R290 Heat Pump Charge, Room Size and Leak Concentration

Compare R290 charge limits by floor area and installation height. Explore a hole leak, floor accumulation, air changes and detector response, with R32 sizing alongside.

#heat pumps #IEC 60335-2-40 #leak dispersion #R290 #R32 #refrigerant charge #root finding #ventilation

Caution

R290 is propane: a leak collects near the floor and can ignite even when the charge is within these limits. Follow the appliance's installation instructions and keep ignition sources away from low spots near it.

This R290 charge limit and room size calculator helps engineers, students and heat-pump owners explore an indoor installation before comparing it with the appliance manual. Enter the complete circuit charge, the room floor area and the lowest installation release height. Choose a design path only when it is documented for the particular appliance.

The sizing calculation follows published descriptions of IEC 60335-2-40:2022, Edition 7, Annex GG. It calculates the basic area-and-height limit and its inverse minimum room area, enhanced-tightness and integral-airflow envelopes, and the three charge thresholds. A separate ventilated-enclosure option shows the special charge cap; its zero formula area means that this room-area equation does not apply. It does not approve an enclosure. Charges above a pathway’s total-charge cap cannot be made acceptable by increasing room area.

Installation height matters because refrigerant released from a higher point can disperse before reaching the floor. Use the manufacturer’s release height, rather than the cabinet centre or an arbitrary mounting measurement. A tested limited releasable charge may be entered when documented; a detector added to a room does not establish that tested value. The R32 comparison uses its A2L thresholds and basic sizing criterion at the same total circuit charge.

The refrigerant leak concentration calculation is a separate scenario. Select liquid or vapour feed, upstream conditions and an equivalent hole diameter. The liquid option assumes immediate evaporation after an incompressible orifice release. The vapour option includes choked and unchoked compressible flow. Both hold upstream conditions constant until the available mass has escaped or isolation limits the release.

Play the leak time to see the floor accumulation develop and clear. Compare the floor concentration with the well-mixed room curve, and inspect the LFL contour and flammable band between the lower and upper limits. Duration above LFL is counted only within the simulation window. Increase that window when the final concentration remains high. Detector scenarios can start outdoor exhaust, close a valve after a delay, or do both. Their timing is driven by the floor-model concentration at the chosen sensor height.

The floor source depth and vertical diffusivity are assumptions to vary, not measured predictions of a particular room. The calculation does not resolve a cold jet, local pockets, stairwells, drains, pits, combustion, pressure relief or oxygen deficiency. A low room average cannot establish the absence of a local flammable mixture.

Regulatory context is checked as of 2 November 2026. Regulation (EU) 2024/573 restricts placing certain self-contained heat pumps up to 12 kW and split air-to-water systems up to 12 kW with F-gas GWP ≥150 on the market from 2027, subject to safety exceptions. The corresponding split air-to-air date is 2029. These rules do not authorize an indoor R290 installation. Installation work belongs to a qualified person; check the appliance instructions, applicable national adoption, EN 378 requirements and the standard in force.

How it is calculated

Charge sizing. IEC 60335-2-40:2022 Ed. 7, Annex GG: GG.1–GG.2 establish applicability, thresholds and the basic unventilated-room route; GG.3–GG.5 concern ventilated enclosures and machinery rooms; GG.13–GG.14 concern A2/A3 circulation airflow and enhanced tightness. Annex LL addresses detection and Annex QQ tested releasable charge. Clause-level applicability and test details were not checked against licensed text.

The published basic relation is mmax=2.5 LFL5/4h0Am_{max}=2.5\,LFL^{5/4}h_0\sqrt A, inverted for minimum area. For R290, m1=4LFLm_1=4LFL, m2=26LFLm_2=26LFL, m3=130LFLm_3=130LFL. GIZ (2025, printed p.35) supplies the basic, 0.35LFLh0A0.35LFLh_0A enhanced-tightness and 0.50LFLHeffA0.50LFLH_{eff}A integral-airflow relations. Here Heff=2.2H_{eff}=2.2 m. The direct indoor routes are capped at m2m_2; below m1m_1 there is no area criterion from these equations. GIZ’s heat-pump report (2022, pp.23–24) describes m3m_3 for a qualifying ventilated enclosure. Zero area in that row means no area equation is evaluated. The total circuit cap remains independent of any tested releasable mass.

