Battery Runtime and Backup Power Calculator

Calculate battery and UPS runtime for fans, lights, TVs or boilers. Compare editable 150/200 Ah inverter examples and size battery counts from runtime, voltage and C-rate limits.

#battery backup #battery runtime #generator #home inverter #inverter #motor starting #Peukert law #UPS

This battery runtime calculator estimates how long an installed bank can supply AC loads and how many batteries a target backup period requires. Use it for home power cuts in India or Pakistan, a boiler UPS, lighting, communications or other small backup systems. Engineers and students can inspect the calculation steps and compare load scenarios.

How long will a 200 Ah battery run fans, lights and TV?

The default example is one 12 V, 200 Ah tubular lead-acid battery and a 900 VA / 756 W inverter. The editable appliance list assumes two 70 W fans, four 10 W lights and an 80 W television: 260 W total. With 85% incremental efficiency, 10 W DC idle draw, a 1.25 Peukert exponent, 50% usable discharge, full initial charge, full health and a 100% temperature factor, modeled runtime is about 2.98 hours. This is an illustrative calculation, not a measured product backup claim.

Select a 150 Ah example to compare capacity. The 1500 VA / 1260 W examples use two 12 V batteries in series for a 24 V inverter. Each preset is a starting point: choose Custom to edit battery voltage, Ah, inverter DC voltage, installed parallel strings, inverter watts and VA. Efficiency, idle draw, discharge limit and Peukert inputs remain separately editable.

How many 12 V batteries for a 3000 W inverter?

Choose a 3000 W example at the inverter's actual 12, 24 or 48 V DC input, then select Full inverter rated watts. Enter the desired hours and the battery's continuous C-rate limit. The battery backup calculator reports batteries per series string, required parallel strings, total batteries, DC current, installed runtime and runtime after rounding to whole strings. At 48 V, four 12 V batteries make one string; they retain the Ah capacity of one battery. More parallel strings add capacity.

An inverter's watt rating alone cannot determine a battery count. Required duration, DC voltage, individual capacity, discharge allowance and current limit all matter. Use the appliance mode when your actual load is smaller than the inverter rating.

Refine the estimate

Each load slot is a starting group. Enter electrical input watts, duty cycle and the group's total starting-to-running power ratio. Motors in one slot start together; put the two default fans in separate slots to model individual sequential starts. A zero duty cycle excludes a group.

The runtime curve varies enabled powers together and stops before exceeding inverter watts, inverter VA or the installed bank's continuous-current limit. Checks use coincident running loads, even for low-duty appliances. The maximum mean AC load result uses the entered duty cycles. Complete-bank entry checks battery current only; choose an individual-battery example or Custom to include inverter ratings. Starting surge remains a separate check. The conservative cycling estimate aligns on periods; the constant-average comparator shows the effect of smoothing.

Use manufacturer data for temperature and aging corrections. The optional Trojan AGM temperature guide is an approximation, not tubular-battery or lithium calibration. A single temperature input follows the viewer's metric/US conversion.

As a UPS runtime calculator, this is a planning estimate: it excludes voltage sag, cutoff behavior, recovery, charging and fuel endurance. Check battery discharge curves and inverter or generator continuous W/VA, starting surge and surge duration. Boiler supplies also need compatible waveform and earthing/neutral arrangements. Installation work belongs to a qualified person.

How it is calculated

Average AC power is Pavg=∑PjdjP_{avg}=\sum P_j d_j; all-load running power includes every enabled load with nonzero duty. Battery current in an on/off state is I=(PAC/η+Pidle)/VI=(P_{AC}/\eta+P_{idle})/V. Inverter efficiency excludes the separate DC idle draw.

Victron BMV-712 Smart manual, attached PDF pages 48–49 (printed 44–45), gives Peukert's constant-current model and the 100 Ah C20 / 75 Ah C5 example. The reference current is Ir=Q/HrI_r=Q/H_r. We express Peukert depletion as g(I)=Imax⁡[1,I/Ir]k−1g(I)=I\max[1,I/I_r]^{k-1}. Above the rated current this reproduces t=Hr(Ir/I)kt=H_r(I_r/I)^k for a fresh, fully discharged bank; below it we cap capacity gain at the nominal Ah.

