Cable Size and Voltage Drop Calculator
Size a cable or find its maximum current and kW at 1%, 3% and 5% voltage drop. Compare computed heating, device coordination and fault-loop limits with explicit IEC and NEC assumptions.
This cable size calculator answers two practical questions: which conductor can serve a specified load, and how much load can an existing cable carry? Engineers, students and designers can compare low-voltage feeders, lighting circuits and wallbox supply routes using explicit heating, voltage-drop and fault-loop assumptions.
Choose “Check / size a cable for a load” to enter current, one-way route length, conductor area and power factor. The tool reports voltage at the load, conductor losses, calculated thermal ampacity and a nominal size candidate satisfying the three modeled area requirements. The metric/US display switch converts physical quantities; metric and AWG conductor families are selected independently.
Choose “How much load can this cable carry?” to work backwards from the selected cross-section, route and installation thermal model. The comparison table gives maximum current at 1%, 3% and 5% total voltage drop, then limits it by heating and reports delivered real power in kW. It includes upstream drop: zero means that budget is already consumed. The maximum-load cards use your entered drop target and also restrict current by the protective-device rating and disconnection screen. Zero on those cards means no positive load passes all entered screens. Cable-only table results remain available to explain the limitation.
Supply presets include 127 V single phase for applicable Brazilian and Mexican supplies, 120 V and 230 V single phase, and common three-phase wye supplies. Presets set circuit and earth voltages only. Enter resistance and both reactances at the actual frequency; 60 Hz data may differ from the 50 Hz defaults.
Ampacity uses the reduced IEC 60287-1-1:2023 steady-state heat balance. Select a specified thermal path, a cable in air with an entered effective surface coefficient, or one cable directly buried in homogeneous soil. Air and soil options calculate the surroundings resistance from diameter and thermal inputs. Defaults are visible engineering assumptions, not certified installation-method ratings. Use actual cable construction, terminal limits, grouping and route data. No standard ampacity tables are reproduced.
The voltage drop calculator retains longitudinal and quadrature phasor components at the receiving-end lagging power factor. Maximum-load results conservatively use resistance at the permitted temperature. Delivered kW uses the reduced receiving voltage; the separate heating-only kW ceiling uses nominal voltage and is labeled before-drop.
The IEC profile checks load, device rating and thermal ampacity. The NEC 2023 profile adds 25% of the continuous portion for ordinary branch circuits. The disconnection screen needs a bonded metallic return path, source loop impedance, PE area and the actual device current guaranteed to trip within the required time. Changing the device or time requires updating that current.
This wire size calculator supports design comparisons, not installation certification. Recheck the candidate’s actual thermal path and impedance. Check against the standard in force, including local amendments and listed cable ratings. TT/RCD and IT protection, harmonics, motor starting, soil drying, solar heating, transient heating and short-circuit withstand need separate assessment. Installation work belongs to a qualified electrician (Elektrofachkraft).
How it is calculated
The model follows the steady-state thermal method of IEC 60287-1-1:2023, edition 3.0, equation (2), reduced for an unarmoured low-voltage cable with negligible dielectric, metallic sheath and armour losses. Attached legal preview s3, pages 14–15, gives the heat balance. Thermal resistances are supplied by the user from manufacturer data, measurements or IEC 60287-2-1:2023 calculations.
For area , bulk resistance per length is . Copper data are from NBS Handbook 100 (1966); EC-H19 aluminum data from NBS Handbook 109 (1972), Table 1, attached page 13. The explicit includes construction and AC resistance effects; it must be derived from actual cable data when those effects matter.
The load-circuit calculation retains the complete series-circuit phasor relation, with current and lagging power factor specified at the receiving end. Let , and ; for single phase and for balanced three phase. With cable-origin voltage magnitude , the source equation is , so and cable drop is . The nonnegative quadrature correction is retained at every power factor. ABIT Power System I (2025), PDF page 46, gives the complete source-voltage phasor relation before its optional approximation; the inverse and sizing algebra are derived here. A zero reported load voltage flags an infeasible positive-voltage solution at the entered current. Joule loss remains .
With and , the thermal rating is . is an explicitly supplied thermal-path multiplier, not a tabulated standard grouping factor. Two conductors heat in single phase; three heat in balanced three phase.
