Home Backup Generator Sizing Calculator

Size a home generator for running loads, sequenced motor starts, voltage dip and site derating. Estimate part-load fuel use, monthly cost and a conditional solar–battery cost crossover.

#derating #fuel-consumption #generator-sizing #home-backup #HOMER #motor starting #NEMA-MG1 #voltage-dip

This generator size calculator helps homeowners, electrical engineers and students estimate the continuous rating needed for a home backup supply. It combines background electrical demand with up to three motor loads, then checks running kW, running kVA, starting demand and a voltage-dip screening limit. It is intended for conventional synchronous liquid-fuel generators.

Start with the equipment nameplates. Enter each motor’s mechanical shaft rating and the numeric locked-rotor kVA-per-horsepower value associated with its NEMA code letter. The default motor sizes are illustrative, not appliance ratings. Open the detailed assumptions to change motor efficiency and running power factor. If a load has electronic speed control, a soft starter or only an electrical-input label, obtain suitable starting data before using the motor model.

To answer “what size generator do I need,” try both a controlled start order and All together. The animated schematic shows each motor waiting, starting and running. The chart includes overlapping starts when the chosen delay is shorter than the entered inrush duration. Sequence savings require actual controls: check automatic pump and thermostat restarts, not just the first transfer after an outage. An omitted motor retains its numbered position in a chosen sequence.

Enter the selected generator’s continuous rating, nameplate power factor, voltage, site altitude and ambient temperature. Running reserve and site losses are applied separately from the starting checks. The displayed minimum is a preliminary nameplate requirement, not a commercially available model recommendation. The voltage curve is an initial-cycle impedance envelope with fixed excitation; it does not predict regulator recovery, frequency dip, acceleration or successful starting. Obtain the generator manufacturer’s transient assessment before purchase.

Generator fuel consumption uses a two-point linear fit that retains idle fuel use. The default calibration comes from Honda EU7000iS tank runtimes. Its endpoint checks verify calibration, not independent predictive accuracy; scaling those coefficients to another size is an approximation, so enter your actual generator’s fuel data. Set average load, daily operating hours and outage days to estimate refills and monthly fuel cost. The editable price baseline is the 2025 US regular gasoline annual average, not a live local price.

The solar-plus-battery comparison reports the first cheaper year-end within the chosen horizon, including stated maintenance and replacement intervals. All capital and service costs are illustrative budgets. Prices stay constant and cash flows are undiscounted; taxes, financing and electricity-bill savings are excluded. Equivalent backup service must be designed independently, including cloudy-weather energy and inverter starting capacity. This tool does not size batteries or calculate their runtime.

Carbon monoxide and back-feed can be fatal. Keep portable generators outside, at least 6.1 m (20 ft) from openings, with exhaust away and working CO alarms. Never connect through a wall outlet. Installation, transfer equipment, grounding, bonding and circuit protection belong to a qualified electrician working to the rules in force.

How it is calculated

Running and locked-rotor demand

Motor electrical running power is shaft power divided by efficiency. Apparent running power is Sr=Pr/PFrS_r=P_r/\mathrm{PF}_r and the quadrature component is Qr=Sr2−Pr2Q_r=\sqrt{S_r^2-P_r^2}. Sum real and quadrature components separately, then take their vector magnitude; do not add unlike power factors as scalar kVA.

For each motor, SLR=KcodeHS_{LR}=K_{code}H with HH in mechanical horsepower and the user-entered KcodeK_{code} in kVA/hp. The locked-rotor convention is described by Baldor-Reliance with reference to NEMA MG 1-2011, §10.37.2. This calculator reproduces no code-letter table. Current is 1000SLR/V1000S_{LR}/V for single phase or 1000SLR/(3V)1000S_{LR}/(\sqrt3V) for balanced three phase.

Start states and sizing

Background demand is already connected. Each motor contributes zero before its start, its locked-rotor complex power for the entered duration, and its running complex power afterward. Evaluating every start and end instant finds the exact maximum of this rectangular envelope, even with overlap. Animation time only reads the cached sizing results.

