R290 Heat Pump Charge, Room Size and Leak Concentration
Compare R290 charge limits by floor area and installation height. Explore a hole leak, floor accumulation, air changes and detector response, with R32 sizing alongside.
Caution
R290 is propane: a leak collects near the floor and can ignite even when the charge is within these limits. Follow the appliance's installation instructions and keep ignition sources away from low spots near it.
This R290 charge limit and room size calculator helps engineers, students and heat-pump owners explore an indoor installation before comparing it with the appliance manual. Enter the complete circuit charge, the room floor area and the lowest installation release height. Choose a design path only when it is documented for the particular appliance.
The sizing calculation follows published descriptions of IEC 60335-2-40:2022, Edition 7, Annex GG. It calculates the basic area-and-height limit and its inverse minimum room area, enhanced-tightness and integral-airflow envelopes, and the three charge thresholds. A separate ventilated-enclosure option shows the special charge cap; its zero formula area means that this room-area equation does not apply. It does not approve an enclosure. Charges above a pathway’s total-charge cap cannot be made acceptable by increasing room area.
Installation height matters because refrigerant released from a higher point can disperse before reaching the floor. Use the manufacturer’s release height, rather than the cabinet centre or an arbitrary mounting measurement. A tested limited releasable charge may be entered when documented; a detector added to a room does not establish that tested value. The R32 comparison uses its A2L thresholds and basic sizing criterion at the same total circuit charge.
The refrigerant leak concentration calculation is a separate scenario. Select liquid or vapour feed, upstream conditions and an equivalent hole diameter. The liquid option assumes immediate evaporation after an incompressible orifice release. The vapour option includes choked and unchoked compressible flow. Both hold upstream conditions constant until the available mass has escaped or isolation limits the release.
Play the leak time to see the floor accumulation develop and clear. Compare the floor concentration with the well-mixed room curve, and inspect the LFL contour and flammable band between the lower and upper limits. Duration above LFL is counted only within the simulation window. Increase that window when the final concentration remains high. Detector scenarios can start outdoor exhaust, close a valve after a delay, or do both. Their timing is driven by the floor-model concentration at the chosen sensor height.
The floor source depth and vertical diffusivity are assumptions to vary, not measured predictions of a particular room. The calculation does not resolve a cold jet, local pockets, stairwells, drains, pits, combustion, pressure relief or oxygen deficiency. A low room average cannot establish the absence of a local flammable mixture.
Regulatory context is checked as of 2 November 2026. Regulation (EU) 2024/573 restricts placing certain self-contained heat pumps up to 12 kW and split air-to-water systems up to 12 kW with F-gas GWP ≥150 on the market from 2027, subject to safety exceptions. The corresponding split air-to-air date is 2029. These rules do not authorize an indoor R290 installation. Installation work belongs to a qualified person; check the appliance instructions, applicable national adoption, EN 378 requirements and the standard in force.
How it is calculated
Charge sizing. IEC 60335-2-40:2022 Ed. 7, Annex GG: GG.1–GG.2 establish applicability, thresholds and the basic unventilated-room route; GG.3–GG.5 concern ventilated enclosures and machinery rooms; GG.13–GG.14 concern A2/A3 circulation airflow and enhanced tightness. Annex LL addresses detection and Annex QQ tested releasable charge. Clause-level applicability and test details were not checked against licensed text.
The published basic relation is , inverted for minimum area. For R290, , , . GIZ (2025, printed p.35) supplies the basic, enhanced-tightness and integral-airflow relations. Here m. The direct indoor routes are capped at ; below there is no area criterion from these equations. GIZ’s heat-pump report (2022, pp.23–24) describes for a qualifying ventilated enclosure. Zero area in that row means no area equation is evaluated. The total circuit cap remains independent of any tested releasable mass.
R32 uses kg/m³ and threshold multipliers 6, 52 and 260; its basic minimum area also satisfies (EMSD 2020, printed pp.6–7).
