Inverter Battery Backup: Will It Recharge Between Power Cuts?
Simulate seven days of power cuts and charging. See whether your inverter or IPS battery still covers day 3, with charger limits, charge taper and lead-acid or LiFePO₄ behaviour.
A battery that survives one power cut can still fail after several days of load shedding. Each outage removes charge, while short grid windows may replace only part of it. This inverter battery backup calculator follows that balance for seven repeating days and answers the practical question: will the battery still cover the cuts on day 3?
It is intended for engineers, students, households and small businesses planning an inverter or IPS supply for essential appliances. Use it to compare a stronger charger, a smaller outage load, a different battery bank or a revised cut schedule. The default is an illustrative 12 V, 220 Ah lead-acid system with three three-hour cuts each day. It covers the first two days and then loses backup late on day 3.
Enter the whole bank voltage and its amp-hour capacity, allowing for measured capacity loss with age. Batteries in series add voltage; parallel strings add amp-hours. Enter the real AC load and the inverter's efficiency and idle draw. Choose lead-acid or LiFePO₄ and set the allowed discharge fraction. All fractions use 0 to 1: an efficiency of 0.9 means 90%.
Set the DC charging current that actually reaches the battery when grid power returns. This is especially important with weak mains or an inverter input limit. The inverter battery charging time result includes a simple adjustable taper near full charge. It assumes the grid is continuously available for that duration; the seven-day simulation interrupts charging whenever another cut begins.
Enter up to four ordered cut windows in hours after midnight. For example, 14.5 means 14:30. Split a cut that crosses midnight into a late-night window and an early-morning window. The schedule repeats unchanged. Press play to move the cursor along the charge strip: amber bands show grid outages, blue shows stored charge, and the schematic shows charging, backup or shutdown. The daily chart and table report the total time the essential load cannot be supplied.
A negative best-case daily charge surplus means the charger cannot replace a full day's demand even before taper losses. More battery capacity can delay the shortfall without fixing that daily deficit. A positive surplus is only a necessary budget check; the timing of the windows and charge acceptance still matter.
This load shedding battery calculator is a planning model using nominal voltage and a simplified charge profile. It does not predict appliance starting surges, voltage sag, BMS trips, battery temperature, long-term damage or irregular outages. Seven successful days do not guarantee indefinite service. Calibrate against measured charge current and backup duration, follow equipment limits, and have installation work carried out by a qualified person.
How it is calculated
The daily schedule repeats for seven days, beginning at midnight. The AC load is bypassed to the grid while it is available. During a cut, the assumed constant battery current is .
Present capacity is . For lead-acid, the rated current is and Peukert's law gives the rate factor . The full-charge discharge allowance is , so its runtime is . No capacity above the nameplate is credited below the rated current. LiFePO₄ uses , treating its discharge capacity as approximately rate independent.
The state variable tracks physical stored Ah, rather than a Peukert-weighted charge counter. The operating cutoff is . Thus high-rate unavailable capacity remains a reserve; it is not charged again as though it had been removed. Partial discharge reduces at per hour. At the cutoff the inverter stops for the rest of that cut; grid return allows charging and later backup. A bank starting below cutoff cannot supply backup until it has recharged above it.
On grid, . Acceptance is 1 below knee , then above it. It reaches the finish-to-bulk ratio at full charge. The model integrates the constant-current and exponential taper portions exactly, caps stored charge at 100%, and discards excess charging opportunity. This adjustable acceptance law is derived here as a planning approximation, not a fitted manufacturer charge curve.
The event loop splits at every cut boundary, midnight, hour mark and discharge cutoff. Hour marks add plotting points; they are not an Euler integration time step. Uncovered time includes fractional hours after cutoff. Charge actually stored and charge actually removed are accumulated separately and checked against . Charts join the exact sampled states with straight segments; the animated state uses the analytic update within each segment.
