Sectional radiator: flow extender (pseudo-diagonal connection)
Flow and temperature of every section of a sectional radiator connected on one side, diagonally, or through a flow extender tube (pseudo-diagonal), and the hole size that makes a perforated extender heat evenly.
A sectional radiator (aluminium, bimetal, cast iron) connected on one side takes water in at the top and out at the bottom of the same end. A flow extender is a tube pushed into the bottom header through the return connection: the water now leaves from its far open end, so the radiator works like a diagonal one. Ready-made extenders exist (Valtec VT.503 takes a 16 mm multilayer pipe as long as the radiator minus one section); many people make one from a piece of plastic pipe, and some drill small holes opposite every section.
This calc solves the water flow through every section of the radiator as a pipe network: the headers, the nipples between sections, the vertical channels, the ring around the tube, the tube itself and its holes. Each section gives off heat by the EN 442 law, and the water that cools in it gets heavier — a gravity head that pulls more flow down the sections that receive too little. The drawing shows the water temperature over each section's height and, when you press ▶, the water moving through every passage at its own speed.
What it shows
- the mean water temperature and flow of every section, for your connection and, side by side, for the same radiator connected on one side and diagonally;
- the radiator's output and return temperature, and the output relative to a diagonal connection;
- how uneven the sections are in two bounds: with the gravity head of the cooled water helping (best case) and with forced flow only (worst case);
- the pressure loss the extender adds compared with a plain same-side connection;
- for an extender, how even the sections are with holes of 0–8 mm, and which hole size is the most even.
How to read it
- With the gravity head counted, the network evens out a same-side, top-to-bottom radiator of ordinary size; a measured 10-section radiator at 127–220 kg/h agreed. Real radiators connected this way at low flow are still often reported to stay cold at the far end, also with the air bled — an effect of layered flow that a pipe network does not capture. The forced-flow bound shows what happens without gravity's help.
- A plain extender in a narrow header can starve the middle sections: their water must squeeze through the ring between the tube and the nipples. Holes of a few millimetres let it in on the way.
- Results depend on the bores and the flow; check both before drawing conclusions. If only the first one or two sections get hot, also check that supply and return are not swapped: a radiator fed at the bottom shows exactly this pattern.
Inputs you need
The section's datasheet output and the over-temperature it is given at (70 K in GOST datasheets, 50 K in EN 442 ones), the number of sections and their width, the flow through the radiator, and the bores of the headers, nipples and channels. Bores are rarely published: measure them through the plug opening, and check them with the water volume of one section from the datasheet.
How it is calculated
The radiator is solved as a network of pipes.
- Nodes: the top header at each section, the bottom header at each section; with a flow extender also the tube at each section it passes, the tube's open end and the outlet.
- Pieces between them: the vertical channel of each section; a header piece of one section width with its nipple; with an extender, the ring between the header (and nipple) and the tube, the tube pieces and the holes.
Each piece loses : laminar friction with for a round bore and 96 for the ring around the tube, turbulent friction by Blasius , and local losses (nipple 0.5 at its own velocity, vertical channel entry and exit 1.5, hole 2.7, tube open end 0.5).
A vertical channel also gets the gravity head of its water, : water that cools in a section is heavier than the supply and pulls flow down that section.
Water enters every section at the supply temperature (the top header carries supply water). A section gives off heat by the EN 442 law scaled to one section, with , together with ; its mean water temperature is .
The node pressures are found by Newton–Picard iterations (secant resistances, the gravity head linearised with its slope) until no flow changes by more than 10⁻⁷ of the total. The same radiator connected on one side without an extender and diagonally is solved alongside for comparison, and the extender again for holes of 0–8 mm.
Assumptions
- The network equations, Blasius friction and the per-section EN 442 law are combined here; the calc is not taken from one publication. Loss coefficients are textbook values for sharp-edged contractions, entries and orifices, not measured on radiators.
- Headers give no heat of their own: their share is counted in the sections, and every section's water enters at the supply temperature. Heat exchange between the water in the tube and in the ring around it is neglected.
- The water in a vertical channel is taken as mixed across it; layering inside headers and channels is not modelled. A section whose flow turns upward is counted as cold.
- Water properties at the mean of supply and room temperature; density fitted to IAPWS values within 0.2 kg/m³ (20–100 °C), viscosity by the Vogel equation.
- Manufacturers rarely publish the bores of headers, nipples and channels: they are inputs. The water volume of one section computed from them can be compared with the datasheet.
Where it applies
- Supply at the top, return at the bottom (same side, diagonal, or same side with an extender in the bottom header). A supply connected at the bottom (supply and return swapped) is not modelled: there the gravity head works against the flow, the first one or two sections take the hot water and the rest stay cool (Mar'ina et al. 2022 measured 50.8, 41.5 and 39.7 °C).