Hole release. Liquid feed uses . Vapour feed uses the ideal-gas isentropic nozzle relation, switching at the critical pressure ratio (NASA Glenn). Density, molar mass and heat-capacity ratio come from CoolProp at the entered states. Source pressure and temperature remain fixed during the release.
Room transport, derived here. Let . Solve , with zero diffusive flux at floor and ceiling. A cosine expansion integrates each linear mode analytically over constant-source/removal intervals. The zero mode is the well-mixed comparison, . Its analytical ventilation integral independently accounts for exhausted mass.
Before release completion, the rising analytical sensor solution is searched by bisection. After release completion, a chronological interval search bounds the analytical exponential sum and its derivatives, locates interior sensor maxima, and refines the earliest threshold crossing. This detector search is independent of chart sampling. Exhaust changes the uniform removal rate after the response delay. Isolation limits the source to the mass released before closure plus the specified trapped tail. Both room models use that same release and control history. Threshold durations are interpolated between time samples. LFL and UFL heights are roots of the modal profile, bisected to the specified height tolerance independently of the drawing grid; the flammable band excludes concentrations above UFL.
Assumptions
One closed room, initially free of refrigerant, with constant air temperature, atmospheric pressure and floor area. Lateral spreading to the floor is assumed immediate; the exponential floor source and prescribed vertical diffusivity represent stratification without resolving the gravity current. Outdoor-air removal acts uniformly at each height with clean makeup air. Recirculation alone removes no mass.
The transient is a dilute, isothermal dispersion model derived here, separate from the Annex GG charge equations. The 2.1–9.5 vol% propane flammability interval is from NIOSH; ambient vapour density converts it to mass concentrations. The standard sizing LFL remains the prescribed 0.038 kg/m³. Temperature-dependent combustion limits are not modelled.
Liquid release neglects flashing restrictions and boiling delay; vapour release neglects real-gas nozzle corrections. Neither is a refrigerant-circuit blowdown calculation. Automatic exhaust remains active after triggering; no detector reset, fault probability or valve leakage is modelled. The section drawing has a schematic horizontal width because floor area alone does not define a room aspect ratio.
The diffusivity input is displayed in cm²/s and explicitly converted to m²/s before evaluating the transport modes.
Where it applies
This implements the requested 2022 Edition 7 framework, not a complete installation conformity assessment. IEC lists a later edition. The paywalled Annex GG text, detailed airflow and outlet-velocity requirements, sensor qualification, enclosure pressure/duct tests, enhanced-tightness construction, compressor location restrictions and Annex QQ release tests were not independently verified. Conditional sizing paths apply only to a product documented for them; adding room ventilation or a detector does not create eligibility. A ventilated enclosure requires separation from the occupied room, monitored discharge outdoors and its applicable product tests; the number alone is insufficient.
EN 378-1:2016+A1:2020 Annex C also requires installation/access and location classification; that full selection is outside this calculator. Check against the standard in force, national adoption and manufacturer instructions. For an intact ventilated enclosure, gas is discharged outside: the room leak simulation instead represents an escape into the room or containment failure.
Floor concentration depends strongly on the assumed source-depth scale and mixing diffusivity. This vertically resolved screening model cannot exclude more severe local concentrations, especially near a jet or in a pit. Above 10 vol% the dilute assumption is flagged. The LFL-equivalent layer height is a mass/threshold-volume measure; it is distinct from the computed LFL contour and the LFL-to-UFL flammable band.
Default resolution is 128 vertical harmonics and 1,800 time intervals; both are exposed for refinement. Modes and detector events use analytical solutions; peak sampling and time above threshold still depend on chart time resolution. The below-LFL verdict applies only to the simulated window, and an unfinished release prompts extending that window. Contour-height roots use an independent absolute tolerance, entered in mm. Small negative spectral tails are clipped only in reconstructed profiles; conservation uses the unmodified mean mode. Animation interpolates modal states in time and displays a smooth vertical colour field. A coarse source representation or a release shorter than ten sampling intervals is flagged.