R32 uses LFL=0.307LFL=0.307 kg/m³ and threshold multipliers 6, 52 and 260; its basic minimum area also satisfies mc/(0.75LFLh0)m_c/(0.75LFLh_0) (EMSD 2020, printed pp.6–7).

Hole release. Liquid feed uses m˙=CdAo2ρu(pu−pa)\dot m=C_dA_o\sqrt{2\rho_u(p_u-p_a)}. Vapour feed uses the ideal-gas isentropic nozzle relation, switching at the critical pressure ratio (NASA Glenn). Density, molar mass and heat-capacity ratio come from CoolProp at the entered states. Source pressure and temperature remain fixed during the release.

Room transport, derived here. Let S(z)=e−z/hs/[hs(1−e−H/hs)]S(z)=e^{-z/h_s}/[h_s(1-e^{-H/h_s})]. Solve ∂tc=Kz∂zzc−λc+m˙S(z)/A\partial_t c=K_z\partial_{zz}c-\lambda c+\dot m S(z)/A, with zero diffusive flux at floor and ceiling. A cosine expansion integrates each linear mode analytically over constant-source/removal intervals. The zero mode is the well-mixed comparison, dcˉ/dt=m˙/V−λcˉd\bar c/dt=\dot m/V-\lambda\bar c. Its analytical ventilation integral independently accounts for exhausted mass.

Before release completion, the rising analytical sensor solution is searched by bisection. After release completion, a chronological interval search bounds the analytical exponential sum and its derivatives, locates interior sensor maxima, and refines the earliest threshold crossing. This detector search is independent of chart sampling. Exhaust changes the uniform removal rate after the response delay. Isolation limits the source to the mass released before closure plus the specified trapped tail. Both room models use that same release and control history. Threshold durations are interpolated between time samples. LFL and UFL heights are roots of the modal profile, bisected to the specified height tolerance independently of the drawing grid; the flammable band excludes concentrations above UFL.

Assumptions

One closed room, initially free of refrigerant, with constant air temperature, atmospheric pressure and floor area. Lateral spreading to the floor is assumed immediate; the exponential floor source and prescribed vertical diffusivity represent stratification without resolving the gravity current. Outdoor-air removal acts uniformly at each height with clean makeup air. Recirculation alone removes no mass.

The transient is a dilute, isothermal dispersion model derived here, separate from the Annex GG charge equations. The 2.1–9.5 vol% propane flammability interval is from NIOSH; ambient vapour density converts it to mass concentrations. The standard sizing LFL remains the prescribed 0.038 kg/m³. Temperature-dependent combustion limits are not modelled.

Liquid release neglects flashing restrictions and boiling delay; vapour release neglects real-gas nozzle corrections. Neither is a refrigerant-circuit blowdown calculation. Automatic exhaust remains active after triggering; no detector reset, fault probability or valve leakage is modelled. The section drawing has a schematic horizontal width because floor area alone does not define a room aspect ratio.

The diffusivity input is displayed in cm²/s and explicitly converted to m²/s before evaluating the transport modes.

Where it applies

This implements the requested 2022 Edition 7 framework, not a complete installation conformity assessment. IEC lists a later edition. The paywalled Annex GG text, detailed airflow and outlet-velocity requirements, sensor qualification, enclosure pressure/duct tests, enhanced-tightness construction, compressor location restrictions and Annex QQ release tests were not independently verified. Conditional sizing paths apply only to a product documented for them; adding room ventilation or a detector does not create eligibility. A ventilated enclosure requires separation from the occupied room, monitored discharge outdoors and its applicable product tests; the m3m_3 number alone is insufficient.

EN 378-1:2016+A1:2020 Annex C also requires installation/access and location classification; that full selection is outside this calculator. Check against the standard in force, national adoption and manufacturer instructions. For an intact ventilated enclosure, gas is discharged outside: the room leak simulation instead represents an escape into the room or containment failure.