Duty fractions alone do not specify timing. The conservative model aligns on periods as much as possible, sorts their duty boundaries, and sums gˉ=∑Δd g(Istate)\bar g=\sum \Delta d\,g(I_{state}). For a convex depletion function this maximally coincident schedule has at least the depletion of any other overlap pattern with the same duties. The constant-average comparator uses g(Iavg)g(I_{avg}). These are model-based planning estimates; physical recovery is not included.

Usable charge is Qu=Q fT fhealth [SOC0−(1−DOD)]Q_u=Q\,f_T\,f_{health}\,[SOC_0-(1-DOD)]. Runtime is Qu/gˉQ_u/\bar g. Trojan's AGM guidance gives 50% capacity at -18 °C and 100% at 27 °C; the tool linearly interpolates those endpoints and caps the factor at 1 above 27 °C. This interpolation is our approximation. A manufacturer factor replaces it when selected.

A bracketed scalar root solves the Ah needed for the target duration, recomputing the rated current as bank capacity changes. The final minimum is the larger of that root and Ion/ClimitI_{on}/C_{limit}. The enlarged bank's modeled duration is also calculated.

Honda's generator guidance distinguishes running watts from total starting watts. Each load slot is one starting group: motors entered together start together. The default two-fan group gives 400 W before headroom, or 500 W with 25% headroom. Splitting the two 70 W fans into separate slots gives 330 W before headroom, or 412.5 W with the same allowance. With ΔPj=Pj(sj−1)\Delta P_j=P_j(s_j-1), sequential starting needs Pall+max⁡ΔPjP_{all}+\max\Delta P_j; simultaneous starting needs ∑Pjsj\sum P_j s_j. Both running and starting ratings receive the entered headroom, then divide by the entered conservative power factor for VA. Headroom is a user design choice. These load aggregation, overlap-bound and sizing equations are derived here.

Individual-battery entry uses Ns=VDC/VbN_s=V_{DC}/V_b (a whole number), Q=NpQbQ=N_p Q_b, and V=VDCV=V_{DC}. For the selected load, Np,req=⌈Qrequired/Qb⌉N_{p,req}=\lceil Q_{required}/Q_b\rceil and Ntotal=NsNp,reqN_{total}=N_s N_{p,req}. The tool recomputes runtime using Np,reqQbN_{p,req}Q_b. Current divides equally between parallel strings: Istring=Ion/NpI_{string}=I_{on}/N_p. These topology equations follow Victron Wiring Unlimited, section 3.1. A numerical tolerance of 1e-10 in the Ah ratio prevents an exact integer root being rounded upward through floating-point noise.

Full-inverter mode replaces the appliance list with a constant load equal to the selected continuous watt rating. It does not assume motor starting or claim a surge capability. Actual W and VA are compared independently with inverter continuous ratings. Generator sizing still applies the chosen headroom. Only the inverter manufacturer's DC voltage is suitable; changing the example voltage represents choosing a different inverter.

The 150/200 Ah C20 examples are based on Exide IT500/IT750 capacity ratings. The 900 VA example uses Luminous Zolt 1100 ratings (756 W, 12 V); the 1500 VA example uses Power Sine M 1700 ratings (1260 W, 24 V). The shared efficiency, idle draw, DOD, Peukert exponent and C-rate limit are illustrative assumptions, not those products' measured values. Generic 3000 W / 3750 VA examples are design scenarios, not named products.

The runtime curve excludes continuous operating points beyond entered equipment limits. The battery permits Pbat=max⁡[0,η(VQClimit−Pidle)]P_{bat}=\max[0,\eta(V Q C_{limit}-P_{idle})] AC watts. In individual-battery mode the permitted coincident running load is Pmax=min⁡(Pbat,Pinv,PF Sinv)P_{max}=\min(P_{bat},P_{inv},PF\,S_{inv}). Complete-bank mode checks only the entered battery current limit because no inverter rating is specified there. With all enabled powers multiplied by aa, require aPall≤PmaxaP_{all}\leq P_{max}; apply this to coincident running power, not the duty-averaged power. The curve stops at the smaller of this bound and twice the entered load powers. Its displayed average-load boundary is PmaxPavg/PallP_{max}P_{avg}/P_{all}. Every plotted point is also checked directly; infeasible points are omitted. If idle draw consumes the entire current allowance, the curve is empty and an input message explains how to change the system. This is a continuous-operation screen: headroom, starting surge and pulse-current capability remain separate checks.