The best-case daily surplus is before taper or full-charge curtailment. The cutoff-to-full time uses the same acceptance law with uninterrupted grid. Peukert examples and Ah efficiency are checked against the attached Victron manual, PDF pages 48–49 and 34; the ideal one-discharge limit is also checked against Luminous.
Assumptions
- Constant essential AC real power, constant nominal battery voltage and fixed inverter efficiency. The separate idle draw applies only while backup is operating.
- The charger current is net DC current available to the entire bank. Grid power supplies the AC load directly; shared mains limits must already be reflected in this current.
- The initial charge is specified at midnight before day 1. No solar input, generator, self-discharge or extra DC loads are included.
- Lead-acid defaults: C20 rating, Peukert exponent 1.25, 50% allowed discharge and 95% Ah charging efficiency. The exponent and efficiency are illustrative Victron monitor settings, not specifications for every battery.
- LiFePO₄ defaults: 80% allowed discharge, 99% Ah charging efficiency and no rate penalty. A compatible charger and BMS are assumed; BMS current and voltage limits are outside the model.
- Taper knees of 0.85 for lead-acid and 0.95 for LiFePO₄, and finish/bulk current ratio 0.15, are author-selected approximations. Change them to match measured acceptance; they are not manufacturer recommendations.
- Allowed discharge is applied to rate-adjusted available capacity. The displayed operating cutoff therefore includes a Peukert reserve and can exceed the nominal reserve .
- Remaining capacity is a uniform derating. Temperature, resistance growth, recovery after rest and cycle ageing are not modelled.
Where it applies
Use for comparative planning of small inverter/IPS battery banks under a known repeating daily schedule. The seven-day forecast is conditional on the load, current and schedule; a successful day 3 is not a claim of steady operation or battery life.
Peukert is an empirical constant-current approximation. At extreme discharge rates, low temperature or near low-voltage shutdown, measured runtime may be shorter. This tool does not solve a Shepherd terminal-voltage model or select inverter/BMS cutout voltages. Use discharge curves and measured charging records for final design.
The taper model does not reproduce charger absorption timers, equalization, cell balancing, low-temperature charge blocking, charge-voltage compensation or state-of-health changes. Trojan's charging guidance establishes why bulk current cannot be assumed throughout recharge; the adjustable taper here is not a reproduction of that manufacturer's curve. Follow the specific battery's permitted current, voltage and temperature range.
No surge, VA rating, cabling, fuse, earthing, transfer-switch or installation sizing is performed. Installation work belongs to a qualified person.
References
- Victron Energy, BMV-712 Smart manual, sections 7.2.6–7.2.7 and 8; attached PDF pages 34 and 48–49 (printed pages 30 and 44–45). https://www.victronenergy.com/upload/documents/BMV-712_Smart/9172-Manual_BMV_and_SmartShunt-pdf-en.pdf
- Victron Energy, BMV-700H configuration, section 4.5: lithium charge efficiency and discharge floor. https://www.victronenergy.com/media/pg/BMV-700H/en/configuration.html
- Trojan Battery, Battery Maintenance: charger selection and flooded/VRLA charging guidance, accessed 26 October 2026. https://www.trojanbattery.com/resources/battery-maintenance
- Luminous India, How to Choose a Good Inverter for Home, Step 3: ideal 431 W, four-hour, 12 V battery sizing illustration; the reference test explicitly excludes real-world losses and reserve. https://www.luminousindia.com/blogs/how-choose-best-inverter-home-complete-buying-guide
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| Battery chemistry Select the chemistry, then use its manufacturer-approved charge settings. | chemistry | Lead-acid (Peukert) | |