For the metallic earth-fault path, , with . is compared with the entered guaranteed trip current at the required time. The IEC screen follows the IEC 60364-4-41:2005+A1:2017, edition 5.1, including 2018 corrigendum, loop-impedance principle. It does not infer a trip time from a generic curve. The independently entered is the complete phase-to-PE loop reactance per one-way route length; it already includes the return path and mutual coupling. It must describe the actual phase/PE geometry and fault configuration. CLC/TR 50480:2011, section 4.3 Note 2, explains why load-circuit reactance and fault-loop reactance can differ.
The NFPA 70 (NEC), 2023 edition, ordinary branch-circuit design screen uses and conservatively requires . This does not claim code allowable ampacity. Both profiles apply the same physical thermal and loop models.
Area minima follow by solving the heat, full-phasor and fault-loop equations with all non-area quantities held fixed. For the voltage target , the maximum allowable per-conductor resistance is . The implementation evaluates its rationalized positive root for numerical stability; . A nonpositive root means no finite resistance can meet the target. The next metric nominal size or geometrically computed AWG area is selected. A zero area in the minima table marks an infeasible criterion or absence of a listed candidate. The source-impedance and reactance budgets are checked before selection.
Maximum load for an existing cable
The reverse calculation uses the selected area, route and thermal installation model, with conductor resistance at even when the forward-mode drop temperature is lower. Let and . At receiving-voltage target , Kirchhoff's phasor equation gives . Its positive root is evaluated without subtractive cancellation as
If , the available drop budget is exhausted and the current is reported as zero.
For total drop budgets of 1%, 3% and 5%, the table reports and , where in the IEC profile and in NEC mode (continuous share entered in percent). Table power uses , with for single phase and for three phase, converted to kW. It excludes protection limits. The maximum-load cards additionally impose , and ; otherwise their current and power are zero. Device choice and time-current data remain explicit. Heating-only kW is the nominal-voltage equivalent , before any voltage drop.
Installation thermal paths
The specified-path option preserves the entered . For one directly buried isolated cable, , , with homogeneous soil and an isothermal ground surface. This is the single-isolated-cable boundary geometry of IEC 60287-2-1:2023; Cableizer's open implementation documents the same expression (s9). For air, Newton's surface heat balance gives . The entered includes convection and radiation at the limiting surface temperature; it is not the IEC empirical coefficient with units involving . These options add the separately entered shared cable-layer resistance to before applying the common-path multiplier. No installation-method ratings or coefficients are taken from standard tables.
The 127 V single-phase preset is supported by CPFL's supply guide (s10) and Mexico's NOM-001-SEDE-2012, 110-4 (s11). Presets select voltage and phase count, not regional regulatory compliance or frequency-dependent impedance.
Assumptions
- AC, sinusoidal, lagging loads; balanced three phase with an unloaded neutral, or single phase with a full-size return conductor. One cable, no parallel sets.
- Nominal 100% IACS annealed copper or 61% IACS EC-H19 aluminum. PE has the same metal, construction multiplier and temperature as the phase, with an explicit area ratio.
- Default case: 230 V, 32 A, 25 m one way, 6 mm² copper, unity power factor, 70 °C conductor/terminal limit, 30 °C ambient, and 0.08 Ω/km reactance at 50 Hz.
- User-verifiable thermal assumptions: T1 = 0.5 K·m/W, common path = 4 K·m/W, grouping multiplier = 1. These are design inputs, not a certified installation-method ampacity. The 1.05 resistance multiplier is an explicit 5% design allowance, not a standard material constant.
- Thermal paths are constant along the route. Use the thermally worst section. No solar heating, soil drying, dielectric losses or metallic sheath/armour heating.
- Complete phase-to-PE loop reactance defaults to 0.16 Ω/km of one-way route as an explicit close-proximity assumption. It is entered independently of the load-circuit value; obtain both values for the actual geometry, conductor proximity, return path and frequency.
- Receiving-end RMS current and displacement power factor are specified independently of voltage. Upstream drop reduces the cable-origin voltage magnitude; its upstream phase shift and impedance are not reconstructed. The full-phasor inversion is derived here from Kirchhoff's voltage law. Shunt capacitance and leakage are neglected.
- Drop temperature is entered separately from the thermal limit. Fault current uses the hotter of these temperatures to avoid an optimistic cold loop.
