Line Impedance Calculator: GMD, GMR and Carson’s Equations
Calculate overhead-line R, L and C per km from conductor positions, bundles and soil resistivity. Inspect phase and sequence impedance matrices, with Carson earth return and neutral reduction.
This line impedance calculator turns an overhead tower or pole cross-section into electrical parameters for power-frequency studies. Engineers can prepare line models for load flow and fault analysis, while students can follow the connection between conductor geometry, GMD, GMR and sequence impedance. All electrical parameters are per kilometre; there is no line-length assumption hidden in the results.
Enter the horizontal position and representative height of phases A, B and C above the earth plane. Positions are conductor centres, or bundle centres when several subconductors form one phase. Use the viewer’s metric/US switch for geometry entry. The drawing keeps one geometric scale and shows reflected electrostatic image conductors below the earth. Conductor symbols are enlarged so that they remain visible.
Choose a conductor row or enter custom outside diameter, magnetic GMR and AC resistance. The two Prysmian rows are dated manufacturer data for 75 °C and 60 Hz; the IEEE rows reproduce historical test-feeder inputs. These datasets have different resistance bases. For another operating temperature, supply the appropriate AC resistance yourself. The tool does not infer operating temperature from conductor size, and a stranded conductor’s magnetic GMR should come from its data sheet.
Select one to four subconductors per phase. Twin, equilateral-triangle and square bundles use adjacent centre spacing and equal current sharing. Equivalent bundle radii represent their magnetic and electrostatic behaviour. The GMD/GMR calculator then provides the familiar transposed-line estimates, alongside a matrix model that retains the actual phase spacing and conductor heights. The spacing chart isolates the inductance change caused by bundling using the GMD approximation. Each curve stops at its own clearance limit. A message explains when a bundle size has no valid spacing interval.
For earth return, choose the numerical Carson integral or the modified Carson equations commonly used in distribution-feeder examples. Set a representative uniform soil resistivity. Modified Carson is accepted only when its phase and sequence resistance/reactance entries agree with the integral within 5%; otherwise select the integral. An optional neutral or shield wire is eliminated by Kron reduction under the assumption of ideal grounding along the line. This is a useful planning model, but it does not calculate the effect of individual footing resistances.
Read conductor resistance separately from effective positive-sequence resistance, which includes induced return-path losses. The phase impedance matrix includes mutual coupling. Effective inductance is reactance divided by angular frequency. Capacitance uses physical radii and electrostatic images, including the grounded wire when enabled. Negative off-diagonal capacitances are normal for a Maxwell matrix.
Enable full transposition only for equal lengths in all three cyclic phase positions. Otherwise the displayed sequence impedance matrix can contain coupling between sequences; its diagonal values alone do not define three independent networks. This overhead-line model does not cover underground cables, sheaths, layered soils, switching surges, corona, ampacity or sag design. Installation work belongs to a qualified person.
How it is calculated
Geometry and bundles
Centre spacings give . For a regular bundle of subconductors, adjacent spacing gives circumradius and equivalent radius . Use supplied magnetic GMR for in inductance and physical radius in capacitance. Resistance is divided by . For a single solid nonmagnetic round conductor only, GMR is ; do not impose this on stranded ACSR.
Carson earth return
Carson (1926), expressed in SI as Theodoulidis (2015), attached s1 file page 2, Eqs. (1)–(2): . Self terms replace by magnetic GMR. is distance to the reflected conductor. The integral is
The logarithmic wavenumber substitution uses a 601-point base trapezoidal rule, with extra points for wide horizontal separations, bounds from dimensionless wavenumber to , and . A doubled-resolution probe checks convergence. The modified option is its low-argument approximation , and . Units are explicitly converted to Ω/km. Iowa State EE653 s2 pp. 23–31 explains the truncation and neutral reduction. Power frequency alone does not bound truncation error. Both methods are evaluated at the current inputs. The modified option is accepted only when every real and imaginary entry of both the reduced phase and sequence matrices agrees with the integral within 5%. Relative differences use the integral entry magnitude, with a denominator floor of 0.000001 Ω/km for nearly zero components. This 5% comparison screen is a tool policy, not a universal error bound or a standard requirement.
Grounded-wire reduction, capacitance and sequences
For series impedance, . Electrostatic coefficients use , with physical radius on the diagonal. Grounded-wire elimination is applied to P, then inverted: . This is equivalent to taking the phase block of the full Maxwell capacitance matrix at . The electrostatic image construction is derived here from the line-charge potential and the zero-potential earth boundary.
Full transposition averages the three cyclic permutations of the reduced Z and C matrices. With and , , ordered zero, positive, negative (Kersting, 4th ed., Ch. 4; Iowa State s2 pp. 36–40). Positive-sequence L and C are diagonal entries; off-diagonal sequence coupling is retained. The GMD estimates are and .
