Off-Grid Solar System Sizing Calculator

Size an off-grid solar array, battery bank, MPPT or PWM controller and inverter from daily loads, sunless days and worst-month peak sun hours.

#autonomy #battery bank #inverter sizing #load audit #MPPT #off-grid PV #peak sun hours #PWM

Use this off grid solar calculator to turn a daily load audit into a preliminary battery bank, solar array, charge controller and inverter specification. It suits cabins, workshops, remote equipment and classroom design exercises. The defaults describe a small system with lighting, refrigeration, electronics, a pump and direct DC loads. Replace them with measured consumption and the electrical data for your equipment.

Start with the load list. Enter the combined running watts for each row, including the number of appliances, and its equivalent full-power hours per day. A refrigerator connected for 24 hours may run its compressor for only part of that time. Add direct DC loads separately. The audit table shows each contribution; the battery-terminal total also includes inverter conversion losses and any additional idle draw.

Choose the number of sunless days the bank should support, its nominal voltage, allowed depth of discharge and retained capacity at the design temperature and age. This solar battery bank calculator gives both the theoretical minimum and a whole-battery arrangement. Series units establish voltage; parallel strings establish ampere-hours. Confirm that the selected batteries and their management system permit that arrangement and can deliver the reported running and starting currents.

For the array, enter peak sun hours from the worst design month at the actual panel orientation and tilt. This is daily irradiation expressed as equivalent hours at full reference irradiance, not the length of the day. Account for local shading. Enter efficiencies as decimal fractions and avoid counting a loss twice. The solar panel calculator rounds the required array up to complete equal strings and plots how the continuous requirement changes with sun availability.

MPPT and PWM use different sizing paths. MPPT works from energy and panel watts; PWM works from ampere-hours and an estimate of module operating current. A PWM array must match the battery's nominal voltage. Check cold open-circuit voltage, hot operating voltage and the controller's permitted PV short-circuit current. The reported controller current is a minimum design target, not a product recommendation.

The inverter must satisfy continuous watts, continuous VA and starting VA for the loads that can operate together. Enter additional motor starting demand above its normal running demand. Check the manufacturer's permitted surge duration and thermal derating.

This is a daily energy-balance sizing method. It conservatively sends all load energy through storage; it does not simulate hourly weather, charge taper, battery chemistry, detailed IV curves or outage probability. The recovery estimate assumes repeated design-average sunshine and unlimited charge acceptance. Cable sizes, protective devices, earthing, structural support and local compliance require separate design. Installation work belongs to a qualified person; check against the standard in force and the equipment instructions.

How it is calculated

Daily AC energy is ∑Pihi\sum P_i h_i. Battery-terminal daily energy is Eb=EAC/ηinv+EDC+PidlehinvE_b=E_{AC}/\eta_{inv}+E_{DC}+P_{idle}h_{inv}. Every listed AC load is assumed capable of running together. Continuous inverter targets are kinvPACk_{inv}P_{AC} and kinvPAC/PFk_{inv}P_{AC}/PF; starting VA includes the entered incremental starting demand. The battery starting-current envelope treats starting VA as W, conservatively. Inverter idle power enters instantaneous current targets only when energized hours are positive.

Battery capacity follows VeraSol (2024), pp.27–33: Enom=EbN/(DOD fcap)E_{nom}=E_b N/(DOD\,f_{cap}) and Cnom=Enom/VbankC_{nom}=E_{nom}/V_{bank}. Divide by individual battery Ah and round parallel strings upward; series units must give the requested bank voltage. Battery energy is quoted at battery terminals, so round-trip efficiency is not applied again to this capacity calculation.

MPPT array sizing follows VeraSol pp.57–59: Preq=kPVEb/(HfPVηwireηCCηb,Wh)P_{req}=k_{PV}E_b/(H f_{PV}\eta_{wire}\eta_{CC}\eta_{b,Wh}). PWM follows pp.53–56: Ireq=kPVQday/(Hηb,Ahηwire)I_{req}=k_{PV}Q_{day}/(H\eta_{b,Ah}\eta_{wire}). Estimate PWM module current as the midpoint of Isc and Imp, then apply its current derating. Imp is computed from rated watts / Vmp. Round up complete parallel PV strings. Controller output rating uses the whole installed array: MPPT kIParray/Vlowk_I P_{array}/V_{low}; PWM kIIsc,arrayk_I I_{sc,array}. Check the separate factored PV short-circuit current against the permitted input limit. Victron (2020), pp.1–4 explains the voltage-to-current conversion distinction.