- With the gravity head counted, the model evens out a same-side, top-to-bottom radiator at any flow — even a tenth of that head is enough. A measured 10-section radiator at 127–220 kg/h agrees (2–3 °C between sections). Yet radiators connected this way are reported to stay cold at the far end at low flow (Valtec names low flow as the usual cause), also with the air bled and the supply at the top. The likely cause is layering: hot water runs along the top header and cools, cold water stays in the lower part of the far sections. A network of pipes with mixed water in each passage cannot show this. Read the two settings of the gravity switch as bounds: on is the best case, off is the forced-flow case without any help from gravity.
- For the same reason the model can understate what an extender gains. Owners report a plain tube making such a radiator clearly warmer, while at the same flow neither bound here gives more than a diagonal connection (a few per cent above same side). To compare a real radiator, measure the supply and return pipe temperatures and set the flow so that the return temperature here matches.
- Steady operation, no air in the headers, clean channels. If an extender does not help, the channels are likely blocked (Valtec).
- 3–30 sections, 5–1500 kg/h. Differences under about 1 K between sections are within the model's uncertainty.
- The flow through the radiator is an input. On a one-pipe riser with a bypass, a higher pressure loss in the radiator (an extender, small holes) sends less water through it.
- The drawing is a scheme: headers and tube are drawn thicker than to scale, the water temperature over each section's height follows its heat balance, the dots move at the water's speed in each passage times the speed-up.
References
- Valtec. Flow extender for sectional radiators VT.503: passport and operating manual. https://valtec.ru/document/technical/VT.503-0225.pdf
- Mar'ina Z. G., Vereshchagin A. Yu., Novozhilova A. V. Study of the influence of the connection mode of the STI brand aluminum radiator on its thermal characteristics. Energetika. Proc. CIS Higher Educ. Inst. and Power Eng. Assoc. 65(1), 2022, 89–98. https://doi.org/10.21122/1029-7448-2022-65-1-89-98
- Gritzki R., Felsmann C., Rösler M., Gritzki A., Iivonen M., Naumann J. Can we still trust in EN 442? New operating definitions for radiators, parts 1 and 2. REHVA Journal, 2021.
- Karabaş O., Önen M. C., Yiğit K. S. Experimental and numerical investigation of heat transfer performance for all water inlet and outlet configurations in a panel radiator. Buildings 15 (2025) 4259. https://doi.org/10.3390/buildings15234259
- EN 442-2: Radiators and convectors — Test methods and rating (characteristic equation Φ = K_m·ΔT^n).
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| Connection A flow extender is a tube put into the bottom header through the return connection. A plain tube takes the water only from its far open end, so the radiator works like a diagonal one. A tube with holes opposite every section also takes some water on the way, from the sections near the connection. | conn | Same side + flow extender: plain tube | |
| Tube outer diameter PP-R pipe sold as 1/2" is 20 mm outside; Valtec VT.503 takes a 16 mm multilayer pipe. | d_o | mm | 20 |
| Tube inner diameter PP-R 20 mm: 13.2 mm for PN20 and PN25 (3.4 mm wall), 16.2 mm for PN10. Multilayer 16 × 2.0: 12 mm. | d_i | mm | 13.2 |
| Tube length inside the radiator From the outer face of the first section. Valtec's instruction: the radiator length minus one section, so the tube ends at the joint of the last two sections. | L_t | mm | 880 |
| Hole diameter One hole (or several, below) in the tube opposite the middle of every section it passes. The chart "Flow extender: spread by hole diameter" and the card "Most even hole diameter" show which size evens the sections out best. | d_hole | mm | 4 |
| Holes per section | n_hole | 1 | |
| Number of sections | N_s | 12 | |
| Section width (pitch) | s_p | mm | 80 |
| Centre distance of the connections | H_c | mm | 500 |
| Datasheet output of one section From the radiator's datasheet. Datasheets after GOST R 53583 give it at Δt = 70 K (mean water 90 °C, air 20 °C); EN 442 datasheets at ΔT = 50 K (75/65/20 °C). Enter the over-temperature it belongs to below. | Phi_n | W | 190 |
| Over-temperature of the datasheet output | dT_n | K | 70 |
| Radiator exponent n Output ∝ ΔT^n (EN 442). About 1.3 for sectional radiators; the datasheet gives it. | n_x | 1.3 | |
| Header bore Inner diameter of the top and bottom headers. Measure it through the plug opening. | D_h | mm | 28 |