Assumptions

  • AC input watts are measured or nameplate values while on. All enabled nonzero-duty devices can overlap; zero-duty devices are excluded from source sizing.
  • Loads cycle repeatedly over the outage, so the entered duty fractions represent their long-term usage. Very short outages may depend on the initial on/off state.
  • Bank voltage, inverter incremental efficiency and DC idle draw stay constant. The inverter remains on during off periods.
  • Capacity uses the entered rating period. Presets use C20. In individual-battery mode, parallel strings add Ah and series batteries add voltage. In complete-bank mode, enter the whole bank voltage and Ah; individual-battery result cards are unavailable.
  • Temperature and aging multiply available charge without changing the rated-current reference. This is an engineering approximation; measured discharge curves are preferable.
  • Peukert exponent is between 1.00 and 1.50. The 1.25 default follows Victron's lead-acid starting estimate; lithium users should normally use 1.00 and a manufacturer temperature factor.
  • Source sizing assumes the same conservative power factor for starting and running. The 25% default headroom is illustrative. Starting transients affect ratings but their short energy consumption is excluded.
  • Default loads are assumed: one group of two fans totaling 140 W, lights totaling 40 W and a TV at 80 W, all continuously on. Both fans in the first group start together. The group starting multiplier of 2 is also an assumption; replace it with measured data or separate motors into individual slots.
  • The home examples assume 85% incremental inverter efficiency, 10 W DC idle draw, 50% discharge allowance, full initial charge and health, a 100% temperature capacity factor, and a 0.25C continuous limit. These are editable engineering examples, not manufacturer guarantees.
  • Identical batteries are permitted to connect in the chosen series/parallel arrangement, remain balanced, and share parallel current equally. A whole string must be added each time. Verify battery/BMS connection limits and matching condition.
  • Required count is the total number of batteries for the selected duration and continuous current, not the number to add. Startup current is approximate and is not checked against a battery pulse-current limit.

Where it applies

Use for preliminary AC backup planning, not a guaranteed autonomy or motor-starting result. Peukert's fixed exponent becomes unreliable at very high currents. Check the battery's constant-power or constant-current discharge data at the actual cutoff voltage, temperature and load.

The built-in temperature interpolation is limited to -18…50 °C (-0.4…122 °F), with no capacity bonus above 27 °C. It represents Trojan lead-acid guidance and is not a universal lithium model. A custom factor is permitted only where the battery manufacturer allows discharge. Charging temperature limits are separate.

Runtime ignores changing terminal voltage, internal resistance, wiring losses, inverter low-voltage cutoff, BMS trips, self-discharge and recovery. The maximally coincident duty model is conservative only within this simplified depletion model; short outages and startup energy can give shorter real autonomy. There is no charger or generator fuel calculation.

Check inverter and generator continuous W/VA ratings, surge W/VA and duration, motor starting power factor, waveform, voltage dip and generator derating for altitude or temperature. Include battery-charger watts as another load if charging from a generator. For boilers, verify waveform and earthing/neutral compatibility. Installation work belongs to a qualified person; this schematic is functional, not a wiring design.

Do not treat the calculated battery count as approval of a wiring arrangement. Victron cautions against large lead-acid banks with more than about three or four parallel strings. Consider larger individual batteries or a compatible higher-voltage inverter when the arithmetic needs more strings. Check permitted series counts for lithium and BMS systems, pulse-current limits, battery balancing, protection and cable ratings with a qualified person.