- External source resistance and reactance are explicit. Default minimum-voltage factor is 0.95; the separate conventional 0.8 method is not silently added.
- Default protection is a 32 A device with Ia = 160 A entered for 0.4 s. This illustrates the upper magnetic threshold of a typical IEC B32; the actual manufacturer's upper time-current curve governs. Neither device rating nor required time automatically updates Ia.
- Minimum-area calculations assume the same thermal path, grouping, resistance multiplier, load-circuit reactance, complete fault-loop reactance and PE ratio for every candidate. Verify and update these values for the chosen cable.
- Reverse-mode and maximum-load table calculations use the limiting conductor temperature for voltage drop. The entered forward-mode temperature affects only the specified-load calculation.
- Air illustration: 15 mm overall cable diameter, shared internal layers 0.3 K·m/W and effective surface coefficient 8 W/(m²·K). Soil illustration: the same diameter/layers, 0.7 m centre depth and 1.5 K·m/W soil resistivity. These are explicit hypothetical thermal inputs, not ratings for a named cable.
- Buried geometry assumes one fully buried cable, homogeneous non-drying soil and a uniform surface temperature. Air geometry assumes an unobstructed cable with no solar heating and a user-verified effective surface coefficient. Ducts, thermal insulation and complex routes require the specified-path option with studied resistances.
- The 1%, 3% and 5% comparison budgets include upstream drop; a zero current marks an exhausted budget. The comparison table excludes device rating and fault-loop limits. The maximum-load cards include those screens and use the separately entered total target.
- Delivered power is electrical real power at the load, not mechanical shaft output. Heating-only nominal-voltage kW is a before-drop equivalent. Supply presets do not change reactances, source impedance, protection, design profile or local rules.
Where it applies
Rules and source review date: 2026-10-25. Check against the standard in force. This tool provides engineering design screens, not installation approval or a certificate of IEC/NEC compliance. Installation work belongs to a qualified electrician (Elektrofachkraft).
For low-voltage circuits up to 1000 V AC, with the supplied cable thermal model and impedance valid at operating frequency. The material temperature model is used over −20 to 120 °C; permitted cable and terminal temperatures can be lower. At 60 Hz, update both load and fault-loop reactances and the AC resistance multiplier. The 3% default is a selected target; NEC 3% branch / 5% combined guidance is generally informational, while local rules and equipment requirements may differ.
The fault-loop screen applies only to bonded metallic return paths. Its separate complete loop-reactance input must be verified for the actual phase-to-PE path, conductor proximity, mutual coupling and fault configuration; balanced three-phase load reactance is not a substitute. Separate or remote PE routing can substantially alter the loop reactance. It does not verify TT earth-electrode/RCD operation, IT systems, touch voltages, bonding continuity, protective conductor minimum size, disconnection-time rules, prospective maximum fault current, breaking capacity, selectivity or short-circuit thermal withstand. A matching Ia only supports disconnection if the entered device curve and required time are correct. NEC mode uses this loop calculation as an engineering screen, not as a substitute for NEC equipment grounding rules.
NEC listed cable allowable ampacity, adjustment/correction procedures, 110.14(C) terminations, small-conductor protection and special equipment articles remain separate checks. No ampacity tables from VDE 0298-4, IEC 60364-5-52 or NEC are copied. Voltage drop uses the full series-circuit phasor relation even below 10% projected drop. It assumes prescribed receiving current and power factor; constant-power or voltage-dependent loads need a coupled load solution. If no positive receiving voltage exists, the displayed zero voltage is an infeasibility marker and cannot pass the drop screen. Leading power factor, harmonics, unequal single-phase conductors, motor starting, cable joints, transient/cyclic heating and loaded three-phase neutrals are outside scope.
Reference cases use NBS wire resistance data and Schneider's published motor example. Schneider's rounded 5 V result uses conservative resistivity 0.0237 Ω·mm²/m; the full-phasor physical copper model at 90 °C gives about 4.78 V, explicitly allowed in that case's tolerance. This difference is documented rather than fitted away.
Maximum-load mode is a steady-state, prescribed power-factor capacity screen. Its cable-only comparison table must not be used as a protective-device rating. A zero protected load result can mean unsuitable entered protection even while the cable has nonzero physical capacity. The maximum-load calculation does not select or certify a breaker. For air and buried scenarios, confirm actual thermal coefficients, cable geometry and the thermally worst route section; do not substitute their hypothetical defaults for manufacturer data. The analytic ground boundary does not model layered soil, ducts, drying or interacting cable groups.