Floor concentration depends strongly on the assumed source-depth scale and mixing diffusivity. This vertically resolved screening model cannot exclude more severe local concentrations, especially near a jet or in a pit. Above 10 vol% the dilute assumption is flagged. The LFL-equivalent layer height is a mass/threshold-volume measure; it is distinct from the computed LFL contour and the LFL-to-UFL flammable band.

Default resolution is 128 vertical harmonics and 1,800 time intervals; both are exposed for refinement. Modes and detector events use analytical solutions; peak sampling and time above threshold still depend on chart time resolution. The below-LFL verdict applies only to the simulated window, and an unfinished release prompts extending that window. Contour-height roots use an independent absolute tolerance, entered in mm. Small negative spectral tails are clipped only in reconstructed profiles; conservation uses the unmodified mean mode. Animation interpolates modal states in time and displays a smooth vertical colour field. A coarse source representation or a release shorter than ten sampling intervals is flagged.

References

  • IEC 60335-2-40:2022, Ed.7, Annex GG and Annexes LL/QQ; official edition record: https://webstore.iec.ch/en/publication/62837
  • GIZ (2025), R290 Split Air Conditioners Resource Guide, version 2.02, printed pp.34–36: https://www.green-cooling-initiative.org/fileadmin/R290_Split_Air_Conditioners_Resource_Guide__Update_2025_/ResourceGuide_R290_Split_AC_update.pdf
  • GIZ (2022), Can refrigerants with a GWP below 150 be used for Heat Pumps in Europe?, sections 2.1–2.4: https://www.green-cooling-initiative.org/fileadmin/user_upload/Report_Can_HCs_be_used_for_HPs_in_Europe_2022.pdf
  • UNEP TEAP (2021), Energy Efficiency report, Annex 2, printed p.142 (draft Ed.7 worked examples): https://ozone.unep.org/system/files/documents/TEAP-EETF-report-may2021.pdf
  • EIA US and Daniel Colbourne (2025), Enabling Ultra-low GWP Cooling and Heating, printed pp.5–6: https://eia.org/wp-content/uploads/2025/09/Enabling-Ultra-low-GWP-Heating-and-Cooling-Updating-U.S.-Safety-Standards-and-Codes.pdf
  • EMSD (2020), Guidance Note on Household Air-conditioners Using Mildly Flammable Refrigerant, printed pp.6–7: https://www.emsd.gov.hk/frsafety/filemanager/en/publication/gn_household_air_conditioners.pdf
  • EN 378-1:2016+A1:2020, Annex C, classification context; edition record: https://doi.org/10.3403/30291772
  • Regulation (EU) 2024/573, Annex IV points 8(b) and 9(b)/(c), date context 2026-11-02: https://eur-lex.europa.eu/eli/reg/2024/573/oj
  • European Commission, Air conditioning – Climate-friendly alternatives to F-gases: https://climate.ec.europa.eu/areas-action/fluorinated-greenhouse-gases/climate-friendly-alternatives-f-gases/air-conditioning_en
  • NASA Glenn, Mass Flow Choking: https://www.grc.nasa.gov/www/BGH/mflchk.html
  • NIOSH Pocket Guide, Propane: https://www.cdc.gov/niosh/npg/npgd0524.html
  • Bell et al. (2014), CoolProp fluid property library: https://doi.org/10.1021/ie4033999