| Nominal bank voltage Use the whole bank voltage: series voltages add. A four-cell LiFePO₄ pack is typically 12.8 V. | V_bank | V | 12 |
| Bank capacity Use Ah at the bank voltage. Series connection does not add Ah; parallel strings do. | C_bank | Ah | 220 |
| Remaining capacity fraction 1 = rated capacity; 0.8 = 80% remaining. Use measured capacity for an aged bank. | f_health | 1 | |
| Starting charge fraction 1 = fully charged at midnight before day 1; 0.6 = 60%. | s_initial | 1 | |
| Allowed discharge fraction Fraction of the rate-adjusted capacity allowed per full discharge. 0.5 is a planning assumption, not a battery warranty. | d_lead | 0.5 | |
| Allowed discharge fraction 0.8 leaves a 20% reserve; follow the battery and BMS limits. | d_lfp | 0.8 | |
| Capacity rating duration For example, use 20 h for a C20 lead-acid capacity. | H_rating | h | 20 |
| Peukert exponent Use the battery discharge data if available. 1 disables the rate penalty. | k_peukert | 1.25 | |
| Essential AC load Continuous real power during cuts, not the inverter VA rating. Average cycling appliances cautiously. | P_load | W | 150 |
| Inverter efficiency fraction 0.9 = 90% conversion efficiency, excluding the separate idle draw. | eta_inverter | 0.9 | |
| Inverter DC idle draw Added while supplying backup; assumed off after low-battery shutdown. | P_idle | W | 8 |
| Available DC charging current Net bulk current reaching the bank while grid is on. Use the weak-grid or mains-limit value, not an optimistic nameplate value. | I_charge | A | 8 |
| Lead-acid charge efficiency Ah efficiency: 0.95 means 10 Ah delivered stores 9.5 Ah. | eta_lead | 0.95 | |
| LiFePO₄ charge efficiency Ah efficiency. Victron recommends 0.99 for lithium battery monitoring. | eta_lfp | 0.99 | |
| Lead-acid taper starts at Charge fraction where acceptance begins falling. This is an adjustable planning approximation; calibrate from observed charging. | b_lead | 0.85 | |
| LiFePO₄ taper starts at Adjust to the charger/BMS behaviour. 0.95 is an assumed planning knee. | b_lfp | 0.95 | |
| Finish current / bulk current Acceptance falls linearly from bulk current at the knee to this fraction at full charge. 1 gives constant-current charging. | r_tail | 0.15 | |
| Daily cut windows Enter ordered, non-overlapping windows in hours after midnight. Split a cut crossing midnight into two windows. | n_cuts | 3 | |
| Cut 1 starts after midnight 6 = 06:00; 6.5 = 06:30. | start_1 | h | 6 |
| Cut 1 duration Use 0 for no cut in this window. | duration_1 | h | 3 |
| Cut 2 starts after midnight Must follow the end of cut 1. | start_2 | h | 14 |
| Cut 2 duration Grid is unavailable for this whole interval. | duration_2 | h | 3 |
| Cut 3 starts after midnight Must follow the end of cut 2. | start_3 | h | 20 |
| Cut 3 duration The same schedule repeats for seven days. | duration_3 | h | 3 |
| Cut 4 starts after midnight Must follow the end of cut 3. | start_4 | h | 23 |
| Cut 4 duration Keep its end at or before midnight. | duration_4 | h | 0.5 |
| ▶ Inspect elapsed time Press play to follow charge and power flow. Simulation results do not change as the cursor moves. | t_view | h | 70.5 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Will it last on day 3? | Day 3: 0.702 h without backup |
| Day 3 without backup | 0.7 h |
| First backup shortfall | Day 3, hour 22.3 |
| Day 7 without backup | 1.17 h |
| Best-case daily charge surplus | -17 Ah |
| Cutoff-to-full charging time | 18.8 h of uninterrupted grid |
| Charge at cursor (%) | 53.4 |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
Victron: 100 Ah supplies 5 A for 20 h
Source: Victron BMV-712 Smart manual, attached PDF p.48 (printed p.44): 100 Ah at 5 A lasts 20 h. Full discharge is used only to reproduce the capacity test; it is not the recommended lead-acid operating depth.