Feasible bundle-spacing curves
The sweep uses the same strict conductor-diameter, ten-envelope-radius phase clearance, earth clearance and grounded-wire clearance rules as the selected geometry. For each bundle size its circumradius is . The limiting circumradius is the minimum of , , and, when included, . Adjacent spacings remain within 0.05–1.5 m and exceed conductor diameter. Curve endpoints stay just inside the strict limits. Infeasible portions are omitted; if no bundle has an interval, only the single-conductor baseline remains and an input message explains what to change.
Assumptions
- Three straight, parallel phase conductors with identical conductor data and identical regular bundles; one optional single grounded wire.
- Homogeneous nonmagnetic earth and air, with soil displacement current neglected. Sinusoidal steady state, using the convention.
- Constant supplied AC resistance and magnetic GMR at the chosen operating condition. Manufacturer rows use 75 °C / 60 Hz; no temperature or skin-effect correction is added. Custom rows must supply suitable values.
- Bundle centres and equivalent radii approximate the field outside each bundle. Equal current sharing and at least ten bundle-envelope radii of separation are required. The adjacent-spacing formula is exact for the self GMR of a regular bundle under equal sharing; interphase fields use bundle centres.
- The optional wire is ideally multigrounded with zero longitudinal voltage drop. Full transposition means equal lengths in cyclic phase positions while this wire remains fixed.
- Electrostatic capacitance assumes a perfectly conducting earth boundary. The magnetic earth-return integral treats finite earth conductivity separately.
Where it applies
Power frequency 40–70 Hz; soil resistivity 10–10,000 Ω·m; conductor heights 1–80 m; horizontal coordinates within ±60 m. Use representative mean heights along a span when sag matters. Close bundles, overlapping conductors and conductors too close to ground are rejected.
The full numerical Carson integral covers the advertised geometry, frequency and soil ranges under the stated physical assumptions. Modified Carson is restricted by the 5% phase-and-sequence R/X comparison screen described in the method; results are withheld and the user is directed to the integral if it fails. High conductors, wide spacings or low soil resistivity can invalidate the approximation even at 50 or 60 Hz. Small differences from the IEEE benchmark are expected if the integral is selected. Published IEEE matrices are rounded; the reference tolerance is 0.00008 Ω/km. Untransposed lines generally have coupled sequence networks.
Effective and include the selected earth and neutral return model. These are per-unit-length steady-state parameters, not a broadband line model. Physical AC resistance and GMR remain fixed when frequency changes; update custom data where needed.
No underground cable insulation, concentric neutral, sheath bonding, earth stratification, magnetic soil, corona, lightning, surge propagation, ampacity, clearance compliance, footing impedance or sag calculation. The tower support is schematic and is not part of the electromagnetic model. Installation work belongs to a qualified person.
Bundle-spacing sweeps use these same validity constraints for every plotted point. A selected single-conductor geometry can be valid even when no twin, triple or quad bundle fits. Unsupported bundle curves are omitted rather than assigned an artificial minimum sweep interval.
References
- J. R. Carson, Wave Propagation in Overhead Wires with Ground Return, Bell System Technical Journal 5(4), 539–554 (1926). https://doi.org/10.1002/j.1538-7305.1926.tb00122.x
- T. Theodoulidis, On the Closed-Form Expression of Carson’s Integral, Periodica Polytechnica EECS 59(1), 26–29 (2015), file page 2 Eqs. (1)–(2). https://doi.org/10.3311/PPee.7894 ; open paper https://pp.bme.hu/eecs/article/download/7894/6772
- W. H. Kersting, Distribution System Modeling and Analysis, 4th edition, CRC Press, Chapters 4–5. https://doi.org/10.1201/9781315120782 . Open teaching exposition: Iowa State EE653, pp. 24–40, https://wzy.ece.iastate.edu/PPT/EE653%20Modeling%20Series%20Impedance%20of%20Overhead%20and%20Underground%20Lines.pdf