Cummins T-030, Issue 9 (2015), §7.1.9 discusses largest-motor-first sequencing and typically 5–10 s stabilization between load steps. Real controls must enforce the order; recurring automatic restarts may coincide.

The additive site factor is D=1−dhh/304.8−dTΔT/5.6D=1-d_hh/304.8-d_T\Delta T/5.6, with altitude in metres and ΔT=max⁡(T−25 ∘C,0)\Delta T=\max(T-25\,^{\circ}\mathrm C,0) in K. Default slopes follow the Champion 201249 operator manual, rev 20251223. Apply the same factor conservatively to the kW and kVA capacity limits; replace the assumptions with the more restrictive manufacturer site limits.

For each limit, calculate the required continuous nameplate kW. Take the greatest of real and apparent running demand with reserve, peak starting real and apparent demand without overload credit, and the electrical dip requirement.

Voltage screening model derived here

Represent the connected loads by rated-voltage equivalent impedances and the source by fixed 1 pu internal voltage behind purely inductive reactance XX. With nameplate base Sg=Pg/PFgS_g=P_g/\mathrm{PF}_g, the terminal voltage fraction is

v=1(1+XQ/Sg)2+(XP/Sg)2.v=\frac{1}{\sqrt{(1+XQ/S_g)^2+(XP/S_g)^2}}.

For required fraction v0v_0, let a=v02a=v_0^2. Solving the quadratic gives

Sg,min⁡=X{aQ+a2Q2+a(1−a)(P2+Q2)}1−a.S_{g,\min}=\frac{X\{aQ+\sqrt{a^2Q^2+a(1-a)(P^2+Q^2)}\}}{1-a}.

Use the largest value across load states. Reactance must be on the selected generator's nameplate kVA base. Site derating affects capacity, not the electrical reactance base. This voltage-divider derivation is our screening model, not a Cummins performance curve. Cummins T-030 §§4.2.5.6–4.2.5.8, printed pp. 45–47, explain why initial dip and subsequent recovery require different equipment data.

Part-load fuel and ownership cost

Fit F=afPg+bfPoutF=a_fP_g+b_fP_{out} from two measured reference loads. The slope is the fuel-flow difference divided by output-power difference; the intercept is normalized by the reference generator rating. This is HOMER's linear fuel-curve form. The Honda endpoint checks reproduce the calibration data; they do not independently validate predictions between those points or scaling to other generators. Require a strictly positive idle intercept for a running engine. Use every positive fuel-test output interval exactly; reject a zero or negative interval. Average fuel uses all-on real demand times the average-load fraction; sizing uses the full demands.

Monthly hours are daily operating hours times outage days. Multiply hours by fuel flow and dated unit price. Annual operation repeats the planning month twelve times. Cumulative costs include purchase, fuel, maintenance, generator replacement by operating hours, and battery replacement by calendar years. The crossover is the first year-end where solar-plus-battery cumulative cost is no higher; later replacements can reverse it.

Assumptions

  • Conventional synchronous generator, balanced single/split phase or balanced three phase. All listed motors use the entered line-to-line voltage. Split-phase leg limits need a separate check.
  • Three direct-on-line induction-motor equivalents at rated shaft load. A common illustrative locked-rotor PF of 0.35 and the entered rectangular duration describe starting states, not acceleration. Motor efficiency and running PF are editable planning assumptions.
  • Equivalent impedances are held constant within each state. Reported starting kVA and current are nominal-voltage quantities. No credit is taken for reduced current during sag when checking capacity.
  • Fixed internal source voltage, no automatic voltage regulator, governor or frequency dynamics. The electrical envelope can retain a running-load drop after inrush ends. It is not a measured waveform or a guaranteed worst-case transient bound.
  • Default reactance 0.12 pu is an illustrative assumption, not a selected generator's specification. The separate Honda fuel calibration is not a Honda voltage-dip model; Honda EU7000iS is an inverter set.
  • Default fuel points use 5.1 US gal / 16.0 h at quarter load and 5.1 US gal / 6.4 h at full rated 5.5 kW. The Honda checks verify reproduction of these calibration endpoints and their published tank runtimes, not independent predictive accuracy. Scaling normalized fuel coefficients between generators is approximate. Actual size, control mode, fuel and site conditions can change them. Idle is an extrapolation; an off engine consumes zero, while the entered operating hours describe an on engine.
  • Price baseline: EIA 2025 annual US regular gasoline, 3.097 USD/US gal = approximately 0.81814 USD/L, checked 2026-10-25. The USD/L price field is a currency label and stays per litre under the unit switch.
  • All purchase, maintenance, service-life and replacement defaults are illustrative budgets, not quotations. Constant prices, undiscounted cash flows, no residual value, grants, financing or grid-export savings. Replacements are charged at the year-end in which an interval is reached, including the horizon end.
  • The alternative solar-plus-battery installation must independently meet the same outage energy, motor starts and reliability target. Its energy production, battery capacity and autonomy are not calculated here.

