Grid-Forming Inverter: Fault Current, Synthetic Inertia & SCR

Calculate external-grid SCR, inverter fault-current limits and synthetic-inertia power and energy demand. Compare dispatch headroom and usable energy during a prescribed frequency ramp.

#energy storage #fault current #grid-forming inverter #RoCoF #short-circuit ratio #synthetic inertia

A grid-forming inverter can establish an AC voltage reference, but its fault-current capability, synthetic inertia setting and connection-point grid strength describe different things. This calculator puts those quantities on explicit bases so engineers and students can compare them without treating a semiconductor converter like a synchronous generator.

Start with the aggregate inverter MVA rating, plant rated MW, PCC line-to-line voltage and the external-grid three-phase fault level. The short-circuit ratio is external fault MVA divided by plant rated MW. Enter a utility study value that excludes this inverter plant. The tool also reports the ratio on the inverter MVA base and the external-grid Thevenin impedance. SCR is a screening index; there is no universal SCR threshold that proves a grid-forming installation stable.

For the fault-current calculation, enter the initial dispatch, reactive-power ratio, effective coupling reactance and residual PCC voltage. The internal voltage phasor is derived from the initial operating point at nominal PCC voltage. It is held fixed while the PCC voltage falls without a phase jump. The tool calculates the unlimited current demand and clips its magnitude at the selected RMS current ceiling. The voltage-sag chart makes the transition into current limitation visible. Use the manufacturer's supported current limit for the actual fault duration. This simplified magnitude screen does not reproduce a particular current-priority controller, sub-cycle overshoot or fault recovery.

For synthetic inertia, choose H, nominal frequency, signed RoCoF and ramp duration. Falling frequency requests extra export; rising frequency requests reduced export or extra import. H uses the inverter MVA base, while SCR uses plant rated MW. The calculation compares the requested power change with both directional dispatch headroom and usable energy reserve. Rated apparent power and the fixed reactive-power requirement constrain headroom; the short-duration fault-current ceiling is not credited as inertia overload capacity.

Charging capability may differ from generating capability. Set its negative limit independently; changing this limit does not change the generating MW rating used for SCR. The common inverter MVA bound still applies in both directions.

Enter energy available for the selected direction at the AC terminals, beyond the baseline operating schedule. A battery near full charge may have substantial discharge energy but little absorption reserve. The feasible response is spread uniformly over the complete ramp. Press play to follow the prescribed frequency and remaining directional energy; the animation illustrates this energy budget, not a solved grid transient.

The default example uses a 100 MVA inverter, 100 MW plant rating and 500 MVA external fault level at 33 kV. Change the dispatch, H or energy reserve to see which limit controls the response.

This tool does not cover unbalanced faults, grounding, protection coordination, breaker duty, controller tuning, frequency nadir, multi-infeed grid strength, DC-link dynamics or simultaneous sag and frequency support. Connection studies require suitable network and manufacturer models. Installation work belongs to a qualified person; check any applicable requirements against the standard in force.

How it is calculated

Three-phase bases are Ib=Sn/(3Un)I_b=S_n/(\sqrt{3}U_n) and Zb=Un2/SnZ_b=U_n^2/S_n, with explicit unit conversions. External-grid quantities are ∣Zg∣=Un2/Ssc|Z_g|=U_n^2/S_{sc}, Ig=Ssc/(3Un)I_g=S_{sc}/(\sqrt{3}U_n) and SCR=Ssc/PrSCR=S_{sc}/P_r. The MW-denominator definition and independent 717 MVA / 300 MW = 2.39 example are from NYISO's 2021–2030 Comprehensive Reliability Plan, appendices, printed p. 111. A separate Ssc/SnS_{sc}/S_n value prevents confusion when the ratings differ.

The balanced-sag model is derived here from Kirchhoff's voltage law. At the pre-sag PCC voltage 1∠01\angle0 pu, take exported current p0−jq0p_0-jq_0 and lossless reactance jxeffjx_{eff}. The held internal source is E‾=1+xeffq0+jxeffp0\underline E=1+x_{eff}q_0+jx_{eff}p_0. At imposed residual voltage uf∠0u_f\angle0, the demand is idem=p02+[q0+(1−uf)/xeff]2i_{dem}=\sqrt{p_0^2+[q_0+(1-u_f)/x_{eff}]^2}. The magnitude screen is if=min⁡(idem,kI)i_f=\min(i_{dem},k_I) and If=ifIbI_f=i_fI_b. It supplies no prediction of current angle after limiting. ENTSO-E (3 October 2025), pp. 60–66, discusses effective-reactance and magnitude-limit behaviour; Masenge et al. (2025), pp. 3–4, supplies an independent simulated 1.2 pu limited-current plateau, not a validation of this entire reduced model.