- IEEE PES 13-node feeder configurations 601 and 602, public test data: https://ewh.ieee.org/soc/pes/dsacom/testfeeders/testfeeders.pdf . Matrices as reproduced in EPRI OpenDSS, corrected 2011-09-14: https://github.com/tshort/OpenDSS/blob/master/Distrib/IEEETestCases/13Bus/IEEE13Nodeckt.dss
- GridLAB-D IEEE 13-node test-feeder conductor data and spacings, accessed 2026-10-27: https://github.com/GridOPTICS/FNCS-gridlab-d/blob/master/models/IEEE_13_Node_Test_Feeder.glm
- Prysmian TransPowr ACSR/TW US, reduced-diameter electrical properties, file p. 3, Dove and Hawk rows; accessed 2026-10-27. https://na.prysmian.com/sites/na.prysmian.com/files/media/documents/TransPowr%C2%AE%20ACSR-TW%20Bare%20Overhead%20Conductor%20Trapezoidal%20Aluminum%20Conductor%20(US).PDF
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| Earth-return model The integral includes conductor heights. Modified Carson truncates the earth-return terms and omits height dependence; it is available only when its phase and sequence R/X entries agree with the integral within 5% at the current geometry and soil resistivity. | earth_model | Carson integral | |
| Power frequency | f | Hz | 60 |
| Soil resistivity One uniform, nonmagnetic soil half-space. | rho_soil | ohm*m | 100 |
| Fully transposed line Equal lengths in the three cyclic phase positions; the grounded wire stays in place. Results are averaged per unit length. | transposed | false | |
| Phase subconductor All phases use the same conductor. Custom values: diameter, magnetic GMR, and AC resistance at your operating temperature and frequency. | wire | Prysmian Dove/TW | |
| Subconductors per phase 1 = single; 2 = twin; 3 = equilateral triangle; 4 = square. Equal current sharing and well-separated bundles. | n_bundle | 1 | |
| Adjacent bundle spacing Center-to-center distance between neighboring subconductors. | s_bundle | m | 0.4 |
| Include grounded neutral or shield wire One continuous, ideally multigrounded wire; Kron reduction assumes its voltage drop is zero. Disable for a three-wire line. | neutral | true | |
| Grounded-wire conductor | neutral_wire | IEEE 4/0 ACSR | |
| Grounded wire — horizontal position | x_n | m | 0 |
| Grounded wire — height above earth | h_n | m | 11 |
| Phase A — horizontal position | x_a | m | -4 |
| Phase A — height above earth Use a representative mean conductor height along the span; do not use the tower attachment height alone when sag is significant. | h_a | m | 15 |
| Phase B — horizontal position | x_b | m | 0 |
| Phase B — height above earth Use a representative mean conductor height along the span; do not use the tower attachment height alone when sag is significant. | h_b | m | 15 |
| Phase C — horizontal position | x_c | m | 4 |
| Phase C — height above earth Use a representative mean conductor height along the span; do not use the tower attachment height alone when sag is significant. | h_c | m | 15 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Conductor AC resistance per phase | 0.1224 Ω/km |
| Positive-sequence resistance R₁ | 0.1225 Ω/km |
| Positive-sequence inductance L₁ | 1.268 mH/km |
| Positive-sequence capacitance C₁ | 9.141 nF/km |
| Phase GMD | 5.0397 m |
| Bundle magnetic GMR | 8.87 mm |
| Bundle electrostatic radius | 10.82 mm |
| Zero-sequence capacitance C₀ | 5.295 nF/km |
| Largest sequence cross-coupling | 0.035 Ω/km |
| Modified Carson max. R/X discrepancy (%) | 2.78 |
It also shows: Positive-sequence impedance Z₁, Ω/km; Zero-sequence impedance Z₀, Ω/km; Negative-sequence impedance Z₂, Ω/km.
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
IEEE 13-node configuration 601 — all phase-matrix entries
Source: IEEE PES 13-node feeder configuration 601, published R and X in ohm/mile as reproduced in EPRI OpenDSS IEEE13Nodeckt.dss, corrected 2011-09-14. Geometry and historical conductors from GridLAB-D. Converted to ohm/km using 1 mile = 1.609344 km. Tolerance covers printed matrix rounding and rounded modified-Carson constants.
Inputs: Earth-return model = Modified Carson; Phase subconductor = IEEE 556.5 ACSR; Phase A — horizontal position = -0.4572 m; Phase A — height above earth = 8.534 m; Phase B — horizontal position = -1.219 m; Phase B — height above earth = 8.534 m; Phase C — horizontal position = 0.9144 m; Phase C — height above earth = 8.534 m; Grounded wire — height above earth = 7.315 m; the others as above.