References

  • Victron Energy, BMV-712 Smart manual, section 8, attached PDF pages 48–49 (printed 44–45), Peukert law, exponent range and worked capacity examples. https://www.victronenergy.com/upload/documents/BMV-712_Smart/9172-Manual_BMV_and_SmartShunt-pdf-en.pdf
  • Victron Energy, Battery capacity and Peukert exponent, online manual. https://www.victronenergy.com/media/pg/BMV-700H/en/battery-capacity-and-peukert-exponent.html
  • Trojan Battery, AES AGM and Standard AGM battery maintenance, Temperature considerations: capacity at -18 °C and 27 °C. https://www.trojanbattery.com/trojan-aes-batteries/aes-agm-standard-agm-battery-maintenance
  • Honda Power Equipment, Generator Wattage Estimation Guide, Contractor Applications: half-horsepower compressor 975 running W and 1600 starting W. https://powerequipment.honda.com/generators/generator-wattage-estimation-guide
  • Honda Power Equipment, What size generator do I need?, worked household example with 2900 W running and 5300 W summed starting demand. https://powerequipment.honda.com/generators/generator-how-much-power
  • Exide IT500 and IT750 tubular inverter batteries, 150 Ah and 200 Ah at C20. https://www.exidecare.com/find-exide/products/exide-inva-tubular/it500 ; https://www.exidecare.com/find-exide/products/EXIDE-INVA-TUBULAR/IT750
  • Luminous Zolt 1100: 900 VA, 756 W, one 12 V battery. https://www.luminousindia.com/home-inverters/zolt-1100
  • Luminous Power Sine M 1700: 1500 VA, 1260 W, two 12 V batteries / 24 V. https://www.luminousindia.com/home-inverters/power-sine-m-1700
  • Victron Energy, Wiring Unlimited, section 3: series and parallel battery banks, equal current sharing, balancing and parallel-string limitations. https://www.victronenergy.com/media/pg/The_Wiring_Unlimited_book/en/battery-bank-wiring.html

Inputs

InputSymbolUnitDefault
Battery entry
Examples are editable starting points. Series batteries meet the inverter DC voltage; parallel strings add Ah. Complete-bank entry uses the existing voltage/Ah fields and leaves individual-battery cards blank.
bank_entryExample or custom individual batteries
Battery and inverter example
Use Custom to edit any example. The 1500 VA examples use two 12 V batteries in series for a 24 V inverter. Inverter watts and VA are different limits.
system12 V 200 Ah + 900 VA / 756 W
Load to calculate
For the reverse question, select a 3000 W example and Full inverter rated watts. That mode is a constant resistive-equivalent wattage with no assumed motor surge.
load_basisMy appliances: fans, lights, TV or other loads
Number of load groups
Each slot is one starting group: devices in a slot start together. Use separate slots for motors that start individually. Default groups are two 70 W fans, 40 W of lights and an 80 W TV; all are assumed loads.
N_load3
Load group 1: running power (example: 2 fans)
Sum electrical input watts for this group. Both default fans start together; put them in separate slots if they start individually. Use electrical input, not motor shaft power.
P1W140
Load 1: duty cycle
Percent of the outage spent on. A zero duty cycle excludes this load from runtime and peak sizing.
d1%100
Load 1: total starting / running power
Total starting watts divided by running watts for the whole group. Devices in one slot start together. Enter 1 for a group without a starting surge.
s12
Load 2: running power (example: 4 lights)P2W40
Load 2: duty cycle
Percent of the outage spent on. A zero duty cycle excludes this load from runtime and peak sizing.
d2%100
Load 2: total starting / running power
Total starting watts divided by running watts for the whole group. Devices in one slot start together. Enter 1 for a group without a starting surge.
s21
Load 3: running power (example: TV)P3W80
Load 3: duty cycle
Percent of the outage spent on. A zero duty cycle excludes this load from runtime and peak sizing.
d3%100
Load 3: total starting / running power
Total starting watts divided by running watts for the whole group. Devices in one slot start together. Enter 1 for a group without a starting surge.
s31
Load 4: running powerP4W0
Load 4: duty cycle
Percent of the outage spent on. A zero duty cycle excludes this load from runtime and peak sizing.
d4%100
Load 4: total starting / running power
Total starting watts divided by running watts for the whole group. Devices in one slot start together. Enter 1 for a group without a starting surge.
s41
Nominal bank voltage
Use the voltage of the whole bank. Series connections add voltage; parallel strings add Ah.
V_bankV12
Rated bank capacity
Ah of the whole bank at the rating period below. Two 12 V 100 Ah batteries in series make 24 V 100 Ah.
Q_bankA*h100
Capacity rating period
Use the datasheet rating period: a 100 Ah C20 rating corresponds to a 5 A reference current.
H_rateh20
Peukert exponent
Victron's lead-acid starting estimate is 1.25. Use two datasheet discharge ratings to calibrate it; set 1.00 to disable rate derating (often suitable for lithium).
k_p1.25
Initial state of charge
Measured or estimated charge at the start of the outage.
SOC0%100
Maximum depth of discharge
50% sets a 50% remaining-charge floor. Choose the manufacturer's permitted discharge limit.
DOD%50
Remaining capacity / state of health
90% means an aged bank retains 90% of its rated capacity. This is separate from state of charge.
SOH%100
Temperature correction
Use a manufacturer capacity factor for tubular or lithium batteries. The optional Trojan AGM interpolation is only a rough AGM temperature guide.
temp_modeManufacturer capacity factor
Battery temperature
One physical temperature; the viewer converts it to °F or K when you change display units.
T_C°C25
Capacity at operating temperature
Percent of the rated-temperature capacity available at your operating temperature, from the battery manufacturer.
f_T_user%100
Incremental inverter efficiency
Conversion efficiency excluding the separately entered DC idle draw. If measured efficiency already includes idle losses, enter zero idle draw.
eta_inv%85
Inverter DC idle draw
Continuously drawn from the bank, including when every load is off. Sleep modes are not modeled.
P_idleW10
Permitted continuous battery C-rate
Example only: 0.25 per hour means 0.25C (50 A for 200 Ah). Replace it with the battery/BMS continuous rating. Peukert losses and a hard current limit are different checks.
C_limit1/h0.25
Required backup duration
The minimum Ah result uses the conservative cycling model and the same voltage, discharge allowance, health and temperature.
t_targeth4
Load-group starting sequence
Sequential sizing starts one load group while the other enabled groups remain running. Motors in one slot start together; use separate slots for individual sequencing. Allow all groups to start together after uncontrolled restoration.
start_modeOne load group starts at a time
Conservative load power factor
Used for VA only, for both running and starting. Enter the lower applicable power factor; starting power factor may be lower than running.
PF_load0.9
Power sizing headroom
A chosen design allowance, not a manufacturer rule. Applied to continuous and starting power, not battery runtime.
margin%25

