Instant Water Heater and Electric Shower Calculator
Size instant hot-water capacity from flow and winter inlet temperature. Compare electric current, cable voltage drop, breaker inputs, Japanese go ratings and shower cost.
This electric shower calculator connects water demand, heater capacity and the electrical supply. Use it to compare an instant shower, a whole-house tankless unit or a gas water heater before discussing equipment with an installer. Engineers and students can inspect the named calculation steps; household users can see why winter water or a second tap changes the result.
Start with the coldest expected inlet temperature and your desired outlet temperature. Enter the number of showers and other taps operating at once, with each outlet’s actual flow through the heater. Exclude cold water added downstream. All heater-fed streams share one heater outlet target; the result is the heater temperature before mixing, not the final mixed shower temperature. Flow capacity is also shown in US gallons per minute; flow fields accept an explicit unit such as 1 gal/min. Use a bucket and timer to measure flow when practical. A point-of-use electric shower normally serves one outlet; adding taps here does not make that appliance suitable for a multi-outlet installation.
Choose how the available capacity is specified. Electric mode uses the selected nameplate heating power and voltage. Known useful heat mode accepts heat actually transferred to water, rather than gas fuel input. Japanese go mode uses the capacity convention of one litre per minute heated through 25 kelvin per go. The required go result is a thermal equivalent, not a recommendation for a particular product.
The tankless water heater size calculator reports required useful heat and the maximum actual heater flow that can reach your heater outlet target. Electric mode predicts the outlet at a fixed heating setting. The two non-electric modes assume the heater can modulate down to the target; minimum firing rates are not modeled. Compare the flow and winter curves to see the capacity envelope. The flow sweep follows both demand and target-flow capacity so the target crossing stays visible. Press play to animate a changing flow. The animation is a series of steady operating points, not a simulation of warm-up or plumbing pressure.
For an electric unit, enter both its nameplate voltage and the supply voltage at the circuit origin. A 127 V, 220 V or 230 V rating matters: resistance-heater power changes approximately with voltage squared. The cable model includes two copper conductors, voltage drop and feeder loss. Electricity cost includes that feeder loss and assumes the selected power runs for the whole session. Enter your own tariff and currency; the sample price is illustrative as of 27 October 2026.
People searching for chuveiro elétrico fio often encounter conflicting wire and breaker advice. This tool screens a proposed circuit and calculates an area for voltage drop only. Cable area alone cannot establish ampacity. Enter an installer-verified corrected ampacity before interpreting the breaker assessment.
Mains electricity in a wet room requires qualified installation. A qualified electrician must select and test the dedicated circuit, earthing, residual-current protection, isolation and connections against the exact appliance instructions and the standard in force. Brazil's NBR 5410 and the UK's BS 7671 are installation references, not tables reproduced here. A passing ratings inequality does not certify safety. Actual flow limits, thermostat behavior, scald protection, gas supply, flues, pipe losses and activation thresholds remain product-specific.
How it is calculated
The thermal equations are derived here from steady-flow conservation of energy:
Use explicit conversions from L/min to m³/s and W to kW. Water is approximated by 1000 kg/m³ and 4180 J/(kg·K). The heat capacity is consistent with NIST-JANAF liquid-water data near room temperature; density is a nominal engineering approximation.
Maximum thermal flow at the target is . Simultaneous actual heater-fed outlet flows are added; downstream cold bypass flow is excluded. Rinnai defines one Japanese go as 1 L/min heated by 25 K; the corresponding useful heat is about 1.742 kW. Required capacity is when Q is in L/min.
For the full selected electric setting, derive and . Then , , and . Useful heat is . Copper resistivity 0.0225 Ω·mm²/m is the normal-service approximation in Prysmian's 2024 guidance, printed page 34. Both loaded conductors have equal area and length.
Screen with , deliberately giving no credit for cable voltage drop reducing current. Compare , using the installer's corrected cable ampacity. The continuous drop-only area is . It does not size a protective conductor or establish ampacity. Energy at circuit origin is and cost is energy times the entered tariff.
Electric outlet temperature is unregulated at the selected power. Useful-heat and go modes assume modulation to . The animation changes flow through steady operating points and never changes the sizing cards. Flow curves stay below 90°C and span the target-flow crossing. Their lower bound exceeds the full-power flow at 90°C by 1%; their upper bound is 1.5–3 times the target capacity, adjusted for entered demand. This keeps the target crossing readable even when entered demand is far from capacity. A demand outside that plot span remains included in the sizing results and winter curve. Above, near and below target are distinguished with a 1 K comparison band, not a safety threshold. Stiebel Eltron's attached page 1 supplies independent thermal and current reference values; Triton's attached page 9 supplies a separate voltage/power comparison.
