposure; no time-dependent skin injury model is implied.
k_z1
Time-curve samplesn_t601
Voltage-sweep samplesn_v181
DC longitudinal direction
Conventional current direction; the downward VF boundary is about twice the upward one.
dc_dirDownward: hand positive
Elapsed contact time
Moves the electrical indication; the assessment uses the entire entered exposure.
t_shows0.0001

Results

With the default inputs above, the calc gives:

ResultValue
Exposure assessmentDC-4.3
Steady body current942.358 mA
Voltage across body600 V
Total body impedance636.701 Ω
Exposure after clearing1 s
Sustained c₁ current ratio3.141
Heart-current factor1
Disconnection assessmentContact lasts as entered

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

ETSI wet contact at 50 V

Source: ETSI TR 102 614 V1.1.1 (2010), Annex C, printed p.18: median large-area wet hand-to-hand impedance at 50 V.

Inputs: Source voltage = 50 V; Supply waveform = AC 50 Hz; Skin condition = Water-wet; Body current path = Hand to hand; the others as above.

ResultSourceThis calc
Total body impedance2,000 Ω2,000 Ω
Steady body current25 mA25 mA

ETSI wet contact at 150 V

Source: ETSI TR 102 614 V1.1.1 (2010), Annex C, printed p.18: independent published median wet impedance.

Inputs: Source voltage = 150 V; Supply waveform = AC 60 Hz; Skin condition = Water-wet; Body current path = Hand to hand; the others as above.

ResultSourceThis calc
Total body impedance1,400 Ω1,400 Ω
Steady body current107.1 mA107.1 mA

ASSP worked example: saltwater, lower impedance

Source: Ricketts, The Case of the Fatal Ground Fault, Professional Safety (Oct 2021), worked 225 V saltwater-wet hand-to-hand example: 770 Ω and 0.292 A rounded. https://www.assp.org/docs/default-source/psj-articles/mtricketts_1021.pdf?sfvrsn=ba189b47_0

Inputs: Source voltage = 225 V; Supply waveform = AC 50 Hz; Skin condition = Saltwater-wet; Body current path = Hand to hand; Impedance percentile = 5th: lower impedance; the others as above.

ResultSourceThis calc
Total body impedance770 Ω770 Ω
Steady body current292.2 mA292.2 mA

ASSP worked example: median impedance

Source: Ricketts (2021), same independent worked example: median impedance 1115 Ω, current 0.202 A rounded. Published input and impedance are used without changing the physics.

Inputs: Source voltage = 225 V; Supply waveform = AC 50 Hz; Skin condition = Saltwater-wet; Body current path = Hand to hand; the others as above.

ResultSourceThis calc
Total body impedance1,115 Ω1,115 Ω
Steady body current201.8 mA201.8 mA

ASSP worked example: higher impedance

Source: Ricketts (2021), same independent worked example: 95th impedance percentile 1505 Ω; 225/1505 A. The percentile is an impedance rank, not a survival probability.

Inputs: Source voltage = 225 V; Supply waveform = AC 60 Hz; Skin condition = Saltwater-wet; Body current path = Hand to hand; Impedance percentile = 95th: higher impedance; the others as above.

ResultSourceThis calc
Total body impedance1,505 Ω1,505 Ω
Steady body current149.5 mA149.5 mA

Published RCD envelope above rated pickup

Source: Wylex, Lifeline Range RCDs—Technical Data, printed p.47: 300 ms at IΔn. Body current is between 30 and 60 mA; the next faster point cannot be credited.

Inputs: Source voltage = 75 V; Supply waveform = AC 50 Hz; Skin condition = Water-wet; Body current path = Hand to hand; Disconnection model = 30 mA AC/A RCD, non-delayed; the others as above.

ResultSourceThis calc
Exposure after clearing0.3 s0.3 s

Published RCD envelope above twice pickup

Source: Wylex, printed p.47: maximum 150 ms at 2IΔn. At 125 V the modeled body current exceeds 60 mA and remains below 150 mA.