For the prescribed ramp, ΔPreq=−2HSnf˙/fn\Delta P_{req}=-2HS_n\dot f/f_n and Ereq=∣ΔPreq∣TE_{req}=|\Delta P_{req}|T. This uses the nominal-frequency linear inertia relation. ENTSO-E (2025), p. 26, equations (6)–(8), and Appendix F pp. 71–72 provide power/energy relations and worked inertia examples. On the plant MW base, TM=2HSn/PrT_M=2HS_n/P_r; only for equal numerical MW/MVA bases is TM=2HT_M=2H.

At nominal voltage with fixed q0q_0, the rated-current active-power bound is Pc=Sn1−q02P_c=S_n\sqrt{1-q_0^2}. Intersect [−Pc,Pc][-P_c,P_c] with the entered source limits. Select upward or downward headroom according to RoCoF, then limit the magnitude of support to the least of requested power, directional headroom and Ebuf/TE_{buf}/T. Effective H is reduced in the same proportion as the power response. The power reduction is uniform over the full ramp, rather than full response followed by energy exhaustion.

The entered charging limit is independent of the generating rating P_r. P_r limits the upper generating bound and remains the SCR denominator. Charging is bounded by the entered P_min and the inverter apparent-power capability. EPRI's OpenDSS parameter-mapping documentation states that charging ratings may differ from generating ratings.

Assumptions

  • All ratings are aggregate three-phase quantities referred to the stated PCC voltage. Inverter per-unit values and H use S_n; SCR uses rated plant MW, not dispatch.
  • The fault screen assumes balanced positive-sequence fundamental RMS quantities, initially nominal PCC voltage, a lossless fixed coupling reactance and an internal source held at its initial phasor. The sag is imposed independently of the network fault level.
  • The fault and inertia calculations are separate scenarios. Inertia headroom assumes nominal PCC voltage, fixed reactive power and rated apparent power, with no temporary overload credit.
  • The same S_n apparent-power bound is used in both directions. The entered charging limit may exceed the generating MW rating, or impose a tighter charging bound. P_r is the generating rating only.
  • Power-source bounds are available for the entire ramp. The energy reserve is incremental, directional and already adjusted for losses, baseline energy use and state of charge.
  • The ramp is prescribed, not calculated from a disturbance. Response is immediate and constant during it. There is no damping, droop, delay, recovery or energy replenishment model. A zero RoCoF gives zero response; effective H then retains the setting by convention.

Where it applies

Use for preliminary comparisons and teaching. A clipped fault-current magnitude is a screening estimate, not a guaranteed waveform or minimum protection current. Obtain vendor data for current priority, RMS time window, overshoot, sustained duration and recovery; use sequence or EMT models for unbalanced faults and detailed studies. Deep-sag results are particularly sensitive to controller behaviour and neglected resistance.

External-grid bolted-fault current is a separate reference result and is not the grid current at the selected residual voltage. Do not add current magnitudes to infer total fault duty. This plant's current contribution is excluded from the input fault level used for SCR. Closely coupled multiple inverter plants need a suitable multi-infeed assessment; SCR alone cannot establish stability.

Frequency excursion is restricted to ±10% of nominal as a modelling guard, not a grid-code limit. The feasible H result describes only the entered ramp and energy budget, not an independently verified controller inertia or predicted frequency nadir. This calculator applies no national grid-code compliance test. The cited ENTSO-E report is dated 3 October 2025; check any applicable requirements against the standard in force.

References

  • ENTSO-E, Grid forming capability of power park modules — Report on technical requirements, final 3 October 2025, pp. 26, 60–72. https://eepublicdownloads.blob.core.windows.net/public-cdn-container/clean-documents/Reports/2025/TG_GFC_Version_2.pdf
  • NYISO, 2021–2030 Comprehensive Reliability Plan, appendices, printed p. 111: SCR worked example and grid-strength limitations. https://www.nyiso.com/documents/20142/26735166/2021-2030-Comprehensive-Reliability-Plan-Appendices.pdf
  • Masenge, Xu, Chen and Egea-Àlvarez, Modified droop-based fault current control for grid forming converter during network faults, 2024 IEEE PES Innovative Smart Grid Technologies Europe (ISGT EUROPE), published 2025, author manuscript, pp. 3–4. DOI: https://doi.org/10.1109/ISGTEUROPE62998.2024.10863333. Repository: https://strathprints.strath.ac.uk/92188/
  • EPRI, OpenDSS Documentation, Mapping of parameters to IEEE1547-2018: charging and discharging/generation ratings may differ. https://opendss.epri.com/MappingofparameterstoIEEE1547-20.html

