Superheat and Subcooling Calculator with Refrigerant PT Chart

Calculate superheat and subcooling with dew/bubble PT curves, altitude correction, fixed-orifice targets, and TXV/EEV nameplate checks.

#CoolProp #fixed orifice #HVAC #PT chart #refrigerant blends #subcooling #superheat #TXV/EEV

This superheat calculator and subcooling calculator turns manifold pressures and pipe-clamp temperatures into the saturation margins used in air-conditioning service. It is for HVAC technicians, engineers and students checking a stable direct-expansion cooling system. Choose R-410A, R-32, R-407C, R-454B, R-452B, R-22 or R-134a.

Select the pressure reference used by your instrument. Gauge pressure is relative to local atmospheric pressure; the tool adds station pressure before calling CoolProp. Enter site altitude for a standard-atmosphere estimate, or use measured local station pressure. A weather report’s sea-level pressure is unsuitable for this correction. Absolute readings go directly into the property calculation.

Measure pressure and line temperature at matching locations. The suction dew point defines superheat: suction-line temperature minus dew temperature. The liquid-side bubble point defines subcooling: bubble temperature minus liquid-line temperature. For blends, choosing the wrong boundary introduces an error approximately equal to the full saturation glide. An R-407C, R-452B or R-454B PT chart therefore needs two boundaries. Pure R-32 has one saturation curve.

The manifold drawing shows pressure needles and the selected refrigerant’s saturation rings. Blue uses the dew ring; red uses the bubble ring. The adjoining diagram shades the glide band and marks the measured states, SH and SC. Drag either state to change its pressure and line temperature. Gauge faces use bar(g), and the diagram uses °C and MPa absolute. Inputs, results and the larger PT chart support the catalog’s metric/US switch; the manifold drawing keeps its labelled metric scales. The larger refrigerant PT chart provides pressure-based read-off for searches such as R-410A PT chart and R-32 pressure temperature chart.

For a fixed-orifice system, the target superheat calculator uses Craig Migliaccio’s published AC Service Tech approximation from indoor wet bulb and outdoor dry bulb. It is an estimate of charging-chart targets, with an OEM-chart override. For TXV/EEV equipment, enter the nameplate or service-manual subcooling target for the actual operating mode. Default tolerances are screening values and must yield to OEM instructions.

The short diagnosis identifies patterns consistent with undercharge, overcharge, restriction or low airflow. Similar readings can have several causes: a target-band comparison does not establish refrigerant mass or justify a charge change. Verify airflow, stable operation, sensor contact, valve operation and coil condition first.

This tool covers cooling-mode measurement reduction, not heating-mode charging, variable-speed commissioning routines, receiver inventory, refrigerant compatibility, leak repair or a complete refrigeration-cycle model. Installation and refrigerant service work belong to a qualified person following the equipment procedure. The Method notes state the supported saturation ranges, blend limitations and reference comparisons.

How it is calculated

Gauge readings become absolute through pabs=pg+patmp_{abs}=p_g+p_{atm}. Station pressure is measured or estimated with the tropospheric barometric relation patm=101.325(1−0.0065z/288.15)5.25588p_{atm}=101.325(1-0.0065z/288.15)^{5.25588} kPa, with altitude zz in metres (SPINNER TD-00022, §10). Absolute instrument readings receive no offset.

CoolProp evaluates saturation at each measured absolute pressure: Q=1Q=1 for dew and Q=0Q=0 for bubble. Then SH=Tsuction−Tdew,sSH=T_{suction}-T_{dew,s} and SC=Tbubble,l−TliquidSC=T_{bubble,l}-T_{liquid}. Full saturation glide is dew minus bubble at the same pressure. R-454B and R-452B use CoolProp's predefined mixtures R454B.mix and R452B.mix; R-407C and R-410A use the library's refrigerant models. No fixed glide offset is applied.

Before using the fixed-orifice estimate, CoolProp humid_air() evaluates the zero-humidity wet-bulb temperature at the entered return-air dry bulb and local atmospheric pressure (W=0W=0). The wet bulb must lie between that lower limit and the dry bulb, inclusive. Impossible pairs defer both the charge comparison and pattern diagnosis without altering the measurements (CoolProp Humid Air Properties, ASHRAE RP-1485 model).