Inputs: Source voltage = 125 V; Supply waveform = AC 50 Hz; Skin condition = Water-wet; Body current path = Hand to hand; Disconnection model = 30 mA AC/A RCD, non-delayed; the others as above.

ResultSourceThis calc
Exposure after clearing0.15 s0.15 s

Published RCD envelope above five times pickup

Source: Wylex, printed p.47: maximum 40 ms at 5IΔn. This is a clearing-time reference, not a claim that injury is excluded.

Inputs: Source voltage = 225 V; Supply waveform = AC 60 Hz; Skin condition = Water-wet; Body current path = Hand to hand; Disconnection model = 30 mA AC/A RCD, non-delayed; the others as above.

ResultSourceThis calc
Exposure after clearing0.04 s0.04 s

NHTSA worked series-isolation example

Source: NHTSA DOT HS 812 134 (2015), printed p.12, §2.3: 500 V source, 50 000 Ω isolation in series, 500 Ω body; current 500/50 500 A, stated as no greater than 10 mA. https://www.nhtsa.gov/sites/nhtsa.gov/files/812134-hydrogenfuelcellvehelecprotbaroptfuelsyssfty.pdf

Inputs: Source voltage = 500 V; Body current path = Hand to hand; Impedance percentile = 5th: lower impedance; Skin impedance state = Skin bypassed: initial resistance; External series resistance = 50,000 Ω; the others as above.

ResultSourceThis calc
Steady body current9.901 mA9.901 mA

NHTSA worked direct-voltage example

Source: NHTSA DOT HS 812 134 (2015), printed p.12: 500 V directly across a 500 Ω body gives 1000 mA; isolation in a parallel branch does not limit that current. No residual imbalance is assumed for contact across both supply poles.

Inputs: Source voltage = 500 V; Body current path = Hand to hand; Impedance percentile = 5th: lower impedance; Skin impedance state = Skin bypassed: initial resistance; Circuit and return = Contact across both supply poles; Disconnection model = 30 mA AC/A RCD, non-delayed; the others as above.

ResultSourceThis calc
Steady body current1,000 mA1,000 mA
Exposure after clearing1 s1 s

ITU independent short-impulse example

Source: ITU-T K.89 (05/2012), printed p.37, Appendix VI: c₂ example at 3.024 ms is 1.2 A RMS. The numerical curve representation gives about 1.216 A; the 2% tolerance covers graph-fit/rounding accuracy.

Inputs: DC longitudinal direction = Upward: feet positive; the others as above.

ResultSourceThis calc
Short-impulse c₂ check at 3.024 ms1,200 ± 24 mA1,216 mA

Published small-contact worked example

Source: GOST R 70646.1-2023, Table 7 and Annex K example 2, 100 V dry small hand-to-hand contact: 40 000 Ω, 2.5 mA. Cross-check only; this national document is NEQ to IEC 60479-1:2018 and does not verify that edition. https://normadocs.ru/gost_r_70646.1-2023

Inputs: Source voltage = 100 V; Supply waveform = AC 50 Hz; Contact area class = Small, about 100 mm²; Body current path = Hand to hand; the others as above.

ResultSourceThis calc
Total body impedance40,000 Ω40,000 Ω
Steady body current2.5 mA2.5 mA

Published upward DC boundaries at 10 ms

Source: Independent graphical reading of GOST R 70646.1-2023 Figure A.21 (longitudinal upward DC), https://normadocs.ru/gost_r_70646.1-2023 . Approximate positions read from the published plot; absolute tolerance is 6% for line thickness and log-axis reading. This national source is NEQ to IEC 60479-1:2018; these are not normative IEC tabular values.

Inputs: DC longitudinal direction = Upward: feet positive; Contact duration = 0.01 s; the others as above.