| Bore at the nipples (narrowest) The narrowest passage between two sections, usually inside the nipple. With a flow extender, the ring between this bore and the tube is where the water from the near sections must squeeze through. | D_n | mm | 26 |
| Vertical channel bore | d_r | mm | 14 |
| Supply water temperature | T_s | °C | 70 |
| Room air temperature | T_a | °C | 20 |
| Water flow through the radiator 60 kg/h carries about 1.4 kW at a 20 K drop. A one-pipe riser can push several hundred kg/h through a radiator; a two-pipe system with a thermostatic valve often less than 50 kg/h. | m_w | kg/h | 60 |
| Count the gravity head of the cooled water (best case) On: water that cools in a section gets heavier and pulls more flow down that section, as if each section's water were mixed across — this evens a top-to-bottom radiator out almost completely, which matches measurements at 130–220 kg/h but not radiators at low flow that stay cold at the far end. Off (default): forced flow only, the worst case, which reproduces that picture; use it to size an extender and its holes. The result cards show both. | grav | false | |
| Animation time Press ▶ to watch the water: each dot moves at the water's speed in its passage, sped up by the factor below. | t_an | s | 0 |
| Animation speed-up The dots move this many times faster than the water. Lower it at high flows if the dots in the tube flicker. | k_an | 5 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Radiator output | 858 W |
| Output relative to a diagonal connection | 76.5 % |
| Return water temperature | 57.7 °C |
| Spread of sections, with gravity help (best case) | 4 K |
| Spread of sections, forced flow only (worst case) | 30.9 K |
| Coldest section (mean water) | 36.5 °C |
| Pressure loss in the radiator | 30.5 Pa |
| Pressure loss added vs plain same side | 29 Pa |
| Most even hole diameter (flow extender) | 5 mm |
| Water volume of one section | 0.17 L |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
Equal flows, 60 kg/h: the whole radiator follows the EN 442 law of N sections
Source: Limiting case with a closed form: when every section gets the same flow (here the gravity head evens them out), the radiator is one EN 442 emitter of 12 × 190 W at 70 K, n = 1.3: m·c·(θ_in − θ_out) = N·Φ_n·(ΔT_ln/70)^1.3 with θ_in = 50 K, m = 60 kg/h, c = 4185 J/(kg·K). Solved separately by bisection (Python): Φ = 1146.1 W, return 53.57 °C. Not from the network formulas of this calc. Tolerance 0.5 %.
Inputs: Connection = Diagonal: in at the top, out at the bottom far end; Count the gravity head of the cooled water (best case) = yes; the others as above.
| Result | Source | This calc |
|---|---|---|
| Radiator output | 1,146 ± 5.7 W | 1,146 W |
| Return water temperature | 53.57 ± 0.1 °C | 53.57 °C |
Equal flows, 20 kg/h, same side: the whole radiator follows the EN 442 law
Source: Same closed form as the 60 kg/h case at m = 20 kg/h: Φ = 772.1 W, return 36.79 °C (bisection in Python). At low flow the gravity head of the cooled water makes the section flows equal, so the network must reduce to it. Tolerance 0.5 %.
Inputs: Connection = Same side: in at the top, out at the bottom; Water flow through the radiator = 20 kg/h; Count the gravity head of the cooled water (best case) = yes; the others as above.
| Result | Source | This calc |
|---|---|---|
| Radiator output | 772.1 ± 3.9 W | 772.1 W |
| Return water temperature | 36.79 ± 0.1 °C | 36.792 °C |
Mar'ina et al. 2022 (qualitative): 10 sections, same side top to bottom, 0.13 m³/h — sections heat about equally
Source: Qualitative consistency, not a quantitative validation. A 10-section STI Classic 500/80 (192 W per section at 70 K, 0.29 L of water per section) connected on one side top to bottom at 0.13–0.22 m³/h: thermography of the fin surfaces showed the sections within 2–3 °C, and the authors take all sections' outputs as equal. Bores chosen so that one section holds 0.29 L (header 32 mm, channel 21 mm, the real ones are not published); supply 75 °C from the thermograms' scale and room 20 °C are assumptions. The calc's mean water temperatures of the sections must then lie within 3 K.
Inputs: Connection = Same side: in at the top, out at the bottom; Number of sections = 10; Datasheet output of one section = 192 W; Header bore = 32 mm; Bore at the nipples (narrowest) = 30 mm; Vertical channel bore = 21 mm; Supply water temperature = 75 °C; Water flow through the radiator = 127 kg/h; Count the gravity head of the cooled water (best case) = yes; the others as above.
| Result | Source | This calc |
|---|---|---|
| Spread of section temperatures (hottest − coldest) | 1.5 ± 1.5 K | 1.314 K |