| Result | Source | This calc |
|---|---|---|
| Phase-matrix resistance AA | 0.2153 Ω/km | 0.2153 Ω/km |
| Phase-matrix reactance AA | 0.6325 Ω/km | 0.6325 Ω/km |
| Phase-matrix resistance AB | 0.09693 Ω/km | 0.0969 Ω/km |
| Phase-matrix reactance AB | 0.3117 Ω/km | 0.3117 Ω/km |
| Phase-matrix resistance AC | 0.09818 Ω/km | 0.09818 Ω/km |
| Phase-matrix reactance AC | 0.2632 Ω/km | 0.2632 Ω/km |
| Phase-matrix resistance BB | 0.2097 Ω/km | 0.2097 Ω/km |
| Phase-matrix reactance BB | 0.6511 Ω/km | 0.6511 Ω/km |
| Phase-matrix resistance BC | 0.09538 Ω/km | 0.09537 Ω/km |
| Phase-matrix reactance BC | 0.2392 Ω/km | 0.2392 Ω/km |
| Phase-matrix resistance CC | 0.2121 Ω/km | 0.2121 Ω/km |
| Phase-matrix reactance CC | 0.643 Ω/km | 0.643 Ω/km |
IEEE 13-node configuration 602 — all phase-matrix entries
Source: IEEE PES 13-node feeder configuration 602, published R and X in ohm/mile as reproduced in EPRI OpenDSS IEEE13Nodeckt.dss. Phase positions are C-A-B, whereas 601 is B-A-C. Independent published matrix; same unit conversion and rounding allowance as 601.
Inputs: Earth-return model = Modified Carson; Phase subconductor = IEEE 4/0 ACSR; Phase A — horizontal position = -0.4572 m; Phase A — height above earth = 8.534 m; Phase B — horizontal position = 0.9144 m; Phase B — height above earth = 8.534 m; Phase C — horizontal position = -1.219 m; Phase C — height above earth = 8.534 m; Grounded wire — height above earth = 7.315 m; the others as above.
| Result | Source | This calc |
|---|---|---|
| Phase-matrix resistance AA | 0.4676 Ω/km | 0.4677 Ω/km |
| Phase-matrix reactance AA | 0.7341 Ω/km | 0.7341 Ω/km |
| Phase-matrix resistance AB | 0.09818 Ω/km | 0.09818 Ω/km |
| Phase-matrix reactance AB | 0.2632 Ω/km | 0.2632 Ω/km |
| Phase-matrix resistance AC | 0.09693 Ω/km | 0.0969 Ω/km |
| Phase-matrix reactance AC | 0.3117 Ω/km | 0.3117 Ω/km |
| Phase-matrix resistance BB | 0.4645 Ω/km | 0.4645 Ω/km |
| Phase-matrix reactance BB | 0.7446 Ω/km | 0.7446 Ω/km |
| Phase-matrix resistance BC | 0.09538 Ω/km | 0.09537 Ω/km |
| Phase-matrix reactance BC | 0.2392 Ω/km | 0.2392 Ω/km |
| Phase-matrix resistance CC | 0.4621 Ω/km | 0.462 Ω/km |
| Phase-matrix reactance CC | 0.7526 Ω/km | 0.7526 Ω/km |
Prysmian Dove/TW — one-foot GMD R, X and C
Source: Prysmian TransPowr ACSR/TW US, file p. 3, reduced-diameter electrical-properties Dove row: 0.0373 ohm/kft AC75, 0.0813 ohm/kft inductive reactance, and 0.5229 megaohm for a 1000-ft length, on a 1-ft reference radius (footnote 5). https://na.prysmian.com/sites/na.prysmian.com/files/media/documents/TransPowr%C2%AE%20ACSR-TW%20Bare%20Overhead%20Conductor%20Trapezoidal%20Aluminum%20Conductor%20(US).PDF . Equal 1-ft phase spacings at 70 m height reproduce the remote-earth limit; neutral disabled. The printed capacitive reactance implies 16.64314 nF/km, whereas the ideal-air model with the sheet's 0.852-in diameter gives 16.6653 nF/km (0.13% higher). The table's reactance and diameter are slightly inconsistent under the ideal-air formula; retain physical radius and vacuum permittivity, with 0.03 nF/km allowance for this published-data difference. The impedance allowance covers printed X/GMR rounding. No formula or expected value is fitted.
Inputs: Include grounded neutral or shield wire = no; Fully transposed line = yes; Phase A — horizontal position = -0.1524 m; Phase A — height above earth = 70 m; Phase B — height above earth = 70.264 m; Phase C — horizontal position = 0.1524 m; Phase C — height above earth = 70 m; the others as above.
| Result | Source | This calc |
|---|---|---|
| Phase GMD | 0.3048 m | 0.3048 m |
| Positive-sequence resistance R₁ | 0.1224 Ω/km | 0.1224 Ω/km |
| Positive-sequence reactance | 0.2667 Ω/km | 0.2667 Ω/km |
| Positive-sequence capacitance C₁ | 16.643 ± 0.03 nF/km | 16.665 nF/km |
Related Resources
Related courses
IEC Electrical Schematics and Industrial Control Panels
5
Original price was: 42 €.21 €Current price is: 21 €.
Basic Electrical Controls & Diagram Reading
7
Original price was: 32 €.18 €Current price is: 18 €.
Modeling Electrical Motor Faults with FEM Simulation using ANSYS MAXWELL
3
Original price was: 50 €.15 €Current price is: 15 €.







Responses