Cold string voltage uses NsVoc[1+∣βVoc∣ΔT]N_s V_{oc}[1+|\beta_{Voc}|\Delta T] (VeraSol p.64). Hot string Vmp uses the entered retained voltage factor. Ideal recovery divides the discharged autonomy energy by the design-average daily surplus; surplus at or below 1e-9 of daily battery-terminal energy is treated as numerical zero and reported as No surplus. The schematic shows the battery charging from and discharging into the shared DC bus feeding both load branches. This DC-coupled topology is consistent with the Victron SmartSolar installation manual, section 4.6. The drawing is an energy-flow schematic, not a wiring plan.

Assumptions

All daily load energy passes through the battery, including daytime consumption. This is conservative; weather and coincident daytime PV are not simulated. Enter efficiencies and retained fractions as decimals, not percentages. The retained capacity factor covers temperature, age and discharge rate; battery Wh/Ah efficiencies affect array sizing separately.

Default load powers and use times, LFP voltages, 100 Ah battery units, 3 peak sun hours, 0.90 retained battery capacity, 0.85 retained hot Vmp, inverter factors and controller limits are illustrative design inputs, not certified product specifications or local climate data. Default PV module electrical data and Voc coefficient are from VeraSol p.56. The 1.20 array factor suits an illustrative lithium design; use at least the guidance's 1.30 for lead acid unless your documented design supports another allowance.

PWM assumes crystalline modules with a suitable voltage/current plateau; the midpoint-current estimate requires checking against IV curves. PV current factor 1.25 is an editable design allowance. No standard table or jurisdiction-specific protective-device rule is implemented. Temperatures are entered as a Kelvin difference below STC; the field help gives Celsius and Fahrenheit conversions. Electrical quantities use W, Wh, V, A, Ah and VA in both metric and US display modes.

Where it applies

Preliminary sizing of DC-coupled, fixed-load, off-grid PV/battery systems. Results are continuous minimum targets plus whole-component rounding, not a validated bill of materials. Confirm controller power limits, per-tracker current and voltage windows, startup requirements, allowable PV oversizing, connector ratings and thermal derating using actual equipment documentation. Cold Voc must remain below the controller's absolute limit, with any manufacturer-required tolerance margin.

Confirm battery maximum charge/discharge currents, surge duration, BMS compatibility, temperature charging restrictions and allowed series/parallel counts. Larger individual units are preferable to many parallel strings. Lead-acid discharge-rate effects require manufacturer capacity curves; this tool has no Peukert or electrochemical model. Surge VA and watts alone do not establish motor starting success. Recovery can take longer due to absorption/taper and charging-current limits.

Worst-month mean sunshine does not guarantee reliability through an extreme cloudy spell. Use time-series simulation for critical service and assess backup generation separately. No grid interconnection, conductor sizing, overcurrent protection, earthing, lightning, structural, regulatory or cost calculation is included. Installation work belongs to a qualified person. Check against the standard in force and manufacturer instructions.

References

  • VeraSol / Schatz Energy Research Center / GSES, Component-Based Off-Grid Solar Energy Systems: System Design Guidelines (2024), pp.27–35, 50–64. https://verasol.org/wp-content/uploads/2022/06/Design-Guidelines_Component-based-Off-GridSolarEnergySystems_241010.pdf
  • Victron Energy, Which solar charge controller: PWM or MPPT? (20 January 2020), pp.1–4. https://www.victronenergy.com/upload/documents/Technical-Information-Which-solar-charge-controller-PWM-or-MPPT.pdf
  • Victron Energy, SmartSolar MPPT 75/10 up to 100/20, installation manual, section 4.6: DC-coupled PV, battery and load connections. https://www.victronenergy.com/media/pg/Manual_SmartSolar_MPPT_75-10_up_to_100-20/en/installation.html