ResultSourceThis calc
Published DC c1 comparison500 ± 30 mA500 mA
Published DC c2 comparison1,000 ± 60 mA1,000 mA
Published DC c3 comparison1,400 ± 84 mA1,400 mA

Published upward DC boundaries at 50 ms

Source: Independent graphical reading of GOST R 70646.1-2023 Figure A.21 (longitudinal upward DC), https://normadocs.ru/gost_r_70646.1-2023 . Approximate positions read from the published plot; absolute tolerance is 6% for line thickness and log-axis reading. This national source is NEQ to IEC 60479-1:2018; these are not normative IEC tabular values.

Inputs: DC longitudinal direction = Upward: feet positive; Contact duration = 0.05 s; the others as above.

ResultSourceThis calc
Published DC c1 comparison450 ± 27 mA450 mA
Published DC c2 comparison900 ± 54 mA900 mA
Published DC c3 comparison1,200 ± 72 mA1,200 mA

Published upward DC boundaries at 100 ms

Source: Independent graphical reading of GOST R 70646.1-2023 Figure A.21 (longitudinal upward DC), https://normadocs.ru/gost_r_70646.1-2023 . Approximate positions read from the published plot; absolute tolerance is 6% for line thickness and log-axis reading. This national source is NEQ to IEC 60479-1:2018; these are not normative IEC tabular values.

Inputs: DC longitudinal direction = Upward: feet positive; Contact duration = 0.1 s; the others as above.

ResultSourceThis calc
Published DC c1 comparison350 ± 21 mA350 mA
Published DC c2 comparison625 ± 37.5 mA625 mA
Published DC c3 comparison825 ± 49.5 mA825 mA

Published upward DC boundaries at 200 ms

Source: Independent graphical reading of GOST R 70646.1-2023 Figure A.21 (longitudinal upward DC), https://normadocs.ru/gost_r_70646.1-2023 . Approximate positions read from the published plot; absolute tolerance is 6% for line thickness and log-axis reading. This national source is NEQ to IEC 60479-1:2018; these are not normative IEC tabular values.

Inputs: DC longitudinal direction = Upward: feet positive; Contact duration = 0.2 s; the others as above.

ResultSourceThis calc
Published DC c1 comparison270 ± 16.2 mA270 mA
Published DC c2 comparison390 ± 23.4 mA390 mA
Published DC c3 comparison550 ± 33 mA550 mA

Published upward DC boundaries at 500 ms

Source: Independent graphical reading of GOST R 70646.1-2023 Figure A.21 (longitudinal upward DC), https://normadocs.ru/gost_r_70646.1-2023 . Approximate positions read from the published plot; absolute tolerance is 6% for line thickness and log-axis reading. This national source is NEQ to IEC 60479-1:2018; these are not normative IEC tabular values.

Inputs: DC longitudinal direction = Upward: feet positive; Contact duration = 0.5 s; the others as above.

ResultSourceThis calc
Published DC c1 comparison180 ± 10.8 mA180 mA
Published DC c2 comparison270 ± 16.2 mA270 mA
Published DC c3 comparison350 ± 21 mA350 mA

350 V upward DC crosses c₁ at 100 ms

Source: Regression against Figure A.21 of GOST R 70646.1-2023: at 100 ms the upward-DC c₁ is about 350 mA and c₂ about 625 mA. The independently calculated 432 mA contact lies between them (DC-4.1). https://normadocs.ru/gost_r_70646.1-2023

Inputs: Source voltage = 350 V; DC longitudinal direction = Upward: feet positive; Contact duration = 0.1 s; the others as above.

ResultSourceThis calc
Governing zone index44

A non-tripping fast device preserves tabulated impedance

Source: Regression using the dry small-contact median at 25 V from GOST R 70646.1-2023 (169 kΩ) and Ohm's law: 0.147929 mA. It is below a 60 mA guaranteed pickup; an unused configured 5 ms clearing time must not replace that impedance with R₀. https://normadocs.ru/gost_r_70646.1-2023

Inputs: Source voltage = 25 V; Contact area class = Small, about 100 mm²; Body current path = Hand to hand; Disconnection model = Verified device clearing data; Maximum clearing time = 0.005 s; the others as above.