Inputs: Bank capacity = 100 Ah; Essential AC load = 60 W; Inverter DC idle draw = 0 W; Inverter efficiency fraction = 1; Allowed discharge fraction = 1; Available DC charging current = 0 A; Daily cut windows = 1; Cut 1 starts after midnight = 0 h; Cut 1 duration = 24 h; the others as above.
| Result | Source | This calc |
|---|---|---|
| DC current during backup | 5 A | 5 A |
| Single full-charge runtime to operating cutoff | 20 h | 20 h |
| First uncovered backup instant (-1 means none) | 20 h | 20 h |
Victron: C5 = 75 Ah alongside C20 = 100 Ah
Source: Victron BMV-712 Smart manual, attached PDF p.49 (printed p.45): independent ratings 75 Ah at C5 and 100 Ah at C20. I5=15 A; exponent ln(20/5)/ln(15/5)=1.261859507. The rated five-hour discharge checks both the Peukert capacity and simulated cutoff.
Inputs: Bank capacity = 100 Ah; Essential AC load = 180 W; Inverter DC idle draw = 0 W; Inverter efficiency fraction = 1; Allowed discharge fraction = 1; Peukert exponent = 1.262; Available DC charging current = 0 A; Daily cut windows = 1; Cut 1 starts after midnight = 0 h; Cut 1 duration = 24 h; the others as above.
| Result | Source | This calc |
|---|---|---|
| Rate-adjusted capacity (no low-current capacity credit) | 75 Ah | 75 Ah |
| Single full-charge runtime to operating cutoff | 5 h | 5 h |
| First uncovered backup instant (-1 means none) | 5 h | 5 h |
Victron: 10 Ah input stores 9.5 Ah at 95%
Source: Victron BMV-712 Smart manual, attached PDF p.34 (printed p.30), section 7.2.7: 10 Ah delivered at 95% stores 9.5 Ah. With no cut and charge below the taper knee, the first recorded hour independently reproduces that Ah accounting.
Inputs: Bank capacity = 100 Ah; Starting charge fraction = 0.5; Available DC charging current = 10 A; Daily cut windows = 1; Cut 1 starts after midnight = 0 h; Cut 1 duration = 0 h; the others as above.
| Result | Source | This calc |
|---|---|---|
| Charge actually stored during grid hours [2] | 9.5 Ah | 9.5 Ah |
| Stored charge fraction through seven days [2] | 0.595 | 0.595 |
Luminous: 431 W for four hours, ideal 12 V sizing
Source: Luminous, How to Choose a Good Inverter for Home, Step 3: 431 W × 4 h / 12 V is given as 143.6 Ah. The exact quotient is 143.6667 Ah, so that rounded input gives 3.99814 h. This is an ideal one-discharge limit with losses, reserve and Peukert disabled; it does not validate recharging or the suggested practical battery size. https://www.luminousindia.com/blogs/how-choose-best-inverter-home-complete-buying-guide
Inputs: Bank capacity = 143.6 Ah; Essential AC load = 431 W; Inverter DC idle draw = 0 W; Inverter efficiency fraction = 1; Allowed discharge fraction = 1; Peukert exponent = 1; Available DC charging current = 0 A; Daily cut windows = 1; Cut 1 starts after midnight = 0 h; Cut 1 duration = 24 h; the others as above.
| Result | Source | This calc |
|---|---|---|
| Single full-charge runtime to operating cutoff | 4 h | 3.998 h |
| First uncovered backup instant (-1 means none) | 4 h | 3.998 h |
Related Resources
Related articles
Related courses
IEC Electrical Schematics and Industrial Control Panels
5
Original price was: 42 €.21 €Current price is: 21 €.
Basic Electrical Controls & Diagram Reading
7
Original price was: 32 €.18 €Current price is: 18 €.
Modeling Electrical Motor Faults with FEM Simulation using ANSYS MAXWELL
3
Original price was: 50 €.15 €Current price is: 15 €.







Responses