Assumptions
- Clean liquid water, constant properties, negligible pipe heat loss, storage, kinetic energy and elevation effects. The 1000 kg/m³ density approximation introduces a few percent error toward the hot end of the range.
- Every flow input is actual water passing through the heater, before downstream cold mixing. All heater-fed streams share one heater outlet target. Final mixed flow must not be entered here. A mixed-delivery energy balance may be used separately for demand sizing, but it cannot predict the heater outlet temperature or validate the 90°C model limit. This calculator does not model mixing streams.
- Electric mode is one two-wire, single-phase resistance load on a full selected heating setting: no pump, phase-angle control, electronic constant-power regulation or thermostat cycling. Multi-feed heaters require a separate electrical design for each feed.
- Non-electric inputs are useful heat at the water, or Japanese go capacity. Ideal target modulation is assumed; minimum modulation, activation flow, pressure, temperature limits and appliance controls are omitted. No gas consumption or gas installation sizing is calculated.
- Cable resistance is a bulk normal-service approximation. Contacts, source impedance, upstream drop, reactance and unequal conductors are excluded. Use manufacturer cable resistance when a detailed design is required.
- The 3% branch-drop allowance and 0.25 currency/kWh tariff are editable illustrations, reviewed 27 October 2026. No regional electricity price is implied. The monthly estimate uses 30 days.
- The electrical screen is incomplete until corrected ampacity is supplied. Standards ampacity tables are not reproduced. No wire or breaker is automatically approved.
- The viewer converts temperature readings with their offset when switching units. Flow capacity is shown in both L/min and US gal/min because the viewer does not automatically switch L/min; type an explicit gal/min value in a flow field. Diagram and electrical summary labels retain the SI units written beside their numbers.
Where it applies
Electric shower installation belongs to a qualified electrician. Mains electricity and water can cause fatal shock. Use a dedicated circuit, protective earthing, appropriate RCD/DR protection, safe isolation, suitable terminals and all required bathroom-zone protections. The cited Triton manual requires 30 mA RCD protection for its UK installation. RCD/DR protection does not replace earthing. Do not bypass a safety cut-out or restrict a vented shower outlet.
Regulatory context reviewed 27 October 2026: Brazil, ABNT NBR 5410:2004 (corrected 2008); UK, BS 7671:2018+A4:2026 as identified by the IET. These are installation references, not a compliance calculation. Check against the standard in force, current local rules, supply conditions and the exact appliance manual. Have the installer verify cable installation method, grouping, ambient temperature, insulation, protective-device characteristic and breaking capacity, fault/disconnection protection, service capacity and manufacturer minimum conductor requirements.
A generic breaker guide can disagree with a model-specific manual: Lorenzetti's general FAQ and Acqua Century manual illustrate this. The exact model manual and qualified local circuit design govern; a numerical result is only one necessary screen.
Thermal sizing is intended for inlet water 1–40°C and target water 5–65°C with positive total flow and positive rise. An electric heater-outlet result above 90°C is held back because boiling and cut-out behavior are outside the model. Use actual heater flow for this check: downstream cold mixing does not reduce the temperature inside the heater and cannot validate an out-of-range heater state. Non-electric output assumes ideal modulation; a large full-power envelope is not an operating recommendation. Hot water can scald: a target value or a “near target” status within 1 K is not a safe-temperature certification. Verify delivered temperature and product-specific minimum flow, pressure and controls. Gas installation and flue work also require appropriately qualified professionals.
This tool does not authorize appliance voltage mismatch, circuit modifications, adding outlets to a single-outlet shower, or selecting a breaker merely by rounding current up.