For fixed orifices, Craig Migliaccio's AC Service Tech Target Superheat (2019), Example 3, gives SHtarget,°F=(3Twb,°F−80−Tout,°F)/2SH_{target,°F}=(3T_{wb,°F}-80-T_{out,°F})/2. The resulting Fahrenheit difference is converted to K. This published approximation can differ from an equipment charging chart; the OEM option accepts that chart's value directly. TXV/EEV comparison uses the user-entered nameplate/service-manual subcooling. Defaults are approximately ±5 °F (2.78 K) for fixed-orifice SH and ±3 °F (1.67 K) for TXV/EEV SC, following DOE's 2013 guideline and Carrier's service example.

Diagnosis is an author-written screening rule based on DOE printed pp. 31–34. Low dew temperature with high SH/low SC suggests undercharge; low dew with high SH/high SC suggests restriction; high condensing-over-ambient with high SC and normal/low SH suggests overcharge; low dew with low SH and no high SC suggests low airflow or low load. TXV regulation can hold SH normal during a fault, so low-pressure/low-SC undercharge can also be flagged. Other combinations remain unresolved. Condensing-over-ambient uses the mean of dew and bubble temperatures. Generic pressure thresholds are editable: about 35 °F dew and 30 °F condensing-over-ambient. These branches identify possible causes, not a confirmed fault.

The figure and chart use 241 CoolProp samples by default. Gauge-ring temperature marks use shape-preserving interpolation of that curve. Measured SH/SC use direct property calls, independently of display resolution.

The manifold PT axes cover the selected refrigerant's complete supported saturation curve and the line-temperature input limits. They do not depend on the dragged measurements. Dial faces use fixed display ranges by refrigerant: suction/liquid 12/36 bar(g) for R-134a, 16/48 bar(g) for R-22 and R-407C, and 20/60 bar(g) for R-410A, R-32, R-454B and R-452B. Needles stop at the scale ends and indicate an off-scale reading; PT marks are clipped at the chart boundary.

When the published fixed-orifice estimate cannot be used, the charging target and departure display an em dash (unavailable); the raw estimate remains in the calculation steps. Other deferred comparisons also hide the departure. SH/SC brackets are offset vertically from the measured states, with short extension lines at their temperature endpoints, so the drag rings do not conceal the spans.

Assumptions

Stable direct-expansion cooling, with nominal refrigerant composition, calibrated pressure readings, good clamp contact and matching pressure/temperature locations. A compressor service-port reading includes suction-line warming and pressure loss; it is total superheat at that port, not automatically evaporator-outlet superheat.

The selected TXV/EEV target must come from the actual equipment nameplate or service procedure. The illustrative 5.56 K target is not a universal specification. Generic TXV SH screening spans 4–25 °F (2.22–13.89 K), and fixed-orifice diagnostic SC uses 10 ±5 °F unless an OEM reference is entered. These broad DOE ranges are not valve-setting instructions. ACCA's checklist requires the manufacturer-approved method and airflow verification.

Where it applies

Supported saturation pressures are absolute: 100–3000 kPa for R-454B/R-452B; 100–3500 kPa for R-134a; 100–4200 kPa for R-407C; 100–4500 kPa for R-410A/R-22; 100–5000 kPa for R-32. The A2L ceiling avoids a reproducible CoolProp mixture-flash convergence gap at higher pressures; hot/high-head operation outside this range needs another verified property source. Out-of-range refrigerant pressures suppress the result cards; internal property guards only prevent secondary solver failures. Invalid return-air temperature pairs defer the charging comparison and pattern diagnosis.

Charging comparisons require airflow confirmation, stable operation, return dry bulb at least 70 °F (21.1 °C) and outdoor dry bulb at least 55 °F (12.8 °C). The approximate fixed-orifice method is limited here to 50–76 °F wet bulb, 55–115 °F outdoor dry bulb and calculated targets at least 5 °F. For the estimate, wet bulb must also be no lower than the zero-humidity wet-bulb limit at the local air pressure and no higher than return dry bulb. Recheck temperatures and site pressure when this physical range is violated. Do not replace a low or negative estimate with a zero target. Use the OEM procedure when these conditions are unsuitable. These are screening limits, not an ACCA or regulatory compliance certification.

Blend glide depends on pressure and composition. Chemours lists approximate nominal glides of 1.1 K for R-454B and 1 K for R-452B; Honeywell's R-407C chart shows about 7 K at 0 psig. These are context values, not constants in the equations, and full dew-to-bubble glide differs from effective evaporator glide after expansion. CoolProp and manufacturer EOS values can differ: the R-454B check allows 0.3 K, including about 0.22 K discrepancy at the 100 psig bubble point.