References
- NBS Handbook 100 (1966), Copper Wire Tables, Tables 5–6 and material definitions; attached s2. https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook100.pdf
- NBS Handbook 109 (1972), Aluminum Wire Tables, Table 1; attached s6, p.13. DOI:10.6028/NBS.HB.109 — https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook109.pdf
- IEC 60287-1-1:2023, edition 3.0, equation (2); attached s3 legal preview pp.14–15. https://webstore.iec.ch/en/publication/68118
- IEC 60287-2-1:2023, thermal resistance method; obtain cable-specific inputs from this method, manufacturer data or measurements. https://cdn.standards.iteh.ai/samples/104910/6b3e081cc5e640aeb686d84e53dd5f00/IEC-60287-2-1-2023.pdf
- Schneider Electric, Electrical Installation Guide: Calculation of voltage drop in steady load conditions, formulae and Example 1; attached s1. https://www.electrical-installation.org/enwiki/Calculation_of_voltage_drop_in_steady_load_conditions
- Schneider Electric, TN system — Earth-fault current calculation; attached s4. https://www.electrical-installation.org/enwiki/TN_system_-_Protection_against_indirect_contact
- IEC 60364-4-41:2005+AMD1:2017, edition 5.1, including 2018 corrigendum, clause 411.4.4 principle. https://webstore.iec.ch/en/publication/60169
- NFPA 70 (NEC), 2023 edition, 210.19, 210.20 and 110.14(C); NFPA public committee record discusses the 2023 continuous-load text (proposals in that record are not adopted rules), attached s5. https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2025_NEC_P02_FD_PIResponses.pdf
- Eaton, Basics of power system design, voltage-drop considerations, printed p.54: 3% and 5% NEC guidance is informational. https://www.eaton.com/content/dam/eaton/products/design-guides---consultant-audience/eaton-basics-of-power-system-design-dg081001en.pdf
- ABIT, Chandan Mandal, Power System I (2025), PDF page 46: complete series-circuit phasor magnitude relation. Receiving-voltage inversion and area-limit algebra derived here. Attached s7. https://abit.edu.in/wp-content/uploads/2025/08/PS-I-NOTES.pdf
- CLC/TR 50480:2011, section 4.3 Note 2: conductor reactance depends on neighboring conductors and fault configuration; attached s8. https://theiteh.com/catalog/standards/sist/2a319da3-e301-4d84-8b1e-272ef9ac7dad/sist-tp-clc-tr-50480-2011
- Cableizer, Thermal resistance ambient: isolated buried cable and surface heat-transfer expressions; attached s9. https://www.cableizer.com/documentation/T_4iii/
- CPFL Energia, Guia de Ligação Nova, single-phase 127 V supply; attached s10. https://cpfl.com.br/ajuda/ligacao-nova
- Mexico, NOM-001-SEDE-2012, 110-4, nominal circuit voltages include 127 V; attached s11. Cited for voltage only, not as a Mexican compliance profile. https://sidof.segob.gob.mx/notas/docFuente/5280607
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| What do you want to find? Maximum-load mode uses your selected cable, installation and route. It computes 1%, 3% and 5% drop ceilings plus the entered target. | load_mode | Check / size a cable for a load | |
| Design profile Profiles set the design-current rule. Neither replaces locally adopted installation requirements. | profile | IEC — thermal and TN loop assessment | |
| Supply preset Sets circuit type, load voltage and line-to-earth voltage only. Enter cable and source impedances at the actual supply frequency; presets do not change those inputs. | supply | Custom circuit and voltages | |
| AC circuit Sinusoidal load, equal outgoing and return conductors; balanced three-phase neutral carries no current. | circuit | Single phase — two loaded conductors | |
| Circuit voltage Single phase: voltage across the load. Three phase: line-to-line voltage. | U_nom | V | 230 |
| Operating load current Specified receiving-end RMS current per phase, used for voltage drop and losses. Reassess current for voltage-dependent or constant-power equipment. | I_load | A | 32 |
| One-way cable route length Source to load, not the round trip. Return conductors are included by the equations. | L | m | 25 |
| Lagging power factor cos φ Displacement power factor. Leading loads, harmonics and nonlinear neutral loading are outside scope. | pf | 1 | |
