Fridge, Freezer and Mini-Split Solar & Power Station Calculator
Size battery backup and solar panels for a fridge, freezer or mini-split. Check compressor starting capacity and explore daily PV, cycling loads and battery charge.
Use this calculator to estimate whether a power station can keep a fridge, freezer or inverter mini-split running, and how much solar capacity is needed to replace the energy. It separates three questions: daily electricity use, battery endurance, and the inverter capacity needed when the compressor starts. Engineers, students, householders and off-grid users can compare assumptions before measuring or specifying equipment.
For a fridge or freezer, start with its annual energy label or a measured daily total. Measured-cycle mode is restricted to appliances whose cooling and standby states account for all daily energy; confirm this before using it. Enter kWh per year directly; for a measured 24-hour total, multiply the measured kWh by 365 and use the label method. A meter reading over several representative days is better than estimating from maximum nameplate watts. Annual energy already includes test-cycle auxiliaries and defrost. An automatic-defrost fridge with unaccounted heater or ice-maker energy needs the measured daily-total route; maximum non-start watts add no daily energy.
In the measured-cycle method, enter the room temperature during measurement, the expected room temperature and the cabinet temperature. The calculator scales duty with the temperature difference across the cabinet, assuming unchanged cooling capacity and COP. This is a simple heat-leak sensitivity estimate. Door openings, humidity, ice making and compressor efficiency can change the real result. Full duty means the appliance may no longer maintain its target temperature.
For solar for a mini split, enter thermal capacity, the required fraction of that capacity, operating hours and the COP at the chosen part load and ambient temperature. Below minimum modulation, the model cycles the unit. Manufacturer operating-point data or measured electrical input are needed; seasonal efficiency ratings do not specify one operating point.
To answer “can a power station run a fridge,” enter battery capacity, reserve, initial charge, conversion efficiency and inverter idle draw. Check W and VA ratings, maximum-load power factor, and surge duration. Clear the maximum-load PF checkbox if this information is unknown; the screen then remains incomplete. Starting-current multiples vary substantially. A compatible soft-start or inverter compressor can help, but its benefit must be entered from verified data. The capacity screen uses apparent power as a conservative upper bound on starting watts and does not certify successful startup.
To work out how many solar panels to run a refrigerator, enter design-month peak sun hours, the PV derate and solar input limit. Panel sizing covers daily use and optionally recovery of the required backup energy while supplying the ongoing load. The animated schematic and event-based battery charts show an illustrative day, including unused PV and unmet demand. Dispatch resolves compressor switches and PV/load crossings before applying charging losses or storage limits. Average-load backup hours do not predict the exact shutdown time for a short cooling window.
This is an energy and inverter screening tool. It does not calculate food temperature, food safety, refrigerant behavior, wiring, battery current limits or a site's weather reliability. Recheck the worst season and actual equipment limits. Installation work, fixed wiring and transfer arrangements belong to a qualified person.
How it is calculated
Annual-label mode divides the entered kWh/year by 365. For measured total electricity, enter representative daily kWh times 365; that route includes defrost, ice making and other metered auxiliaries. Measured-cycle mode integrates over 24 hours and requires confirmation that these two states account for all daily energy. It is unsuitable for unaccounted defrost or auxiliary loads. Maximum non-start watts affect inverter sizing only.
Measured-cycle duty is adjusted by and capped at unity. This sensitivity is derived from constant cabinet conductance, cooling capacity and COP, not fitted to a refrigerator data set.
For the inverter mini-split, on-state electrical input is rated thermal capacity times the larger of demand fraction and minimum modulation, divided by operating-point COP. Below minimum modulation the duty is demand/minimum fraction. Outside the entered daily cooling window only appliance standby remains. Standby is already included in on-state watts. Compressor periods are fitted to an integer number of cycles within the window.
Average DC demand is average AC demand divided by inverter efficiency plus continuous DC idle draw. Available battery energy is nominal Wh times initial SOC above the reserve floor. No-sun endurance is available Wh divided by average DC W. Required nominal storage assumes starting full and discharging to reserve.
Running and maximum non-start apparent powers are calculated separately: and . Continuous inverter VA must cover the larger, plus the other steady load. If maximum-load PF is unknown, clear its availability checkbox: the inverter screen then stays incomplete. Starting VA comes from known starting current times voltage, or running VA times an entered current multiple. Continuous W, continuous VA, surge VA and duration are screened separately. Surge VA also provides a conservative upper bound on real starting watts; exceeding that bound does not prove an actual start fails.