References
- IEC 60335-2-40:2022, Ed.7, Annex GG and Annexes LL/QQ; official edition record: https://webstore.iec.ch/en/publication/62837
- GIZ (2025), R290 Split Air Conditioners Resource Guide, version 2.02, printed pp.34–36: https://www.green-cooling-initiative.org/fileadmin/R290_Split_Air_Conditioners_Resource_Guide__Update_2025_/ResourceGuide_R290_Split_AC_update.pdf
- GIZ (2022), Can refrigerants with a GWP below 150 be used for Heat Pumps in Europe?, sections 2.1–2.4: https://www.green-cooling-initiative.org/fileadmin/user_upload/Report_Can_HCs_be_used_for_HPs_in_Europe_2022.pdf
- UNEP TEAP (2021), Energy Efficiency report, Annex 2, printed p.142 (draft Ed.7 worked examples): https://ozone.unep.org/system/files/documents/TEAP-EETF-report-may2021.pdf
- EIA US and Daniel Colbourne (2025), Enabling Ultra-low GWP Cooling and Heating, printed pp.5–6: https://eia.org/wp-content/uploads/2025/09/Enabling-Ultra-low-GWP-Heating-and-Cooling-Updating-U.S.-Safety-Standards-and-Codes.pdf
- EMSD (2020), Guidance Note on Household Air-conditioners Using Mildly Flammable Refrigerant, printed pp.6–7: https://www.emsd.gov.hk/frsafety/filemanager/en/publication/gn_household_air_conditioners.pdf
- EN 378-1:2016+A1:2020, Annex C, classification context; edition record: https://doi.org/10.3403/30291772
- Regulation (EU) 2024/573, Annex IV points 8(b) and 9(b)/(c), date context 2026-11-02: https://eur-lex.europa.eu/eli/reg/2024/573/oj
- European Commission, Air conditioning – Climate-friendly alternatives to F-gases: https://climate.ec.europa.eu/areas-action/fluorinated-greenhouse-gases/climate-friendly-alternatives-f-gases/air-conditioning_en
- NASA Glenn, Mass Flow Choking: https://www.grc.nasa.gov/www/BGH/mflchk.html
- NIOSH Pocket Guide, Propane: https://www.cdc.gov/niosh/npg/npgd0524.html
- Bell et al. (2014), CoolProp fluid property library: https://doi.org/10.1021/ie4033999
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| Room floor area | A_room | m^2 | 30 |
| Ceiling height | H_room | m | 2.5 |
| Installation release height Use the lowest possible release point stated by the appliance manufacturer. | h_0 | m | 1.8 |
| Total circuit charge | m_c | kg | 0.5 |
| Documented appliance design Choose only a design path documented for this appliance. | route | Basic room area / height | |
| Tested limited releasable charge Enable only when the manufacturer supplies a tested releasable mass. | limited | false | |
| Tested releasable mass This changes the room calculation; the total-charge cap still applies. | m_test | kg | 0.3 |
| Room temperature | T_room | °C | 20 |
| Atmospheric pressure | p_room | kPa | 101.325 |
| Hole feed phase | feed | Liquid orifice, immediate evaporation | |
| Upstream temperature | T_up | °C | 35 |
| Upstream absolute pressure | p_up | bar | 14 |
| Equivalent hole diameter | d_hole | mm | 0.3 |
| Discharge coefficient A scenario assumption for the hole geometry, not a refrigerant property. | C_d | 0.62 | |
| Background air changes | ACH | h^-1 | 0.5 |
| Vertical mixing diffusivity Prescribed floor-layer mixing; vary this widely when room mixing is unknown. | K_z | cm^2/s | 0.2 |
| Floor source depth scale The assumed floor source decreases exponentially with this height scale. | h_s | m | 0.1 |
| Detector response scenario | response | No automatic response | |
| Detector height | h_det | m | 0.15 |