Inputs

InputSymbolUnitDefault
Lighting: total running power
Combined power of every appliance in this row. Include quantities here; set unused rows to zero.
P_1W40
Lighting: equivalent full-power hours/day
For cycling appliances use equivalent running hours, not elapsed connection time.
h_1h5
Refrigerator: total running power
Combined power of every appliance in this row. Include quantities here; set unused rows to zero.
P_2W100
Refrigerator: equivalent full-power hours/day
For cycling appliances use equivalent running hours, not elapsed connection time.
h_2h8
Electronics: total running power
Combined power of every appliance in this row. Include quantities here; set unused rows to zero.
P_3W100
Electronics: equivalent full-power hours/day
For cycling appliances use equivalent running hours, not elapsed connection time.
h_3h4
Pump / other AC: total running power
Combined power of every appliance in this row. Include quantities here; set unused rows to zero.
P_4W500
Pump / other AC: equivalent full-power hours/day
For cycling appliances use equivalent running hours, not elapsed connection time.
h_4h0.5
Direct DC loads: total running power
Loads on the battery bus. Include any DC converter losses.
P_dcW10
DC loads: equivalent hours/day
Set power to zero if there are no DC loads.
h_dch24
Inverter energy efficiency
Decimal fraction at the expected load; 0.92 means 92%.
eta_inv0.92
Additional inverter idle draw
DC-side overhead not already included in the stated efficiency; avoid counting it twice.
P_idleW8
Inverter energized hours/day
Must cover each AC row's running hours.
h_invh24
Aggregate running power factor
Running W / VA. Check actual appliance VA, especially motors.
pf_ac0.85
Inverter continuous sizing factor
Design allowance, not a regulatory factor.
k_inv1.25
Additional simultaneous starting demand
Starting VA ABOVE running VA. Sum increments for motors that can start together; use measured/nameplate values.
S_extraVA1500
Battery bank nominal voltage
Use actual chemistry voltage, e.g. 25.6 V for an 8-cell LFP bank.
V_bankV25.6
Minimum operating battery voltage
Under-load voltage at the lower operating limit. Used for conservative controller and discharge current ratings.
V_lowV22.4
Maximum battery charging voltage
Manufacturer's charge setting, including temperature compensation where relevant.
V_chargeV28.8
Days of autonomy
Number of days with no solar input, at the entered daily loads.
t_autod2
Allowed depth of discharge
Decimal fraction of nominal capacity. Follow battery manufacturer limits.
dod_max0.8
Retained battery capacity
Combined cold, ageing and discharge-rate capacity fraction. 0.90 leaves 90% available before the DoD limit. This is not round-trip efficiency.
f_cap0.9
Individual battery nominal voltage
Must divide the bank voltage into a whole number of series units. Confirm the battery permits series connection.
V_unitV12.8
Individual battery rated capacity
Rated ampere-hours at the relevant discharge rate. Confirm permitted parallel strings.
C_unitAh100
Worst design month's peak sun hours/day
Daily plane-of-array irradiation divided by 1 kW/m². Use local tilt, orientation and shading; not daylight hours.
H_sunh3
Array oversizing factor
Reserve for ageing and recovery. VeraSol uses at least 1.30 for lead acid and 1.10 for lithium. This does not guarantee a recovery deadline.
k_pv1.2
PV-side wiring efficiency
Decimal fraction. In PWM mode represents current transmission allowance.
eta_wire0.97
Charge controller type
PWM requires a nominal-voltage matched array. MPPT converts excess PV voltage into charging current.
controllerMPPT · size from watts and energy
MPPT: retained module STC power
Combined operating-temperature, dirt and tolerance derating; exclude wiring, controller and battery losses entered separately.
f_pv0.8
MPPT conversion efficiency
Decimal fraction; used in the energy yield, not as a reduction of required controller current rating.
eta_cc0.98
MPPT: battery round-trip energy efficiency
Wh delivered / Wh charged. All daily loads conservatively pass through storage.
eta_bwh0.92
PWM: retained module current
Dirt and tolerance current derating. Default is 0.95 × 0.97, VeraSol Example 20.
f_current0.9215
PWM: battery coulombic efficiency
Ah delivered / Ah charged; different from Wh efficiency.
eta_bah0.9
Module rated STC power
Default module electrical data: VeraSol Example 20, p. 56. Replace with your module datasheet.
P_modW330
Module STC maximum-power voltage
Default 37.8 V from VeraSol Example 20.
V_mpV37.8
Module STC open-circuit voltage
Default 46.2 V from VeraSol Example 20.
V_ocV46.2
Module STC short-circuit current
Default 9.27 A from VeraSol Example 20.
I_scA9.27
PV modules in each series string
The calculator rounds up the number of parallel strings, keeping complete equal strings.
n_series2
Cold design temperature below 25 °C
Temperature DIFFERENCE: 25 °C minus minimum design cell temperature. −10 °C gives 35 K; 20 °C gives 5 K. In Fahrenheit: (77 − Tmin°F) / 1.8.
dT_coldK35
Fractional Voc rise per kelvin of cooling
Enter the POSITIVE magnitude: a datasheet coefficient of −0.29%/°C becomes 0.0029/K.
beta_oc1/K0.0029
Retained Vmp at hottest design cells
Vmp(hot) / Vmp(STC), from temperature coefficients or IV curves. Default 0.85 is an illustrative design allowance; verify for your site.
f_hot0.85
Controller absolute maximum PV voltage
Cold string Voc must remain strictly BELOW this rating. Use the actual controller datasheet.
V_limitV150
Controller maximum permitted PV short-circuit current
Compare with factored whole-array Isc. Limits for connectors, reverse polarity and individual trackers may differ.
I_limitA50
MPPT voltage headroom above charging voltage
Use manufacturer's required hot operating/startup allowance. PWM uses a fixed 0.5 V allowance here.
V_headV5
Controller current sizing factor
User design allowance applied to PV Isc and controller current. Not an NEC or IEC conductor/OCPD calculation.
k_current1.25

