Towel Warmer Moved Away from the Riser: Will It Heat?
Will a towel warmer moved to another wall still heat by gravity from the hot-water riser? Flow, temperatures and heat output for your pipes, bends and heights, with the stall and backward-flow cases.
What it answers
In many apartment buildings a water towel warmer hangs on two valved outlets of the hot-water riser. When it is moved to another wall, it is fed through new pipes and no pump: water flows only because the warmer cools it (a thermosiphon) and because the riser flow pushes a little between the two outlets. Whether that is enough depends on heights, pipe bores, bends, insulation and on which way the riser flows. Installers quote rules of thumb (up to 4–5 m, a slope of a few millimetres per metre, pipes of DN 20 or more); this calculator works out your actual layout instead.
How to use it
- Riser: the water temperature at the outlets (measure it), which way the water flows, the flow, the pipe and the outlet spacing.
- Lines: the pipe, the developed length of each line with all its bends, how deep the in-wall run lies below the lower outlet, and the insulation.
- Warmer: bottom or top-and-bottom connection, its heated height, its rated output at ΔT = 50 K from the data sheet, and the height of its lower connection.
The results give the flow through the warmer, its inlet and outlet temperatures, the heat output, and how much of the output is kept compared with the same warmer hung at the riser. The drawing shows the water temperature along the loop; press ▶ at Time to watch the water move. The charts show how far the warmer can go with PP-R 20, 25 and 32 pipes, and what the riser flow does: a downward flow helps, an upward one fights the gravity flow and can stop it or reverse it.
Good to know
Run the lines below the outlets or vent every hump: trapped air stops a gravity loop. Hang the warmer at or above the lower outlet. Insulate the lines in the wall. If the tool reports a second steady state, the loop can also stand still; it usually restarts once the riser is hot again.
How it is calculated
The loop
The warmer and its two lines form a loop in parallel with the riser between its two outlets. The calculation walks around the loop in the flow direction and balances pressures at a loop flow :
Gravity head. around the loop, element by element (each piece of line, the warmer, the riser between the outlets) with the density of the water in it. Equivalently, water cooled at a height drives the loop by , where is the outlet where the cooled water rejoins the riser: cooling above it drives the flow, cooling below it (in a dip that is not insulated) holds it back. The warmer cools its water at the middle of its heated height.
Push of the riser. The riser flow between the outlets loses pressure to friction and the run of the two tees (). A downward riser flow raises the pressure at the upper outlet and helps the loop; an upward flow pushes the other way.
Losses. Each line piece: (laminar) or Blasius; fittings: with of PP-R fittings (90° bend 1.2, 45° 0.5, dividing tee 1.2, combining tee 0.8, adapter 0.25), ball valves 0.3, warmer entry and exit 1.5, and the low-flow term of the two-K method (bend 800, 45° 500, valve 300, tee branch 500).
Temperatures. A line cools as . The warmer follows the EN 442 law on the log-mean difference, . Where the riser carries the returned water back to the inlet (an upward riser), the inlet water is the mix, solved together with the loop.
Every steady state. is scanned over both directions; each place where it falls through zero is a stable state. The hottest is shown; a second one (usually a standstill) is reported.
Reference. The same warmer hung at the riser: 0.3 m stubs plus the vertical runs, two bends per line, no dip.
Assumptions
- One-dimensional, steady flow; the equations are derived here from the energy and momentum balance, not taken from one source.
- The warmer cools its water at the middle of its heated height; its internal resistance is its entry and exit (ζ 1.5 in all).
- Fitting coefficients: PP-R values of a manufacturer's design guide (FD-Plast); low-flow terms from the two-K method (Hooper, 1981), meant for threaded fittings; ball valve ζ 0.3 from typical Kv of DN15 valves. At Re of a few hundred they are the least certain part.
- Heat loss of the lines per metre and kelvin is estimated here for each insulation choice (0.2, 0.3, 0.5, 0.8 W/(m·K)), not measured.
- Water density from Kell (1975); viscosity from a Vogel-type fit (within 1 % of IAPWS values at 20–80 °C).
- The riser water between the outlets keeps the riser temperature unless the riser carries returned water back to the inlet.
Where it applies
- No published measurement of a towel warmer on a riser was found to compare with; the result is an engineering estimate. Measure the riser and the warmer's inlet and outlet to calibrate it.
- Below about 2 kg/h the water in long horizontal lines may layer (hot on top, cold below) and creep both ways in one pipe, which a one-dimensional model cannot show.
- Air in the lines, sludge, half-closed valves and a riser that stops circulating at night are not modelled; any of them can leave the warmer cold.
- Which steady state the loop takes when there are two depends on its history (for example a start after the hot water was off).
- Installer rules of thumb (natural circulation up to 4–5 m from the riser, slope 3–30 mm/m, pipes DN 20 or more) are not norms; this tool calculates the actual layout instead.
- Moving a towel warmer fed from a shared riser may need approval (in Russia it is a re-arrangement of the flat under the Housing Code, art. 25–26).
References
- Mileikovsky V. O. Natural circulation pressure for devices on single-pipe risers. Данфосс INFO 1-2/2012. https://repositary.knuba.edu.ua/bitstreams/7cfa8fb9-575d-4e78-8410-c3dd827c31a8/download
- Khromov E. V. Hot water temperature in apartment buildings (measured riser temperatures, cooling in bathroom risers with towel warmers). Сантехника 3/2017. https://www.abok.ru/for_spec/articles.php?nid=6688
- FD-Plast. Design of polypropylene pipelines (local loss coefficients of PP-R fittings, roughness).