Negative SH/SC flag uncertain phase or measurement consistency, not a negative physical quantity of superheating/subcooling. A matching target does not prove correct charge. Multiple faults, noncondensables, variable-speed controls, abnormal load and pressure drops can defeat this short pattern screen. It computes no refrigerant mass, charging quantity, allowable charge, room concentration or leak safety limit. No mass or energy balance is inferred from the four measurements.

The illustrative gauge ranges are display choices, not instrument or equipment pressure ratings. Full-range PT axes keep state dragging stable but make short SH/SC spans small; use the numerical results for precise temperature differences.

References

  • CoolProp 8.0.0, fluid-property and predefined-mixture equations of state. Bell et al. (2014), DOI: https://doi.org/10.1021/ie4033999 ; https://coolprop.org/fluid_properties/Mixtures
  • Craig Migliaccio, AC Service Tech, Target Superheat, 15 April 2019, Example 3: https://www.acservicetech.com/posts/target-superheat
  • DOE Building America, Measure Guideline: Air Conditioner Diagnostics, Maintenance, and Replacement (2013), printed pp. 30–34: https://www1.eere.energy.gov/buildings/publications/pdfs/building_america/measure_guide_air_cond_diagnostics.pdf
  • Carrier, Form 38-12XA (November 1993), p. 6, cooling charging procedure and required liquid-line temperature table: https://www.shareddocs.com/hvac/docs/1009/Public/0E/38-12XA.pdf
  • ACCA, Quality HVAC Installation Checklist, p. 2, manufacturer-approved charge method and airflow verification: https://assets.ctfassets.net/3q1a0w8cwuwf/2aLWaGnTLTYuxebXda2y5r/beb57f6d2c808d60eb0877cab01bcf7f/ACCAQualityHVACInstallationChecklist-fillable.pdf
  • Honeywell, Genetron R-407C PT chart G525-715 (August 2017), pp. 1–2: https://prod-edam.honeywell.com/content/dam/honeywell-edam/pmt/oneam/en-us/refrigerants/documents/pmt-am-genetron407c-pressure-temp-chart-tech-tool1.pdf?download=false
  • Honeywell, Solstice R-454B PT chart TCS-24-09-EN (May 2024), p. 1: https://prod-edam.honeywell.com/content/dam/honeywell-edam/pmt/oneam/en-us/refrigerants/documents/hon-ess-am-3161690-adm-tds-pt-chart-solstice-454b-ltr-en.pdf
  • Chemours, Opteon XL41 product information, R-454B nominal glide approximately 1.1 K: https://www.opteon.com/en/-/media/files/opteon/opteon-xl41-product-information.pdf
  • Chemours, Opteon XL55 product information C-10214 (May 2016), R-452B nominal glide approximately 1 K: https://www.opteon.com/en/-/media/files/opteon/opteon-xl55-product-information.pdf
  • SPINNER, Technical Information TD-00022, section 10, barometric formula: https://www.spinner-group.com/images/download/technical_documents/SPINNER_TD00022.pdf
  • CoolProp 8.0.0, Humid Air Properties, ASHRAE RP-1485 model; humidity ratio W ≥ 0 and wet-bulb inputs/outputs: https://coolprop.org/fluid_properties/HumidAir.html

Inputs

InputSymbolUnitDefault
RefrigerantrefrigerantR-407C
Metering devicemeteringTXV / EEV
Fixed-orifice targettarget_methodAC Service Tech published estimate
Pressure referencepressure_basisGauge (relative to local air)
Suction pressurep_suctionkPa480
Liquid-line pressurep_liquidkPa1800
Suction-line temperatureT_suctiondegC14
Liquid-line temperatureT_liquiddegC38
Local air pressureatm_methodEstimate from altitude
Site altitudealtitudem0
Station pressure (absolute)
Use local station pressure, without a sea-level correction.
p_stationkPa101.325
Condenser entering dry bulbT_outdoordegC35
Return-air dry bulbT_indoordegC26.7
Return-air wet bulb
Measure near the evaporator inlet.
T_wetbulbdegC19.4
Cooling operation is stablestabilizedtrue
Airflow meets the OEM requirementairflow_checkedtrue
OEM target superheatSH_oemK8.33
Nameplate target subcooling
Read the target for this equipment and operating mode.
SC_nameplateK5.56
Diagnostic subcooling reference
Use an OEM value; the default 10 °F is only a generic screening reference.
SC_fixedK5.56
Superheat comparison toleranceSH_bandK2.78
Subcooling comparison toleranceSC_bandK1.67
PT curve samplesn_PT241
Low-pressure dew-temperature thresholdT_evap_lowdegC1.7
High condensing-over-ambient thresholdDT_cond_highK16.67