Results

With the default inputs above, the calc gives:

ResultValue
Battery-terminal daily energy2,225 Wh
Minimum nominal battery energy6,182 Wh
Minimum bank capacity241.5 Ah
Selected nominal bank energy7,680 Wh
Total individual batteries6
Selected-bank autonomy2.48 d
Minimum array before string rounding1,272 W
Installed array STC power1,320 W
Total PV modules4
Minimum controller output rating73.7 A
PV input short-circuit rating target23.2 A
Cold string open-circuit voltage101.8 V
Inverter continuous real-power target925 W
Inverter continuous apparent-power target1,088 VA
Inverter starting apparent-power target2,371 VA
Bank continuous discharge target36.7 A
Bank starting-current upper estimate115.8 A
Ideal recovery after sunless interval8.2 d

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

VeraSol Example 6 · 2-day battery bank

Source: VeraSol System Design Guidelines (2024), p.30, Worked Example 6. Published energy 6306 Wh and 263 Ah are rounded. Uses 2207 Wh/day already at the battery terminals, not an AC-side load.

Inputs: Lighting: total running power = 0 W; Refrigerator: total running power = 0 W; Electronics: total running power = 0 W; Pump / other AC: total running power = 0 W; Direct DC loads: total running power = 2,207 W; DC loads: equivalent hours/day = 1 h; Additional inverter idle draw = 0 W; Additional simultaneous starting demand = 0 VA; Battery bank nominal voltage = 24 V; Individual battery nominal voltage = 12 V; Minimum operating battery voltage = 21 V; Allowed depth of discharge = 0.7; Retained battery capacity = 1; the others as above.

ResultSourceThis calc
Usable energy for sunless interval4,414 Wh4,414 Wh
Minimum nominal battery energy6,306 Wh6,306 Wh
Minimum bank capacity263 ± 0.5 Ah262.7 Ah

VeraSol Examples 22–23 · MPPT array

Source: VeraSol pp.53,58–59, Examples 18,22–23: 1500 Wh AC / 0.9 + 112 Wh DC; 4.6 PSH; efficiencies 0.97×0.95×0.8; power derate 0.86×0.95×0.97; 1.3 reserve. Intermediate published values are rounded, so the continuous requirement differs slightly. Three series modules follow p.64.