| Continuous share of load NEC 2023 design current = noncontinuous current + 125% of continuous current. Ordinary, non-100%-rated assemblies. | f_cont | % | 100 |
| Conductor size family Independent of the metric/US display switch. | family | Metric cable areas | |
| Phase conductor Only nominal area is used from this size list; resistance is computed from resistivity. | wire_metric | 6 mm² | |
| Phase conductor Geometric area only; an AWG area does not establish a listed cable rating. | wire_awg | AWG 10 | |
| Conductor metal Bulk properties from NBS Handbooks 100 and 109. Verify cable alloy and measured resistance. | metal | Annealed copper — 100% IACS | |
| Resistance construction / AC multiplier Ratio of effective cable resistance to ideal bulk-metal resistance. Default 1.05 is a stated design allowance, not a standard value; enter manufacturer data including strand lay, skin and proximity effects. | k_R | 1.05 | |
| Conductor temperature for voltage drop Expected hottest operating temperature for the specified load. Maximum-load mode instead uses the limiting temperature conservatively. | T_calc | degC | 70 |
| Load-circuit reactance per conductor Used only for load voltage drop. 0.08 Ω/km is Schneider's 50 Hz fallback; the same geometry is about 0.096 Ω/km at 60 Hz. Enter actual load-circuit data. The complete phase-to-PE fault-loop reactance is a separate input. | x_per_km | ohm/km | 0.08 |
| Installation thermal model Computed thermal scenarios, not IEC/NEC installation-method ratings. Supply actual cable geometry and thermal data; no ampacity tables are used. | installation | Specified thermal path — any studied route | |
| Limiting conductor / terminal temperature Use the lower permitted cable and termination temperature. NEC installation and terminal restrictions still apply. | T_limit | degC | 70 |
| Ambient medium temperature Air or soil temperature excluding heat generated by this cable; include nearby unrelated heat sources. | T_ambient | degC | 30 |
| Per-core internal thermal resistance T1 Manufacturer value or IEC 60287-2-1 calculation for the actual construction. The default is an explicit design assumption. | T_core | K*m/W | 0.5 |
| Common thermal path T2 + T3 + T4 Combined bedding, jacket and environment path per cable, before grouping. Use measured or calculated data for the route. Default 4 is a design assumption, not an installation-method rating. | T_shared | K*m/W | 4 |
| Overall cable diameter Overall multicore-cable diameter, including the outer jacket, not conductor diameter. | D_cable | mm | 15 |
| Common internal layers T2 + T3 Cable bedding/jacket path shared by all cores, excluding T1 and surroundings. Default is an explicit assumption; use manufacturer or construction calculations. | T_layers | K*m/W | 0.3 |
| Effective surface heat-transfer coefficient Combined convection and radiation at the limiting cable-surface temperature, from a thermal study or measurement. Default 8 is an assumption, not a standard coefficient. No sun or enclosing conduit. | h_surface | W/(m^2*K) | 8 |
| Burial depth to cable centre Vertical ground-surface-to-axis distance. One isolated cable, homogeneous soil, no duct or backfill boundary. | burial_depth | m | 0.7 |
| Soil thermal resistivity Use measured worst-season soil properties. Default 1.5 is an explicit assumption. Soil drying and moisture migration are outside the model. | rho_soil | K*m/W | 1.5 |
| External thermal-path grouping multiplier 1 = isolated circuit. Increase using a thermal interaction study. This is a model multiplier, not an IEC/NEC tabulated derating factor. | G_heat | 1 | |
| Total voltage-drop target Explicit total design target, not an automatic legal limit. The comparison table always shows 1%, 3% and 5%; this input controls the maximum-load result cards. | drop_limit | % | 3 |
| Upstream voltage drop Drop already consumed before this cable, as a percentage of the same nominal circuit voltage. | drop_upstream | % | 0 |
| Protective-device rated current Conservative coordination screen requires design current ≤ device rating ≤ computed thermal ampacity. | I_break | A | 32 |
| Source line-to-earth voltage U0 Use line-to-earth voltage even for a three-phase circuit; e.g. 230 V for 400 V wye or 120 V for 208 V wye. Center-tapped 240 V uses 120 V. TN/bonded metallic return only. | U_earth | V | 230 |