References
- Stiebel Eltron, Tempra tankless electric water heater submittal, rev. 6.2018, attached source s1, page 1 (published thermal rises and current): https://stiebel-eltron-usa.com/sites/default/files/pdf/submittal-sheet-tempra.pdf
- Rinnai, Hot water capacity: Japanese go definition and simultaneous demand: https://www.rinnai.jp/products/waterheater/gas/about/power/
- Rinnai FAQ 1140, 24-go winter flow example at 7°C inlet / 42°C outlet: https://faq.rinnai.co.jp/faq/show/1140?site_domain=default
- Lorenzetti, Acqua Century Digital and Electronic installation manual, sections 2–3 and troubleshooting: https://www.lorenzetti.com.br/manuais/centuryeletronico/index.html
- Lorenzetti, Electric showerheads FAQ (generic guide; exact model instructions take precedence): https://www.lorenzetti.com.br/en/tips/faq/electric-showerheads
- Triton, Safeguard Pumped Care instructions, January 2018, attached source s4, page 9 (printed page 7), paired voltage/power ratings; page 4, electrical safety. Pump power is excluded from the element-only reference: https://www.tritonshowers.ie/pub/media/custom/upload/p/d/File-1516805712.pdf
- Prysmian, Electrical Information for Low Voltage Cables, 2024, printed page 34, voltage-drop method and normal-service copper resistivity: https://asean.prysmian.com/sites/asean.prysmian.com/files/media/documents/241218%20-%20Prysmian%20Electrical%20Information%20for%20Low%20Voltage%20Cables.pdf
- NIST-JANAF, liquid water thermochemical data near 298 K: https://janaf.nist.gov/tables/H-063.html
- IET, current BS 7671 edition and amendments, checked 27 October 2026: https://electrical.theiet.org/bs-7671-18th-edition-wiring-regulations/ensure-you-are-up-to-date-with-bs-7671/
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| Available heater capacity Use useful heat or go mode for a gas water heater. Electrical and electricity-cost results apply only to electric mode. | heater_type | Electric resistance heater | |
| Nameplate electric power Power of the selected heating setting at its nameplate voltage. Full-power, fixed-resistance model; no pump or thermostat control. | P_nom | kW | 7.5 |
| Useful heat output Heat transferred to water, not gas input power. Use the manufacturer's rated useful output. | P_use | kW | 24 |
| Japanese capacity rating (go) One go heats 1 L/min through 25 K. This compares thermal capacity only. | go_nom | 24 | |
| Electric power reaching water (fraction) 1 means all element power heats the water; 0.98 means 98%. Pipe losses are excluded. | eta | 1 | |
| Cold water inlet temperature Use the coldest measured or design inlet temperature for winter sizing. | T_in | °C | 15 |
| Desired heater outlet temperature Target at the heater outlet, before downstream cold mixing. All heater-fed streams use this target. This is a sizing target, not a safe temperature recommendation. | T_set | °C | 40 |
| Simultaneous showers Count simultaneous shower streams supplied by this heater. Their flow entries must exclude downstream cold mixing. A point-of-use shower unit normally serves one outlet. | n_shower | 1 | |
| Actual heater flow per shower Enter only water passing through this heater, before downstream cold mixing. Do not enter final mixed shower flow. You may type an explicit unit such as "1 gal/min" (US gallons). | q_shower | L/min | 4 |
| Other simultaneous taps Add only taps this heater is designed to serve; enter the heater-fed flow of each, not its final mixed flow. | n_tap | 0 | |
| Actual heater flow per other tap Enter only each tap’s flow through this heater, excluding added cold water after the heater. All heater-fed streams use the same heater outlet target. An explicit unit such as "1 gal/min" is accepted. | q_tap | L/min | 3 |
| Heater nameplate voltage Match the actual appliance rating: examples include 127, 220, 230 and 240 V. | V_nom | V | 220 |
| Supply voltage at circuit origin Examples: 127 V Brazil, 220 V Brazil/Argentina, 230 V UK. Changing this does not make a mismatched appliance safe. | V_supply | V | 220 |
| One-way copper cable route length From circuit origin to heater; the calculation includes both loaded conductors. Zero omits cable loss for comparisons. | L_cable | m | 20 |
| Proposed copper conductor area Area of each loaded conductor. This does not determine ampacity without the cable type and installation conditions. | A_cable | mm^2 | 6 |
| Proposed breaker rating An input to screen, not an automatic breaker recommendation. Follow the exact appliance manual and local design. | I_n | A | 40 |
| Installer-verified cable ampacity (0 = unknown) Enter corrected current-carrying capacity after installation method, insulation, grouping and ambient derating. Zero leaves the protection assessment incomplete. | I_z | A | 0 |
| Allowed branch-circuit voltage drop (%) User-selected allowance for this cable only. The default 3% is illustrative, not a limit taken from a wiring standard; reserve allowance for upstream wiring. | drop_allow | 3 | |
| Shower or simultaneous-use session duration Full selected power for the entire session; all active outlets run together. | t_session | min | 8 |
| Electricity price (your currency per kWh) Illustrative tariff, reviewed 27 October 2026. Replace with your current marginal price. Keep one currency; taxes and standing charges are excluded. | tariff | 1/kWh | 0.25 |
| Sessions per day Used for a 30-day estimate. A simultaneous session is one run of the heater. | sessions_day | 2 | |
| Flow animation time Press ▶ for a quasi-steady flow sweep. It changes the drawing only; this is not a warm-up simulation. | t_anim | s | 6 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Useful heat required at target | 6.97 kW |
| Available useful heat | 7.16 kW |
| Heater outlet before mixing | 40.7 °C |
| Heater outlet relative to target | Near target (within 1 K) |
| Maximum heater flow at target | 4.11 L/min |
| Maximum heater flow at target (US) | 1.09 gal/min |
| Required Japanese capacity (go) | 4 |
| Full-power current (electric only) | 33.3 A |
| Cable voltage drop (electric only) | 2.27% / 5 V |
| Drop-only minimum area: ampacity still required | 4.65 mm² |
| Proposed cable and breaker screen | Incomplete: enter verified cable ampacity |
| Electricity per shower/session | 0.977 kWh |
| Cost per shower/session (your currency) | 0.244 |
| 30-day cost (your currency) | 14.7 |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
Tempra 12: 240 V, 1.5 US gpm
Source: Stiebel Eltron Tempra submittal, rev 6.2018, attached page 1: 12 kW, 240 V, 50 A and 54°F rise at 1.5 US gpm. 54°F difference = 30 K. Published whole-degree thermal values are rounded; allow 2%. One feed only, no cable drop.