Inputs

InputSymbolUnitDefault
Room floor areaA_roomm^230
Ceiling heightH_roomm2.5
Installation release height
Use the lowest possible release point stated by the appliance manufacturer.
h_0m1.8
Total circuit chargem_ckg0.5
Documented appliance design
Choose only a design path documented for this appliance.
routeBasic room area / height
Tested limited releasable charge
Enable only when the manufacturer supplies a tested releasable mass.
limitedfalse
Tested releasable mass
This changes the room calculation; the total-charge cap still applies.
m_testkg0.3
Room temperatureT_room°C20
Atmospheric pressurep_roomkPa101.325
Hole feed phasefeedLiquid orifice, immediate evaporation
Upstream temperatureT_up°C35
Upstream absolute pressurep_upbar14
Equivalent hole diameterd_holemm0.3
Discharge coefficient
A scenario assumption for the hole geometry, not a refrigerant property.
C_d0.62
Background air changesACHh^-10.5
Vertical mixing diffusivity
Prescribed floor-layer mixing; vary this widely when room mixing is unknown.
K_zcm^2/s0.2
Floor source depth scale
The assumed floor source decreases exponentially with this height scale.
h_sm0.1
Detector response scenarioresponseNo automatic response
Detector heighth_detm0.15
Detector threshold / LFLf_det0.25
Response delayt_delays10
Emergency total air changes
Outdoor exhaust with clean makeup; recirculation does not remove refrigerant.
ACH_emh^-16
Mass released after valve closure
Trapped indoor refrigerant continues to leak at the same source rate.
m_tailkg0.05
Simulation durationt_ends1800
Vertical harmonicsN_modes128
Time intervalsN_time1800
Leak timet_shows300
Contour height toleranceeps_zmm0.001

Results

With the default inputs above, the calc gives:

ResultValue
Charge envelopeIncrease area or change appliance
Selected charge envelope0.414 kg
Formula minimum room area43.86 m²
Selected charge envelope use1.209
Leak concentrationFloor exceeds LFL in simulated window
Initial leak rate1.542 g/s
Release stop time324.2 s
Peak floor concentration0.0997 kg/m³
Peak floor concentration / LFL2.545
Peak well-mixed concentration / LFL0.166
Floor time ≥ LFL in simulated window1,543.9 s
Mixed time ≥ LFL in simulated window0 s
Flammable band at shown time0.158 m
LFL contour height at shown time0.158 m
Mass released in simulated window0.5 kg
Mass remaining in room at end0.398 kg
Mass exhausted by simulation end0.102 kg
R32 basic charge envelope for this room5.632 kg
R32 minimum area at same total charge0 m²

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

UNEP: 30 m² wall-mounted basic example

Source: UNEP TEAP May 2021, printed p.142 (attached PDF p.154), draft Ed.7 example; 0.414 kg rounded to three decimals. The correct unrounded value is about 0.41353 kg.

Inputs: the default inputs above.

ResultSourceThis calc
Selected charge envelope0.414 ± 0.002 kg0.4135 kg

UNEP: 30 m² enhanced-tightness example

Source: UNEP TEAP May 2021, printed p.142 (attached PDF p.154), draft Ed.7 example; 0.718 kg is rounded.

Inputs: Documented appliance design = Enhanced tightness; the others as above.

ResultSourceThis calc
Selected charge envelope0.718 ± 0.001 kg0.7182 kg

UNEP: circulation airflow reaches charge cap

Source: UNEP TEAP May 2021, printed p.142 (attached PDF p.154). The reported 0.99 kg is rounded; 26 × 0.038 gives the implemented 0.988 kg cap.

Inputs: Documented appliance design = Integral circulation airflow; the others as above.

ResultSourceThis calc
Selected charge envelope0.99 ± 0.003 kg0.988 kg

EIA: R290 threshold masses

Source: EIA US and Colbourne 2025, printed p.6, published charge-threshold values for IEC Edition 7.

Inputs: the default inputs above.

ResultSourceThis calc
R290 no-area threshold0.152 kg0.152 kg
R290 direct indoor cap0.988 kg0.988 kg
R290 special arrangement cap4.94 kg4.94 kg

EMSD: R32 small-charge area exemption

Source: EMSD 2020, printed pp.6–7: R32 m₁ = 6 LFL, LFL 0.307 kg/m³; charges at or below m₁ have no area criterion. The 1.5 kg example is within that published exemption.

Inputs: Total circuit charge = 1.5 kg; the others as above.

ResultSourceThis calc
R32 minimum area at same total charge0 m²0 m²
R32 standard LFL0.307 kg/m³0.307 kg/m³