| External fault-loop resistance Source, supply and bonding resistance up to the cable origin, excluding this cable. | R_external | ohm | 0.2 |
| External fault-loop reactance Inductive reactance of the external loop at supply frequency. | X_external | ohm | 0.05 |
| Cable phase-to-PE loop reactance Complete phase-to-PE loop reactance per kilometre of one-way route, including the return path and mutual coupling. Obtain data for the actual fault configuration, conductor proximity and frequency. Default 0.16 Ω/km is an explicit close-proximity design assumption; it is independent of load-circuit reactance. | x_fault_km | ohm/km | 0.16 |
| PE / phase conductor area ratio Same material and route assumed. The sizing calculation holds this ratio constant; it does not select a code-compliant PE size. | pe_ratio | 1 | |
| Minimum-voltage factor for fault current Applied to U0 only; external R/X is modeled explicitly. Do not add the conventional 0.8 factor unless its extra conservatism is intended. | c_min | 0.95 | |
| Required disconnection time Enter the time required by the locally adopted rules and circuit category. | t_disconnect | s | 0.4 |
| Current guaranteeing trip within that time Ia Read the upper tolerance of the actual device time-current curve at the required time. Default 160 A is 5 × 32 A for a typical IEC B32 magnetic element; confirm the device. Changing device rating or required time requires updating this value. | I_trip | A | 160 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Maximum load at entered target — all screens | 32 A |
| Delivered load at that maximum | 7.18 kW |
| Heating-only operating-current ceiling | 36.1 A |
| Heating ceiling × nominal voltage (before drop) | 8.3 kW |
| Conductor selection | 6 mm² — verify thermal path |
| Calculation basis | Candidate assumes the same thermal path and PE ratio; verify the actual cable. |
| Thermal / device coordination | Within thermal model |
| Calculated thermal ampacity | 36.1 A |
| Design load current | 32 A |
| Voltage-drop target | Within voltage-drop target |
| Total voltage drop | 2.51 % |
| Load voltage — full phasor solution | 224.2 V |
| Conductor heat loss | 184.8 W |
| Disconnection-current screen | Ia met — confirm curve at 0.4 s |
| Minimum prospective earth-fault current | 568.5 A |
| Hot earth-fault loop impedance | 0.384 Ω |
| Maximum loop impedance for entered Ia | 1.366 Ω |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
NBS: 10 AWG copper resistance at 20 °C
Source: NBS Handbook 100 (1966), Table 6, printed p.17 (attached p.23): resistance of 1000 ft of 10 AWG annealed copper at 20 °C. Published diameter is rounded; AWG geometry is computed without rounding.
Inputs: Conductor size family = AWG wire sizes; Conductor temperature for voltage drop = 20 °C; Resistance construction / AC multiplier = 1; One-way cable route length = 304.8 m; Operating load current = 10 A; the others as above.
| Result | Source | This calc |
|---|---|---|
| One-way conductor resistance | 0.9988 ± 0.001 Ω | 0.9989 Ω |
NBS: hot 10 AWG copper at 75 °C
Source: NBS Handbook 100 (1966), Table 6, printed p.17 (attached p.23): 10 AWG, 1000 ft, 75 °C. Tests temperature correction independently against the published wire table.
Inputs: Conductor size family = AWG wire sizes; Conductor temperature for voltage drop = 75 °C; Resistance construction / AC multiplier = 1; One-way cable route length = 304.8 m; Operating load current = 10 A; the others as above.
| Result | Source | This calc |
|---|---|---|
| One-way conductor resistance | 1.215 ± 0.002 Ω | 1.215 Ω |
Schneider: 35 mm² three-phase motor feeder
Source: Schneider Electric Electrical Installation Guide, Calculation of voltage drop in steady load conditions, Example 1: 35 mm² Cu, 50 m, 400 V, 100 A, cosφ 0.8, cable drop 5 V. https://www.electrical-installation.org/enwiki/Calculation_of_voltage_drop_in_steady_load_conditions . Their conservative resistivity 0.0237 Ω·mm²/m and rounded coefficient give 5 V; the full-phasor copper solution at 90 °C gives about 4.78 V. Tolerance 0.4 V covers the conservative resistivity, rounded coefficient and longitudinal approximation in that worked example; formula is not fitted.