Results

With the default inputs above, the calc gives:

ResultValue
Superheat7.17 K
Subcooling5.46 K
Target comparisonSubcooling within target band
Pattern suggestsNo distinctive fault pattern
Suction dew point6.83 °C
Liquid-side bubble point43.46 °C
Selected charge target5.56 K
Measured minus target-0.1 K
Suction-pressure glide6.11 K
Liquid-pressure glide4.75 K
Mean condensing above ambient10.84 K
Local atmospheric pressure101.33 kPa

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

Honeywell R-407C superheat example

Source: Honeywell Genetron R-407C PT chart G525-715 (August 2017), p. 1: 40 psig, 32 °F line, approximately 22 °F dew and 10 °F superheat. Rounded source values; tolerance 0.06 K.

Inputs: Suction pressure = 275.8 kPa; Liquid-line pressure = 1,379 kPa; Suction-line temperature = 0 °C; Liquid-line temperature = 29.444 °C; the others as above.

ResultSourceThis calc
Superheat5.556 ± 0.06 K5.59 K
Suction dew point-5.556 ± 0.06 °C-5.59 °C

Honeywell R-407C subcooling example

Source: Honeywell Genetron R-407C PT chart G525-715 (August 2017), p. 1: 200 psig, 85 °F liquid line, approximately 92 °F bubble and 7 °F subcooling. Rounded chart; tolerance 0.06 K.

Inputs: Suction pressure = 275.8 kPa; Liquid-line pressure = 1,379 kPa; Suction-line temperature = 0 °C; Liquid-line temperature = 29.444 °C; the others as above.

ResultSourceThis calc
Subcooling3.889 ± 0.06 K3.872 K
Liquid-side bubble point33.333 ± 0.06 °C33.316 °C

AC Service Tech target-superheat example

Source: Craig Migliaccio, AC Service Tech, Target Superheat (15 April 2019), Example 3: 64 °F wet bulb and 96 °F outdoor dry bulb give an 8 °F target. Temperature difference converted to 4.444444 K.

Inputs: Metering device = Fixed orifice / capillary; Return-air wet bulb = 17.778 °C; Condenser entering dry bulb = 35.556 °C; the others as above.

ResultSourceThis calc
Published fixed-orifice superheat estimate4.444 K4.444 K
Selected charge target4.444 K4.444 K

R-454B dew and bubble versus manufacturer

Source: Honeywell Solstice 454B PT chart TCS-24-09-EN (May 2024), p. 1: at 100 psig bubble 34.1 °F and dew 36.3 °F; at 300 psig bubble 99.6 °F. CoolProp's mixture EOS differs by about 0.22 K at the low-side bubble point; 0.3 K absolute tolerance preserves both sources.

Inputs: Refrigerant = R-454B; Suction pressure = 689.5 kPa; Liquid-line pressure = 2,068 kPa; the others as above.

ResultSourceThis calc
Suction dew point2.389 ± 0.3 °C2.417 °C
Suction bubble-point temperature1.167 ± 0.3 °C0.948 °C
Liquid-side bubble point37.556 ± 0.3 °C37.354 °C

Standard atmosphere at 1000 m

Source: SPINNER Technical Information TD-00022, section 10: at 1000 m, standard atmospheric pressure is 898.8 hPa (89.88 kPa). Published table rounded to 0.1 hPa.

Inputs: Site altitude = 1,000 m; the others as above.

ResultSourceThis calc
Local atmospheric pressure89.88 kPa89.875 kPa

Carrier liquid-line charging table

Source: Carrier Form 38-12XA (November 1993), p. 6, required liquid-line temperature table for R-22: row 134 psig, 0 °F SC gives 76 °F saturation and 10 °F SC gives 66 °F liquid line. Table rounding allowed by 0.3 K tolerance.

Inputs: Refrigerant = R-22; Liquid-line pressure = 923.9 kPa; Liquid-line temperature = 18.889 °C; Nameplate target subcooling = 5.556 K; the others as above.

ResultSourceThis calc
Liquid-side bubble point24.444 ± 0.3 °C24.332 °C
Subcooling5.556 ± 0.3 K5.443 K

Related Resources

Responses

Your email address will not be published. Required fields are marked *

L ading...