Results

With the default inputs above, the calc gives:

ResultValue
Runtime of the installed bank2.98 h
Batteries needed for target + current (module entry)2
Batteries in each series string (module entry)1
Parallel strings needed (module entry)2
Batteries currently installed (module entry)1
Runtime with the required battery count7.09 h
Minimum bank Ah for target + current252.9 A·h
Installed bank voltage12 V
Installed bank Ah200 A·h
Installed all-loads-running C-rate0.132 1/h
Installed running current per string26.3 A
Average AC load260 W
AC energy for target duration1,040 W·h
Battery current: all loads running26.3 A
Approximate battery starting current40 A
Minimum continuous inverter / generator rating325 W
Minimum surge inverter / generator rating500 W
Minimum continuous apparent-power rating361 VA
Minimum surge apparent-power rating556 VA
Runtime if the average load were constant2.98 h
Maximum mean AC load at these duty cycles501.5 W

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

Victron: 100 Ah at 5 A lasts 20 h

Source: Victron BMV-712 Smart manual, attached PDF page 48 (printed page 44): published 100 Ah, constant 5 A, 20 h example. A 60 W ideal AC load at 12 V represents that current; no discharge reserve or losses are added. The later discharge-rate paragraph confuses charge and current: the rating is 100 Ah, while its 20-hour reference current is 5 A.

Inputs: Number of load groups = 1; Load group 1: running power (example: 2 fans) = 60 W; Load 1: total starting / running power = 1; Maximum depth of discharge = 100 %; Incremental inverter efficiency = 100 %; Inverter DC idle draw = 0 W; Battery entry = Enter complete bank voltage and Ah; the others as above.