PV nameplate sizing assumes all load energy passes through charging, conservatively dividing by charging efficiency, PV derate and peak sun hours. Recovery adds the requested backup energy divided by recovery days. Inspect the timeline for input clipping, battery-full curtailment and unmet demand.
For dispatch, accepted PV is piecewise linear between five-minute knots on the illustrative solar curve. Exact compressor switching times and cooling-window boundaries are merged with these knots. Each segment is split again wherever PV equals DC demand. Positive and negative energy flows are integrated separately; charging efficiency applies only to stored surplus. Full-charge and reserve hits are solved within each segment and recorded in the battery and cumulative-energy traces. Later surplus cannot erase earlier unmet demand. Only the power chart uses five-minute load and PV averages. The animated schematic samples the event results without recomputing dispatch.
Assumptions
One cooling appliance plus a steady unity-power-factor AC load. All quantities are user scenarios, not product presets. Default 475 kWh/year, 150 W running draw and a starting-current multiple of five are illustrative and must be replaced for equipment selection. Default maximum-load PF 0.8 is an explicit illustrative assumption. Clear the PF availability checkbox if no data or justified assumption is available. No soft-start or inverter-compressor surge reduction is assumed.
Annual-label cycles are energy-equivalent illustrations; they do not reconstruct a real compressor or defrost schedule. Label-mode temperature is not adjusted because the test climate and cabinet conductance are unknown. The measured-cycle temperature model assumes a single compartment and unchanged COP; combined fridge/freezer heat loads and high-ambient capacity loss require measurements. Mini-split COP is supplied at the chosen ambient and part load; it is not inferred from SEER.
Inverter efficiency is constant and excludes the separately entered idle draw. Battery capacity includes aging and thermal derating supplied by the user; no Peukert model or BMS dynamics are included. Keep AC outputs enabled for cycling loads; some power stations turn off at low draw.
Measured-cycle mode has no separate heater or auxiliary schedule. Its energy-completeness confirmation is mandatory; an automatic-defrost fridge with unaccounted heater energy must use metered daily-total energy via annual mode.
The PV curve is an idealized repeatable day centered on noon, approximated linearly between five-minute knots, with no cloud forecast. The energy dispatch assumes compatible simultaneous solar charging and AC output, adequate DC/BMS power capability, and no inverter trip. Low-battery and unmet-demand traces are energy accounting, not an appliance restart simulation.
Where it applies
Use for preliminary energy budgeting and capacity screening of AC compressor appliances within their manufacturer's operating limits. Results do not establish startup compatibility: verify waveform, voltage, frequency, motor current, surge duration, ambient derating, BMS discharge limits and equipment warranties. Do not substitute a resistive-load voltage-reduction boost rating for motor-start capacity.
The temperature correction is a first-order cabinet heat-leak estimate only. A duty of one flags potentially inadequate cooling. The mini-split model assumes the supplied COP applies while running at the modeled modulation point and does not model humidity, solar gains, transient room pull-down, cycling degradation or heating/defrost operation.
Average-load no-sun hours and storage sizing use the entire daily schedule. Exact endurance during a short outage depends on its start time. A single sunny day cannot prove indefinite service or recovery after several cloudy days. When the input limit clips PV, the panel count is a lower-bound nameplate estimate requiring further time-series design. Event dispatch resolves compressor switches, PV/load crossings and storage bounds within the piecewise-linear PV model. It does not simulate subsecond motor-start transients or battery power limits. The energy balance remains conditional on successful inverter operation.
The Solar Lab's measured totals support the scale of daily demand, but its running-watt and one-sixth-duty statements do not reproduce those totals; no universal divide-by-six rule is used. Virginia Tech's example validates electrical energy integration, not its generic refrigerator duty or voltage-times-current shortcut. Use true watts for energy and VA for inverter loading. GE documents a defrost heater operating while the compressor is off; compressor cycling alone does not capture its electricity. Measured-cycle mode must not be used with unaccounted defrost or auxiliary loads. Food temperature and food safety are outside this model. Installation work belongs to a qualified person.