Inputs: Nameplate electric power = 12 kW; Heater nameplate voltage = 240 V; Supply voltage at circuit origin = 240 V; One-way copper cable route length = 0 m; Actual heater flow per shower = 5.678 L/min; Cold water inlet temperature = 10 °C; the others as above.
| Result | Source | This calc |
|---|---|---|
| Full-power rise at the entered total flow | 30 ± 0.6 K | 30.336 K |
| Actual full-power current including feeder resistance | 50 A | 50 A |
Tempra 12: reduced voltage and power at 208 V
Source: Stiebel Eltron Tempra submittal, rev 6.2018, attached page 1: at 208 V the 12 model is 9 kW, 44 A, 41°F rise at 1.5 US gpm. 41°F difference = 22.7778 K. Same 240 V element resistance predicts 9.0133 kW; the published ratings and rises are rounded.
Inputs: Nameplate electric power = 12 kW; Heater nameplate voltage = 240 V; Supply voltage at circuit origin = 208 V; One-way copper cable route length = 0 m; Actual heater flow per shower = 5.678 L/min; Cold water inlet temperature = 10 °C; the others as above.
| Result | Source | This calc |
|---|---|---|
| Electric power dissipated in element | 9 ± 0.03 kW | 9.013 kW |
| Actual full-power current including feeder resistance | 44 ± 0.8 A | 43.333 A |
| Full-power rise at the entered total flow | 22.778 ± 0.46 K | 22.785 K |
Triton: 8.5 kW at 240 V becomes about 7.8 kW at 230 V
Source: Triton Safeguard Pumped Care manual, January 2018, attached page 9 (printed 7): paired element ratings 8.5 kW/240 V and 7.8 kW/230 V. Test the element only: the separately listed 120 W pump is excluded. It does not verify total appliance current or a breaker selection.
Inputs: Nameplate electric power = 8.5 kW; Heater nameplate voltage = 240 V; Supply voltage at circuit origin = 230 V; One-way copper cable route length = 0 m; the others as above.
| Result | Source | This calc |
|---|---|---|
| Electric power dissipated in element | 7.8 ± 0.05 kW | 7.806 kW |
Rinnai 24-go winter delivery
Source: Rinnai FAQ 1140, https://faq.rinnai.co.jp/faq/show/1140?site_domain=default : a 24-go heater delivers about 17 L/min for inlet 7°C and outlet 42°C. The definition predicts 17.14 L/min; published flow is rounded. No gas input or electric current is inferred.
Inputs: Available heater capacity = Japanese go rating; Cold water inlet temperature = 7 °C; Desired heater outlet temperature = 42 °C; Actual heater flow per shower = 17 L/min; the others as above.
| Result | Source | This calc |
|---|---|---|
| Maximum heater flow at target | 17 ± 0.2 L/min | 17.143 L/min |
Rinnai 28-go winter delivery
Source: Rinnai FAQ 1140, https://faq.rinnai.co.jp/faq/show/1140?site_domain=default : for inlet 7°C and outlet 42°C, a 28-go unit delivers 20 L/min. This is the published useful thermal capacity; gas input, hydraulics and electrical design are not checked.
Inputs: Available heater capacity = Japanese go rating; Japanese capacity rating (go) = 28; Cold water inlet temperature = 7 °C; Desired heater outlet temperature = 42 °C; Actual heater flow per shower = 20 L/min; the others as above.
| Result | Source | This calc |
|---|---|---|
| Maximum heater flow at target | 20 ± 0.1 L/min | 20 L/min |