Inputs: Lighting: total running power = 150 W; Lighting: equivalent full-power hours/day = 10 h; Refrigerator: total running power = 0 W; Electronics: total running power = 0 W; Pump / other AC: total running power = 0 W; Direct DC loads: total running power = 28 W; DC loads: equivalent hours/day = 4 h; Additional inverter idle draw = 0 W; Inverter energy efficiency = 0.9; Battery bank nominal voltage = 24 V; Individual battery nominal voltage = 12 V; Minimum operating battery voltage = 21 V; Worst design month's peak sun hours/day = 4.6 h; Array oversizing factor = 1.3; PV modules in each series string = 3; MPPT conversion efficiency = 0.95; MPPT: battery round-trip energy efficiency = 0.8; MPPT: retained module STC power = 0.7925; Cold design temperature below 25 °C = 5 K; the others as above.

ResultSourceThis calc
Battery-terminal daily energy1,779 Wh1,779 Wh
MPPT array requirement before string rounding861 ± 2 W860.4 W
Total PV modules33
Installed array STC power990 W990 W

VeraSol Examples 18–20 · PWM current method

Source: VeraSol pp.53–56, Examples 18–20. The p.56 statement '22.3' conflicts with p.53's 23.3 A and the numerator of p.56's own division. Use the correct 23.3 A. Published Imp=8.73 A is rounded; rated P/Vmp gives 8.73016 A. No separate cable loss is included in that example.

Inputs: Lighting: total running power = 150 W; Lighting: equivalent full-power hours/day = 10 h; Refrigerator: total running power = 0 W; Electronics: total running power = 0 W; Pump / other AC: total running power = 0 W; Direct DC loads: total running power = 28 W; DC loads: equivalent hours/day = 4 h; Additional inverter idle draw = 0 W; Inverter energy efficiency = 0.9; Battery bank nominal voltage = 24 V; Individual battery nominal voltage = 12 V; Minimum operating battery voltage = 21 V; Worst design month's peak sun hours/day = 4.6 h; Array oversizing factor = 1.3; Charge controller type = PWM · size from ampere-hours and current; PV modules in each series string = 1; PV-side wiring efficiency = 1; Cold design temperature below 25 °C = 5 K; the others as above.

ResultSourceThis calc
PWM required array operating current23.3 ± 0.1 A23.272 A
Derated PWM module operating current8.3 ± 0.02 A8.294 A
Selected PV strings in parallel33
Installed array STC power990 W990 W

VeraSol Example 28 · cold string voltage

Source: VeraSol p.64, Example 28: three modules, 46.2 V Voc, −0.29%/°C, 20 °C cells (5 K below STC). Published 140.7 V rounds per-module voltage to 46.9 V first; unrounded physics gives 140.6097 V.

Inputs: PV modules in each series string = 3; Cold design temperature below 25 °C = 5 K; the others as above.

ResultSourceThis calc
Cold open-circuit voltage per module46.9 V46.87 V
Cold string open-circuit voltage140.7 V140.6 V

Victron · 100 W MPPT voltage conversion

Source: Victron, Which solar charge controller: PWM or MPPT? (20 Jan 2020), p.3. Published ideal current is 7.7 A from 100 W at 13 V. This checks ideal power conversion; the selected controller current rating separately uses minimum battery voltage and allowance.

Inputs: Lighting: total running power = 1 W; Lighting: equivalent full-power hours/day = 1 h; Refrigerator: total running power = 0 W; Electronics: total running power = 0 W; Pump / other AC: total running power = 0 W; Direct DC loads: total running power = 0 W; Additional inverter idle draw = 0 W; Additional simultaneous starting demand = 0 VA; Module rated STC power = 100 W; Module STC maximum-power voltage = 18 V; Module STC open-circuit voltage = 21.6 V; Module STC short-circuit current = 6.12 A; PV modules in each series string = 1; Battery bank nominal voltage = 12 V; Individual battery nominal voltage = 12 V; Minimum operating battery voltage = 11 V; Maximum battery charging voltage = 13 V; MPPT voltage headroom above charging voltage = 0 V; Retained Vmp at hottest design cells = 0.9; the others as above.

ResultSourceThis calc
Installed array STC power100 W100 W
Ideal MPPT current at charging voltage7.7 ± 0.01 A7.692 A