Inputs: Phase conductor = 35 mm²; AC circuit = Balanced three phase — three loaded conductors; One-way cable route length = 50 m; Operating load current = 100 A; Circuit voltage = 400 V; Lagging power factor cos φ = 0.8; Conductor temperature for voltage drop = 90 °C; Resistance construction / AC multiplier = 1; the others as above.
| Result | Source | This calc |
|---|---|---|
| Cable voltage drop from the full phasor relation | 5 ± 0.4 V | 4.777 V |
NBS: EC-H19 aluminum resistivity at 30 °C
Source: NBS Handbook 109 (1972), Table 1, printed p.5, attached p.13: EC-H19 (61% IACS) volume resistivity at 30 °C = 0.029403 Ω·mm²/m. This checks the aluminum branch and its temperature coefficient against a published material table.
Inputs: Conductor metal = EC aluminum — 61% IACS; Conductor temperature for voltage drop = 30 °C; Resistance construction / AC multiplier = 1; the others as above.
| Result | Source | This calc |
|---|---|---|
| Resistivity at voltage-drop temperature | 0.0294 Ω·mm²/m | 0.0294 Ω·mm²/m |
Review regression: 6 mm² at cos φ = 0.1 needs rejection
Source: Independent reviewer supplied these series-circuit results for defaults with cos φ=0.1, L=200 m and PE/phase area=2: load voltage 219.74 V and 4.46% drop, requiring the next candidate 10 mm². These expected values are from the independent review, not calculator output. ABIT, Power System I (2025), PDF p.46 gives the complete phasor magnitude relation before its optional approximation. https://abit.edu.in/wp-content/uploads/2025/08/PS-I-NOTES.pdf
Inputs: Lagging power factor cos φ = 0.1; One-way cable route length = 200 m; PE / phase conductor area ratio = 2; the others as above.
| Result | Source | This calc |
|---|---|---|
| Load voltage — full phasor solution | 219.7 V | 219.7 V |
| Total voltage drop | 4.46 ± 0.01 % | 4.461 % |
| Next candidate area, zero means no candidate | 10 mm² | 10 mm² |
Review regression: 10 mm² satisfies the full-phasor target
Source: Independent reviewer reports approximately 2.36% full-phasor drop for 10 mm² with the same 230 V, 32 A, 200 m, cos φ=0.1 case. Expected value supplied by the independent review; ABIT Power System I (2025), PDF p.46 supports the series-circuit phasor derivation. https://abit.edu.in/wp-content/uploads/2025/08/PS-I-NOTES.pdf
Inputs: Lagging power factor cos φ = 0.1; One-way cable route length = 200 m; PE / phase conductor area ratio = 2; Phase conductor = 10 mm²; the others as above.
| Result | Source | This calc |
|---|---|---|
| Total voltage drop | 2.36 ± 0.01 % | 2.365 % |
| Next candidate area, zero means no candidate | 10 mm² | 10 mm² |
Reverse 127 V: current and delivered power from published AWG resistance
Source: NBS Handbook 100 (1966), Table 6, attached p.23: AWG 10 at 75 °C is 1.215 ohm per 1000 ft. In a 127 V single-phase circuit, 3% = 3.81 V and Ohm's law gives 3.81/(2 × 1.215) = 1.567901 A. Expected current is independently derived from the published resistance, not the calculator's resistivity model; tolerance covers the rounded table. Delivered power uses 127 × 0.97 V times this current = 0.193150 kW; heating is nonlimiting in this long, lightly loaded case.
Inputs: Conductor size family = AWG wire sizes; Limiting conductor / terminal temperature = 75 °C; Resistance construction / AC multiplier = 1; One-way cable route length = 304.8 m; Load-circuit reactance per conductor = 0 Ω/km; What do you want to find? = How much load can this cable carry?; Supply preset = 127 V single phase — Brazil / Mexico; the others as above.
| Result | Source | This calc |
|---|---|---|
| Maximum current allowed by voltage drop alone [2] | 1.568 ± 0.002 A | 1.568 A |
| Delivered real load power at each heat-and-drop ceiling [2] | 0.1931 ± 3 × 10⁻⁴ kW | 0.1932 kW |
Related Resources
Related articles
Related courses
IEC Electrical Schematics and Industrial Control Panels