References
- The Solar Lab, How Much Power Does Your Fridge Actually Use? Original 24-hour measurements; reported 1.3–1.33 kWh/day. https://www.thesolarlab.com/how-tos/how-much-power-does-your-fridge-use
- Cleversolarpower by Nick, How Many Solar Panels To Run a Fridge/Freezer? (14 March 2024). Original test and sizing workflow; video description identifies inverter idle draw and days of autonomy. https://www.youtube.com/watch?v=1hC_twV7Ces
- PECRON, How Long Will a Portable Power Station Run? Manufacturer's steady 120 W / 1024 Wh example, 7.25 h at an aggregate 85% planning factor. https://www.pecron.com/blogs/news/how-long-will-a-portable-power-station-run
- Jackery Australia, 4 Best Battery Backup For Refrigerators During Power Outages. Manufacturer's 2042.8 Wh, 400 W, 85% worked example gives 4.3 h rounded. https://au.jackery.com/blogs/buying-advice/battery-backup-for-refrigerator
- Victron Energy, Help me choose the right inverter/charger. Primary manufacturer guidance on continuous load, compressor start, watts versus VA, derating and DC-side capability. https://www.victronenergy.com/inverters-chargers/help-me-choose
- Grisso and Walker, Virginia Cooperative Extension, ENERGY SERIES: Estimating Appliance and Home Electronic Energy Use, 2009, publication 2901-9014, p. 1. 200 W window-fan energy example; quoted reference case attached. https://vtechworks.lib.vt.edu/bitstreams/a283e5b3-4ce7-4b23-b7b3-7dbaea0e6e6e/download
- GE Appliances, Refrigerator - Automatic Defrost System. Primary manufacturer explanation: defrost heater operation is separate from compressor and fans. https://products.geappliances.com/appliance/gea-support-search-content?contentId=16679
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| Appliance energy method One appliance, plus an optional steady AC load. Annual labels are test-condition estimates; measured daily energy is preferable. | energy_method | Fridge / freezer: annual energy label | |
| Annual appliance electricity Enter the label's kWh per year. For a measured day, multiply its kWh by 365. Includes defrost and auxiliaries. | E_year | kWh | 475 |
| Compressor running power Measured true watts while cooling. Maximum label watts or voltage × current do not give average energy. Defrost/auxiliary events are not added in measured-cycle mode. | P_meas | W | 150 |
| Appliance power when not cooling Controls and standby power; included throughout the day. | P_off | W | 2 |
| Measured compressor duty fraction Fraction of time cooling at the reference temperature. Use only when cooling plus standby capture all daily energy; separate defrost and auxiliary events are excluded. | D_ref | 0.4 | |
| Cooling and standby account for all daily energy Required for this method. Separate defrost, ice-maker and other auxiliary events are not modeled. If any energy is unaccounted, measure total kWh over representative days and enter daily kWh × 365 in the annual-energy method. | cycle_energy_complete | false | |
| Room temperature during duty measurement Reference ambient for the simple heat-leak adjustment. | T_ref | degC | 25 |
| Expected room temperature Duty scales with ambient-to-cabinet temperature difference at constant cooling capacity and COP. | T_amb | degC | 32 |
| Cabinet temperature Use about 4 °C for a fridge or −18 °C for a freezer. A combined fridge/freezer needs measured energy. | T_cab | degC | 4 |
| Rated cooling capacity Thermal cooling capacity, not electrical input watts. | Q_rated | kW | 3.5 |
| Required cooling / rated capacity Enter the room's estimated part-load cooling demand as a fraction of rated capacity. | load_frac | 0.5 | |
| COP at this ambient and part load Cooling watts divided by electrical watts at this operating point. Use manufacturer data or measurements; seasonal SEER is not this COP. | COP_part | 4 | |
| Minimum modulation / rated capacity Below this thermal output the unit cycles at its minimum modulation. Verify the unit's data. | min_frac | 0.2 | |
| Daily cooling window Cooling is enabled for this many hours each day; standby power remains outside the window. | h_use | h | 8 |
| Cooling window starts at Local clock hour, with midnight = 0. The window must end by midnight. | h_start | h | 10 |
| Illustrative compressor cycle period The energy model integrates partial cycles exactly. Timing is illustrative, not a thermostat simulation. | cycle_time | h | 1 |
| Maximum non-start appliance draw Maximum instantaneous non-start total, including pull-down or defrost. Enter its PF separately. This checks inverter capacity only and adds no daily energy; use measured daily totals for unaccounted auxiliary loads. | P_peak | W | 350 |
| Use an entered maximum-load power factor Clear this if maximum-load PF is unknown and no justified conservative assumption is available. The inverter screen then stays incomplete. | peak_pf_available | true | |