- Hooper W. B. The two-K method predicts head losses in pipe fittings. Chemical Engineering, 24 Aug 1981, 96–99.
- Stelrad. Classic Towel Rail data sheet: EN 442 outputs at 75/65/20 °C and exponents n. https://www.stelrad.com/wp-content/uploads/2025/05/Classic-Towel-Rail_Web-FF.pdf
- Kell G. S. Density, thermal expansivity and compressibility of liquid water from 0 to 150 °C. J. Chem. Eng. Data 20 (1975) 97–105.
- ISO 13732-1:2006 (ГОСТ Р ИСО 13732-1-2015). Burn thresholds of hot surfaces.
- SP 30.13330.2020, clause 9.8: towel warmers on hot-water supply or circulation pipes with constant flow.
- Sunerzha. How to connect a water towel warmer (riser flow direction, bypass types). https://sunerzha.com/blog/articles/kak-pravilno-podklyuchit-vodyanoy-polotentsesushitel/
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| Hot water temperature at the riser outlets Measure it on the riser pipe beside the outlets (a contact or IR thermometer on a matt spot). Bathroom risers of Russian apartment blocks measured 45–51 °C (Khromov, 2017), although 60–75 °C is required at the taps. | T_r | °C | 50 |
| Flow direction in the riser Water cools as it flows, so the riser is slightly warmer on the side the water comes from. A circulation (return) riser usually runs downward; a supply riser fed from the basement runs upward. | dir_r | Downward (usual for a circulation return riser) | |
| Flow in the riser Circulation alone carries about 100–250 kg/h (0.03–0.07 L/s per riser in design examples). A supply riser carries 500–2000 kg/h while neighbours draw hot water; a pure circulation riser does not. | G_r | kg/h | 150 |
| Riser pipe | riser | Steel 1″ (DN25) | |
| Distance between the riser outlets (centre to centre) | H_t | mm | 400 |
| Pipe of the connection lines | pipe | PP-R 20 PN20 | |
| Supply line length, upper outlet to the warmer The whole developed length, verticals included. | L_s | m | 2 |
| Return line length, warmer to the lower outlet The whole developed length, verticals included. | L_rt | m | 2 |
| Depth of the in-wall run below the lower outlet Both lines run along the wall at this depth. A negative value puts the run above the lower outlet; a run above both outlets forms a hump where air collects. | dip | mm | 200 |
| 90° bends in each line | n90 | 5 | |
| 45° bends in each line | n45 | 1 | |
| Line insulation | ins | Foam around the pipe in a wall chase | |
| Warmer connection | conn | Both connections at the bottom (ladder, U, M) | |
| Heated height above the warmer's lower connection For a warmer fed at the top: the distance between its two connections. | H_w | mm | 750 |
| Height of the warmer's lower connection above the lower riser outlet | z_w | mm | 0 |
| Rated heat output at ΔT = 50 K (75/65/20 °C) From the data sheet (EN 442). A chrome ladder 760×500 gives 246 W (Stelrad); a painted one of the same size gives about 1.5 times more. If a shop states the output at ΔT = 70 K, multiply it by about 0.65. | Q_50 | W | 250 |
| Heat output exponent n EN 442 data of towel rails give 1.18–1.30. | n_w | 1.25 | |
| Bathroom air temperature | T_a | °C | 24 |
| Time (flow animation) | t_an | s | 0 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Heat output of the warmer | 83 W |
| Output kept compared with the warmer at the riser | 87 % |
| Water entering the warmer (hottest surface) | 49 °C |
| Water leaving the warmer | 41 °C |
| Flow through the warmer (negative: backwards) | 8.9 kg/h |
| Gravity head around the loop | 11.5 Pa |
| Push of the riser flow | 3.8 Pa |
| Heat lost by the lines | 17 W |
| Stable steady states (2: it can also stall) | 1 |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
Water density at 50 °C
Source: NIST Chemistry WebBook, water at 0.101325 MPa (IAPWS-95): 988.03 kg/m³ at 50 °C.
Inputs: the default inputs above.
| Result | Source | This calc |
|---|---|---|
| Water density at the riser temperature | 988 kg/m³ | 988 kg/m³ |
Water density at 80 °C
Source: NIST Chemistry WebBook, water at 0.101325 MPa (IAPWS-95): 971.79 kg/m³ at 80 °C.
Inputs: Hot water temperature at the riser outlets = 80 °C; the others as above.
| Result | Source | This calc |
|---|---|---|
| Water density at the riser temperature | 971.8 kg/m³ | 971.8 kg/m³ |
Water viscosity at 50 °C (within 1 %)
Source: NIST Chemistry WebBook, water at 0.101325 MPa (IAPWS 2008 viscosity): 0.5465 mPa·s at 50 °C.
Inputs: the default inputs above.
| Result | Source | This calc |
|---|---|---|
| Water viscosity at the riser temperature | 5.465 × 10⁻⁴ ± 5.5 × 10⁻⁶ Pa·s | 5.442 × 10⁻⁴ Pa·s |
Water viscosity at 80 °C (within 1.2 %)
Source: NIST Chemistry WebBook, water at 0.101325 MPa (IAPWS 2008 viscosity): 0.3544 mPa·s at 80 °C.
Inputs: Hot water temperature at the riser outlets = 80 °C; the others as above.
| Result | Source | This calc |
|---|---|---|
| Water viscosity at the riser temperature | 3.544 × 10⁻⁴ ± 4.3 × 10⁻⁶ Pa·s | 3.51 × 10⁻⁴ Pa·s |