| Detector threshold / LFL | f_det | 0.25 | |
| Response delay | t_delay | s | 10 |
| Emergency total air changes Outdoor exhaust with clean makeup; recirculation does not remove refrigerant. | ACH_em | h^-1 | 6 |
| Mass released after valve closure Trapped indoor refrigerant continues to leak at the same source rate. | m_tail | kg | 0.05 |
| Simulation duration | t_end | s | 1800 |
| Vertical harmonics | N_modes | 128 | |
| Time intervals | N_time | 1800 | |
| Leak time | t_show | s | 300 |
| Contour height tolerance | eps_z | mm | 0.001 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Charge envelope | Increase area or change appliance |
| Selected charge envelope | 0.414 kg |
| Formula minimum room area | 43.86 m² |
| Selected charge envelope use | 1.209 |
| Leak concentration | Floor exceeds LFL in simulated window |
| Initial leak rate | 1.542 g/s |
| Release stop time | 324.2 s |
| Peak floor concentration | 0.0997 kg/m³ |
| Peak floor concentration / LFL | 2.545 |
| Peak well-mixed concentration / LFL | 0.166 |
| Floor time ≥ LFL in simulated window | 1,543.9 s |
| Mixed time ≥ LFL in simulated window | 0 s |
| Flammable band at shown time | 0.158 m |
| LFL contour height at shown time | 0.158 m |
| Mass released in simulated window | 0.5 kg |
| Mass remaining in room at end | 0.398 kg |
| Mass exhausted by simulation end | 0.102 kg |
| R32 basic charge envelope for this room | 5.632 kg |
| R32 minimum area at same total charge | 0 m² |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
UNEP: 30 m² wall-mounted basic example
Source: UNEP TEAP May 2021, printed p.142 (attached PDF p.154), draft Ed.7 example; 0.414 kg rounded to three decimals. The correct unrounded value is about 0.41353 kg.
Inputs: the default inputs above.
| Result | Source | This calc |
|---|---|---|
| Selected charge envelope | 0.414 ± 0.002 kg | 0.4135 kg |
UNEP: 30 m² enhanced-tightness example
Source: UNEP TEAP May 2021, printed p.142 (attached PDF p.154), draft Ed.7 example; 0.718 kg is rounded.
Inputs: Documented appliance design = Enhanced tightness; the others as above.
| Result | Source | This calc |
|---|---|---|
| Selected charge envelope | 0.718 ± 0.001 kg | 0.7182 kg |
UNEP: circulation airflow reaches charge cap
Source: UNEP TEAP May 2021, printed p.142 (attached PDF p.154). The reported 0.99 kg is rounded; 26 × 0.038 gives the implemented 0.988 kg cap.
Inputs: Documented appliance design = Integral circulation airflow; the others as above.
| Result | Source | This calc |
|---|---|---|
| Selected charge envelope | 0.99 ± 0.003 kg | 0.988 kg |
EIA: R290 threshold masses
Source: EIA US and Colbourne 2025, printed p.6, published charge-threshold values for IEC Edition 7.
Inputs: the default inputs above.
| Result | Source | This calc |
|---|---|---|
| R290 no-area threshold | 0.152 kg | 0.152 kg |
| R290 direct indoor cap | 0.988 kg | 0.988 kg |
| R290 special arrangement cap | 4.94 kg | 4.94 kg |
EMSD: R32 small-charge area exemption
Source: EMSD 2020, printed pp.6–7: R32 m₁ = 6 LFL, LFL 0.307 kg/m³; charges at or below m₁ have no area criterion. The 1.5 kg example is within that published exemption.
Inputs: Total circuit charge = 1.5 kg; the others as above.
| Result | Source | This calc |
|---|---|---|
| R32 minimum area at same total charge | 0 m² | 0 m² |
| R32 standard LFL | 0.307 kg/m³ | 0.307 kg/m³ |

Responses