ResultSourceThis calc
Average battery current5 A5 A
Runtime of the installed bank20 h20 h

Victron: C5 capacity 75 Ah at 15 A

Source: Victron BMV-712 Smart manual, attached PDF page 49 (printed page 45). Published C20 = 100 Ah and C5 = 75 Ah imply currents 5 A and 15 A. Exponent ln(20/5)/ln(15/5) = 1.261859507 is calibrated to these two independent datasheet-style ratings; expected runtime is the published 5 h.

Inputs: Number of load groups = 1; Load group 1: running power (example: 2 fans) = 180 W; Load 1: total starting / running power = 1; Peukert exponent = 1.262; Maximum depth of discharge = 100 %; Incremental inverter efficiency = 100 %; Inverter DC idle draw = 0 W; Battery entry = Enter complete bank voltage and Ah; the others as above.

ResultSourceThis calc
Average battery current15 A15 A
Runtime of the installed bank5 h5 h

Honda half-horsepower compressor: 975 W running, 1600 W start

Source: Honda Power Equipment, Generator Wattage Estimation Guide, Contractor Applications, Air Compressor 1/2 hp row: 1600 starting W and 975 running W. https://powerequipment.honda.com/generators/generator-wattage-estimation-guide . Manufacturer estimates, not universal appliance ratings.

Inputs: Number of load groups = 1; Load group 1: running power (example: 2 fans) = 975 W; Load 1: total starting / running power = 1.641; Power sizing headroom = 0 %; Conservative load power factor = 1; Battery entry = Enter complete bank voltage and Ah; the others as above.

ResultSourceThis calc
Minimum continuous inverter / generator rating975 W975 W
Minimum surge inverter / generator rating1,600 W1,600 W
Minimum surge apparent-power rating1,600 VA1,600 VA

Trojan AGM: half rated capacity at -18 °C

Source: Trojan AES AGM and Standard AGM battery maintenance, Temperature considerations: published endpoint 50% capacity at -18 °C (0 °F). Only this endpoint is checked; linear interpolation between published endpoints is the calculator's approximation. https://www.trojanbattery.com/trojan-aes-batteries/aes-agm-standard-agm-battery-maintenance

Inputs: Temperature correction = Trojan lead-acid guide (linear approximation); Battery temperature = -18 °C; Battery entry = Enter complete bank voltage and Ah; the others as above.

ResultSourceThis calc
Applied temperature capacity factor0.50.5

Trojan AGM: rated capacity at 27 °C (80.6 °F)

Source: Trojan's published temperature endpoint is 100% capacity at 27 °C. Its displayed 80 °F is rounded; the exact conversion of 27 °C is 80.6 °F. This case checks the physical endpoint using the single Celsius input. Metric/US display conversion is provided by the viewer, not a second calculator input. https://www.trojanbattery.com/trojan-aes-batteries/aes-agm-standard-agm-battery-maintenance

Inputs: Temperature correction = Trojan lead-acid guide (linear approximation); Battery temperature = 27 °C; Battery entry = Enter complete bank voltage and Ah; the others as above.

ResultSourceThis calc
Applied temperature capacity factor11
Battery temperature used in guide27 °C27 °C

Honda household example: 2900 running W, 5300 simultaneous-start W

Source: Honda, What size generator do I need?, household example table: refrigerator 1600/200 W start/run, furnace 1600/600 W, five lights 300/300 W, TV 300/300 W, microwave 1500/1500 W; published totals 5300/2900 W. Lights and TV combine into one 600 W non-surge slot. This test deliberately selects simultaneous starting; Honda's later managed-load 3000 W example has a different switching schedule. https://powerequipment.honda.com/generators/generator-how-much-power

Inputs: Number of load groups = 4; Load group 1: running power (example: 2 fans) = 200 W; Load 2: running power (example: 4 lights) = 600 W; Load 3: running power (example: TV) = 600 W; Load 4: running power = 1,500 W; Load 1: total starting / running power = 8; Load 2: total starting / running power = 2.667; Power sizing headroom = 0 %; Conservative load power factor = 1; Load-group starting sequence = All load groups start together; Battery entry = Enter complete bank voltage and Ah; the others as above.