| Maximum non-start load power factor PF for the P_peak operating condition, including pull-down, electronics or a defrost heater. Default 0.8 is an illustrative assumption; enter measured or specified data. | PF_peak | 0.8 | |
| Other steady AC load Assumed unity power factor and on for 24 hours. | P_other | W | 0 |
| Running power factor True watts / apparent VA at compressor running point. | PF_run | 0.8 | |
| Compressor starting data A soft-start or inverter compressor needs its own verified starting data. No reduction is assumed. | start_method | Starting current / running current | |
| Starting-current multiplier Illustrative assumption only. Replace with data or a measurement, including any soft-start. | start_mult | 5 | |
| Starting current Locked-rotor current is conservative if no measured transient is available. | I_start | A | 8 |
| AC output voltage Must match the appliance's required voltage and frequency. | V_ac | V | 230 |
| Required surge duration Use the compressor's measured or specified startup duration. | t_start | s | 1 |
| Inverter continuous real-power rating Use the derated rating at the expected ambient temperature. | W_cont | W | 1500 |
| Inverter continuous apparent-power rating Enter VA or the manufacturer's continuous current limit times voltage. Do not silently treat W as VA. | S_cont | VA | 1500 |
| Inverter surge real-power rating Only use a surge rating that applies for the entered duration, not a resistive-load boost mode. | W_surge | W | 3000 |
| Inverter surge apparent-power rating Check current/VA capability for motor loads with the manufacturer. | S_surge | VA | 3000 |
| Inverter rated surge duration Duration for which both entered surge ratings apply. | t_surge | s | 2 |
| Nominal battery capacity Use remaining capacity after aging and temperature derating. This is DC nameplate energy, not measured AC output. | C_batt | Wh | 2000 |
| Usable depth of discharge 0.9 leaves a 10% nominal-capacity reserve. Avoid subtracting a reserve twice if the station already excludes it. | DoD | 0.9 | |
| Initial state of charge Fraction of nominal energy at midnight, before the plotted day. | SOC_initial | 1 | |
| Inverter conversion efficiency Exclude idle draw, which is entered separately. For an aggregate 85% planning factor use 0.85 and zero idle draw. | eta_inv | 0.9 | |
| Inverter DC idle draw Consumed continuously, even while the compressor is off. Disable AC auto-shutoff for cycling loads. | P_idle | W | 8 |
| Required no-sun backup duration Sizing uses the daily-average load; short windows depend on compressor and AC schedule phase. | backup_hours | h | 24 |
| One panel's rated power STC panel nameplate. The array's weather and controller losses are separate. | P_panel | W | 200 |
| Installed panel count Use zero for battery-only operation. | N_panel | 4 | |
| Peak sun hours per day Equivalent full-sun hours on the array plane for the design month, not daylight hours. | PSH | h | 4 |
| Sunrise-to-sunset duration Illustrative smooth PV day, symmetric around noon. | daylight | h | 12 |
| PV-to-DC-bus derate Combined panel temperature, shade, dirt, wiring and controller derate. Inverter and battery charging losses are separate. | derate_pv | 0.8 | |
| Maximum accepted solar input Clips the plotted DC input. Also check MPPT voltage, short-circuit current and panel-series limits separately. | P_pv_limit | W | 1000 |
| Battery charging efficiency Applied to PV surplus stored in the battery. PV serving the DC load directly avoids this loss. | eta_charge | 0.95 | |
| Sunny days to recover backup energy Panels cover ongoing daily load plus the energy used during the required no-sun backup. | recovery_days | day | 3 |
| Day timeline — press ▶ Move through the illustrative day. Sizing and the battery dispatch are cached while playing. | clock_hour | h | 18 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Total daily AC energy | 1.3 kWh |
| No-sun backup at average load | 26.4 h |
| Battery from full for required backup | 1,820 Wh |
| Inverter capacity screen | Within entered ratings; verify startup |
| Required start capability | 938 VA |
| Panels: daily load + backup recovery | 4 |
| PV nameplate before panel rounding | 718 W |
| Unmet DC demand, AC-equivalent | 0 Wh |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
PECRON: 1024 Wh at steady 120 W
Source: PECRON, How Long Will a Portable Power Station Run?, worked example: 1024 Wh × 0.85 / 120 W = 7.25 h (rounded). This validates a steady load, not a universal fridge duty cycle. https://www.pecron.com/blogs/news/how-long-will-a-portable-power-station-run
Inputs: Appliance energy method = Fridge / freezer: measured watts and cycles; Compressor running power = 120 W; Appliance power when not cooling = 0 W; Measured compressor duty fraction = 1; Expected room temperature = 25 °C; Nominal battery capacity = 1,024 Wh; Usable depth of discharge = 1; Inverter conversion efficiency = 0.85; Inverter DC idle draw = 0 W; Cooling and standby account for all daily energy = yes; the others as above.