Inputs

InputSymbolUnitDefault
Inverter apparent-power rating
Three-phase aggregate rating. All inverter per-unit quantities and H use this base.
S_nMVA100
Plant rated active power for SCR
Maximum generating nameplate MW, not current dispatch. SCR = external-grid fault MVA / these rated MW.
P_rMW100
PCC line-to-line RMS voltage
All currents and impedances are referred to this voltage level.
U_nkV33
External-grid three-phase fault level
Utility/Thevenin fault level at the PCC, excluding this plant's inverter contribution.
S_scMVA500
Initial active power exported
Positive = export; negative = charging/import. Frequency support starts from this dispatch.
P_0MW60
Initial reactive power / inverter rating (pu)
Positive = reactive injection. Held fixed for the nominal-voltage inertia headroom calculation.
q_00
Available active-power lower limit
Use a negative value for available charging throughout the ramp. Charging capability may differ from generating MW rating; the inverter MVA bound still applies.
P_minMW0
Available active-power upper limit
Available generation/discharge before the inverter apparent-power limit is applied.
P_maxMW100
Inverter-to-PCC effective reactance (pu)
On S_n and U_n bases. Include coupling filter, transformer and selected virtual reactance. Excludes the external grid impedance.
x_eff0.2
Residual PCC voltage / nominal (pu)
Imposed balanced voltage sag, with no phase jump. This is an input, not a solved network voltage.
u_f0.5
Controlled fault RMS current limit (pu)
Manufacturer-supported RMS limit at the actual fault duration. Does not specify sub-cycle peak current or inertia overload capability.
k_I1.2
Requested synthetic inertia H
Inertia constant on the inverter MVA base. On equal MW/MVA bases, mechanical starting time T_M = 2H.
H_sets5
Nominal system frequencyf_nHz50
Applied rate of change of frequency
Negative = falling frequency and requested extra export. Zero gives no inertia power or energy demand.
r_fHz/s-1
Frequency-ramp duration
Prescribed constant-RoCoF test. The tool checks the final frequency stays within 10% of nominal.
T_ramps3
Usable directional energy reserve
Extra AC-side energy available beyond baseline dispatch: deliverable for falling frequency, absorbable for rising frequency. Account for state of charge and losses before entry.
E_bufMW*h0.05
Ramp time ▶
Moves the ramp marker and remaining-energy bar. The balanced-sag calculation is a separate scenario.
t_plays1.5

Results

With the default inputs above, the calc gives:

ResultValue
Short-circuit ratio (external MVA / rated MW)5
Inverter controlled RMS current ceiling2.099 kA
Clipped inverter fault-current screen, RMS2.099 kA
External-grid bolted-fault RMS current8.748 kA
Requested inertia power change20 MW
Feasible inertia power change20 MW
Directional power headroom40 MW
Requested extra ramp energy0.01667 MW·h
Feasible extra ramp energy0.01667 MW·h
Effective H supported for this ramp5 s

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

ENTSO-E grid-simulator inertia example, 10 s starting time

Source: ENTSO-E (3 October 2025), Appendix F, Fig. 47, p. 71: 0.2 pu power variation at 1 Hz/s and 50 Hz gives T_M=10 s. Equal MW/MVA bases are used here, so H=5 s; falling frequency sets export-positive sign.

Inputs: the default inputs above.

ResultSourceThis calc
Requested inertia power change20 MW20 MW
Equivalent mechanical starting time on plant MW base10 s10 s

ENTSO-E islanding inertia example, 20 s starting time

Source: ENTSO-E (3 October 2025), Appendix F, Fig. 48, p. 72: published 0.2 pu power variation, 0.5 Hz/s RoCoF, 50 Hz and T_M=20 s. Compare the steady linear inertia relation, not the transient trace.

Inputs: Requested synthetic inertia H = 10 s; Applied rate of change of frequency = -0.5 Hz/s; the others as above.

ResultSourceThis calc
Requested inertia power change20 MW20 MW
Equivalent mechanical starting time on plant MW base20 s20 s

NYISO published 300 MW, 717 MVA SCR example

Source: NYISO 2021–2030 Comprehensive Reliability Plan, appendices, printed p. 111: a 300 MW inverter-based resource at a 717 MVA fault level has SCR 2.39. The publisher's indexed passage supplies the independent value; the PDF download is access-protected and is attached as a link.

Inputs: Inverter apparent-power rating = 300 MVA; Plant rated active power for SCR = 300 MW; External-grid three-phase fault level = 717 MVA; Available active-power upper limit = 300 MW; Initial active power exported = 180 MW; the others as above.

ResultSourceThis calc
Short-circuit ratio (external MVA / rated MW)2.392.39

Masenge et al. published 1.2 pu limited-current plateau

Source: Masenge et al. (2025), pp. 3–4, Fig. 5 and Table I: 400 MVA, 6.6 kV, linking inductance 0.15 pu, approximately 50% residual voltage and controlled fault current 1.2 pu. Checks the published magnitude plateau only. The paper uses reactive-current priority; its detailed controller and recovery are not implemented here.

Inputs: Inverter apparent-power rating = 400 MVA; Plant rated active power for SCR = 400 MW; PCC line-to-line RMS voltage = 6.6 kV; Initial active power exported = 240 MW; Available active-power upper limit = 400 MW; Inverter-to-PCC effective reactance (pu) = 0.15; Usable directional energy reserve = 1 MW·h; the others as above.

ResultSourceThis calc
Magnitude-clipped fault-current screen (pu)1.21.2