ResultSourceThis calc
All enabled loads running2,900 W2,900 W
Minimum continuous inverter / generator rating2,900 W2,900 W
Minimum surge inverter / generator rating5,300 W5,300 W

Exide 150 Ah C20: 7.5 A for 20 hours

Source: Exide IT500 product page publishes 150 Ah at C20; Exide battery selector identifies the 12 V inverter application. Thus the independent rating current is 150/20 = 7.5 A for 20 h. A lossless 90 W load at 12 V represents that rating. This verifies the example selection and rated-current behavior, not real inverter efficiency. https://www.exidecare.com/find-exide/products/exide-inva-tubular/it500

Inputs: Battery and inverter example = 12 V 150 Ah + 900 VA / 756 W; Number of load groups = 1; Load group 1: running power (example: 2 fans) = 90 W; Load 1: total starting / running power = 1; Maximum depth of discharge = 100 %; Incremental inverter efficiency = 100 %; Inverter DC idle draw = 0 W; Permitted continuous battery C-rate = 1 1/h; the others as above.

ResultSourceThis calc
Average battery current7.5 A7.5 A
Runtime of the installed bank20 h20 h
Nominal stored energy1,800 W·h1,800 W·h

Victron series-bank example: four batteries, 48 V / 200 Ah / 9600 Wh

Source: Victron Wiring Unlimited, section 3.1, four batteries in series illustration: 48 V / 200 Ah / 9600 Wh. The example uses four 12 V 200 Ah batteries; series increases voltage without increasing Ah. The selected 480 W ideal load implies 10 A by P/V. https://www.victronenergy.com/media/pg/The_Wiring_Unlimited_book/en/battery-bank-wiring.html

Inputs: Battery and inverter example = 3000 W inverter / 48 V / 200 Ah batteries; Number of load groups = 1; Load group 1: running power (example: 2 fans) = 480 W; Load 1: total starting / running power = 1; Maximum depth of discharge = 100 %; Incremental inverter efficiency = 100 %; Inverter DC idle draw = 0 W; Permitted continuous battery C-rate = 1 1/h; the others as above.

ResultSourceThis calc
Nominal stored energy9,600 W·h9,600 W·h
Average battery current10 A10 A

Luminous 1500 VA example uses two batteries at 24 V

Source: Luminous Power Sine M 1700 product page states 1500 VA / 1260 W and a 24 V dual-battery system using two 12 V batteries. This checks the example data and series topology, not efficiency or runtime. The 150 Ah individual capacity follows Exide IT500 C20. Product data checked 2026-10-25. https://www.luminousindia.com/home-inverters/power-sine-m-1700

Inputs: Battery and inverter example = 2 × 12 V 150 Ah + 1500 VA / 1260 W; the others as above.

ResultSourceThis calc
Installed bank voltage24 V24 V
Installed bank Ah150 A·h150 A·h
Whole batteries per series string22
Installed individual batteries22
Chosen inverter continuous watts1,260 W1,260 W
Chosen inverter continuous apparent power1,500 VA1,500 VA

Runtime curve stops at the inverter's published 756 W

Source: Luminous Zolt 1100 product page, technical specifications: 756 W continuous and 900 VA. With C_limit set to an illustrative 1C and unity load power factor, the watt rating is the active limit. The runtime curve's highest plotted load must be 756 W, not the previous 1512 W extrapolation. https://www.luminousindia.com/home-inverters/zolt-1100

Inputs: Load to calculate = Full inverter rated watts: how many batteries?; Permitted continuous battery C-rate = 1 1/h; Conservative load power factor = 1; the others as above.

ResultSourceThis calc
Mean AC power over the load sweep [61]756 W756 W

Runtime curve respects 900 VA at an assumed 0.5 power factor

Source: Luminous Zolt 1100 product page publishes 900 VA and 756 W. At the explicitly assumed load power factor of 0.5, 900 VA permits 450 W; VA is the active boundary. The 0.5 power factor is a test input, not an inverter specification. https://www.luminousindia.com/home-inverters/zolt-1100

Inputs: Load to calculate = Full inverter rated watts: how many batteries?; Permitted continuous battery C-rate = 1 1/h; Conservative load power factor = 0.5; the others as above.

ResultSourceThis calc
Mean AC power over the load sweep [61]450 W450 W

Related Resources

Responses

Your email address will not be published. Required fields are marked *

L ading...