| Result | Source | This calc |
|---|---|---|
| No-sun backup at average load | 7.25 ± 0.01 h | 7.253 h |
Jackery: 2042.8 Wh at steady 400 W
Source: Jackery Australia, 4 Best Battery Backup For Refrigerators During Power Outages: 2042.8 Wh × 0.85 / 400 W = 4.3 h. Rounded continuous-draw example, not measured cycling runtime. https://au.jackery.com/blogs/buying-advice/battery-backup-for-refrigerator
Inputs: Appliance energy method = Fridge / freezer: measured watts and cycles; Compressor running power = 400 W; Appliance power when not cooling = 0 W; Measured compressor duty fraction = 1; Expected room temperature = 25 °C; Nominal battery capacity = 2,043 Wh; Usable depth of discharge = 1; Inverter conversion efficiency = 0.85; Inverter DC idle draw = 0 W; Cooling and standby account for all daily energy = yes; the others as above.
| Result | Source | This calc |
|---|---|---|
| No-sun backup at average load | 4.3 ± 0.05 h | 4.341 h |
Virginia Tech: 200 W for four hours per day
Source: Virginia Cooperative Extension, ENERGY SERIES: Estimating Appliance and Home Electronic Energy Use (2009), p. 1. Independent window-fan example: 200 W for 4 h/day over 120 days gives 96 kWh, or 0.8 kWh per operating day. This validates duty-weighted electrical energy, not refrigerator performance. https://vtechworks.lib.vt.edu/bitstreams/a283e5b3-4ce7-4b23-b7b3-7dbaea0e6e6e/download
Inputs: Appliance energy method = Fridge / freezer: measured watts and cycles; Compressor running power = 200 W; Appliance power when not cooling = 0 W; Measured compressor duty fraction = 0.1667; Expected room temperature = 25 °C; Cooling and standby account for all daily energy = yes; the others as above.
| Result | Source | This calc |
|---|---|---|
| Total daily AC energy | 0.8 kWh | 0.8 kWh |
Review regression: 350 W at 0.8 PF exceeds a 400 VA inverter
Source: Independent reviewer supplied 350 W / 0.8 = 437.5 VA and a failing 400 VA continuous screen. W-to-VA relation corroborated by Victron, Help me choose, section 3.4 (VA and Watts). https://www.victronenergy.com/inverters-chargers/help-me-choose
Inputs: Inverter continuous real-power rating = 400 W; Inverter continuous apparent-power rating = 400 VA; the others as above.
| Result | Source | This calc |
|---|---|---|
| Required continuous apparent-power capacity | 437.5 VA | 437.5 VA |
| Continuous load / available inverter capacity | 1.094 | 1.094 |
Review regression: three minutes on / three off with lossy charging
Source: Independent review in this task: one-second and half-second integrations both give 71.5 Wh unmet for 120 W on / 0 W off, 3 min on and 3 min off from 08:00 to 16:00, flat 60 W PV in that window, initially usable 50 Wh, unity inverter efficiency, zero idle draw and 50% charging efficiency. Exact independent energy accounting: 80 on-intervals require 240 Wh net discharge; 80 off-intervals can store 120 Wh. With 50 Wh initially and 1.5 Wh stored at the end, unmet = 240 - 120 - 50 + 1.5 = 71.5 Wh. The internal fixture uses the same event dispatch function as the user scenario.
Inputs: the default inputs above.
| Result | Source | This calc |
|---|---|---|
| Short-cycle dispatch reference fixture | 71.5 Wh | 71.5 Wh |
Related Resources
Related articles
-
Complete Solar PV System Simulation in Python, Irradiance, MPPT, Battery Storage & Grid Performance Analysis -
MATLAB/Simulink model creation for a battery energy storage system -
Design and Simulation of a Lithium-Ion Battery Powered Power-Split Hybrid Electric Vehicle Using a Planetary Gear-Based Series–Parallel Architecture
Related courses
IEC Electrical Schematics and Industrial Control Panels
5
Original price was: 42 €.21 €Current price is: 21 €.
Basic Electrical Controls & Diagram Reading
7
Original price was: 32 €.18 €Current price is: 18 €.
Modeling Electrical Motor Faults with FEM Simulation using ANSYS MAXWELL
3
Original price was: 50 €.15 €Current price is: 15 €.







Responses