ResultSourceThis calc
Steady body current0.1479 ± 0.001 mA0.1479 mA
Exposure after clearing1 s1 s
Governing zone index11

ITU published 3 A capacitor-discharge example

Source: ITU-T K.89 (2012), Table VI.1, printed p.37: 700 µs half-value, 3.024 ms equivalent duration, 3 A peak and 1.2 A RMS. The exact peak/√6 conversion is 1.224745 A; 2.5% tolerance covers the published rounding. https://www.itu.int/rec/dologin_pub.asp?id=T-REC-K.89-201205-I!!PDF-E&lang=e&type=items

Inputs: the default inputs above.

ResultSourceThis calc
ITU 700 µs example equivalent duration0.003024 s0.003024 s
ITU 3 A example equivalent RMS current1,200 ± 30 mA1,225 mA

ITU published 5 A capacitor-discharge example

Source: ITU-T K.89 (2012), Table VI.1, printed p.37: 350 µs half-value, 1.512 ms equivalent duration, 5 A peak and 2 A RMS. Exact conversion is 2.041241 A; tolerance covers the table's rounding. https://www.itu.int/rec/dologin_pub.asp?id=T-REC-K.89-201205-I!!PDF-E&lang=e&type=items

Inputs: the default inputs above.

ResultSourceThis calc
ITU 350 µs example equivalent duration0.001512 s0.001512 s
ITU 5 A example equivalent RMS current2,000 ± 50 mA2,041 mA

A 4.49 µs RC impulse remains unassessed

Source: Scope regression: IEC 60479-2:2019 official scope limits these impulse values to 0.1–10 ms. For the stated IT circuit, 3τ≈4.49 µs is outside scope. Code 0 must flag an unassessed impulse; zone index 1 assesses only the separately calculated steady leakage. https://webstore.iec.ch/en/publication/63392

Inputs: Circuit and return = IT first earth contact; Capacitance per pole to earth = 0.001 uF; the others as above.

ResultSourceThis calc
Impulse applicability code00
Governing zone index11

Long IT transient does not conceal sustained DC-4.3

Source: Review regression. The independent nonlinear circuit gives about 571.7 mA sustained current, above the downward-DC c₃≈560 mA in GOST R 70646.1-2023 Figure A.21 at 10 s. The 3τ impulse is longer than IEC 60479-2's 10 ms applicability limit and must be separately marked unassessed. https://normadocs.ru/gost_r_70646.1-2023 ; https://webstore.iec.ch/en/publication/63392

Inputs: Source voltage = 830 V; Circuit and return = IT first earth contact; Insulation resistance per pole = 100 Ω; Capacitance per pole to earth = 1,000 uF; Hand-to-feet impedance ratio = 0.7; Contact duration = 10 s; the others as above.

ResultSourceThis calc
Impulse applicability code00
Governing zone index66

Contact shorter than 3τ is not a complete discharge

Source: Method regression: the capacitor-discharge equivalence uses the full assumed 3τ duration (ITU-T K.89, Appendix VI). A contact interrupted sooner is not that waveform and must remain unassessed by this equivalence. https://www.itu.int/rec/dologin_pub.asp?id=T-REC-K.89-201205-I!!PDF-E&lang=e&type=items

Inputs: Circuit and return = IT first earth contact; Contact duration = 1 × 10⁻⁴ s; the others as above.

ResultSourceThis calc
Impulse applicability code-2-2

An actually tripping fast device uses the initial-current state

Source: Physics regression paired with the non-pickup case. IEC initial median resistance R₀=750 Ω gives 600/750=0.8 A, above 60 mA pickup; the verified clearing time is 5 ms. This is an assumed device example, not a published protective-device performance claim. R₀ population values follow the cited IEC/GOST framework, https://normadocs.ru/gost_r_70646.1-2023

Inputs: Contact area class = Small, about 100 mm²; Body current path = Hand to hand; Disconnection model = Verified device clearing data; Maximum clearing time = 0.005 s; the others as above.

ResultSourceThis calc
Steady body current800 mA800 mA
Total body impedance750 Ω750 Ω
Exposure after clearing0.005 s0.005 s