Where it applies

Use this as a preliminary selection and cost-comparison screen, then verify a real generator with its manufacturer. Check against the standard in force; the cited historical NEMA edition describes the code-letter convention, not an installation approval.

Input ranges cover household and small commercial examples, but do not certify every combination. The additive derating model is rejected below 30% retained capacity. The generator's actual engine and alternator limits, fuel specification and altitude adaptation govern. No site uprating is credited below 25 °C or at sea level.

Not applicable to current-limited inverter-generator voltage response, VFD or soft-start input harmonics, highly unbalanced split-phase circuits, large constant-power electronic loads, feeder voltage drop, fault protection, motor torque and thermal limits, or medical and other life-safety service. Reduced voltage reduces induction-motor starting torque approximately with voltage squared; passing the dip screen alone does not establish acceleration.

Enforce the selected sequence with suitable controls. Check All together for uncontrolled coincident restarts. Enter fuel points that imply strictly positive idle consumption for the running engine. The two Honda endpoint checks are calibration checks; no withheld measured operating point validates the interpolated or scaled curve. Use the fuel curve within its measured load range and for the actual measured generator. Fuel properties and part-load controls can make the real curve nonlinear.

CO: portable generators outdoors, at least 6.1 m (20 ft) from openings, exhaust directed away, working CO alarms. Back-feed: never use a wall outlet; approved transfer equipment must isolate the utility. Installation work, circuit loading, grounding, bonding and protection belong to a qualified electrician following local rules and manufacturer instructions.

References

  • Cummins Power Generation, T-030 Liquid-Cooled Generator Set Application Manual, A040S369 Issue 9, 02-2015, §§4.2.5.6–4.2.5.8 (starting and sustained voltage dip), printed pp. 45–47; §7.1.9 (sequence), printed p. 260. https://www.cummins.com/sites/default/files/2024-08/t030-Liquid-cooled-gen-set-application-manual.pdf Corrected attachment s11 supersedes the obsolete section label in the author-protected source entry s3.
  • HOMER Energy, HOMER Pro 3.7 Help Manual (2016), printed pp. 347–349; current worked-example page. Attached excerpt s9 is a short manual transcription of the open page, not the original PDF. https://homerenergy.com/products/pro/docs/latest/generator_fuel_curve_intercept_coefficient.html
  • Honda Power Equipment, EU7000iS Specifications, accessed 2026-10-25. Attached excerpt s10 is a short transcription of the manufacturer table. Calibration endpoint reproduction only; no independent predictive validation. https://powerequipment.honda.com/generators/models/eu7000is
  • Champion Power Equipment, 201249 18-kW Home Standby Generator Operator's Manual, 5843-M-OP rev 20251223, High Altitude: 3.5% per 304.8 m and 1% per 5.6 K above 25 °C. These are editable example slopes. https://files.plytix.com/api/v1.1/file/public_files/pim/assets/4f/00/c2/58/58c2004f402f6e6c14d10b32/texts/8a/08/5f/68/685f088a55f01038f8f4be00/201249-OM-english.pdf?dw=1
  • Baldor-Reliance, Company News, locked-rotor current worked example for a 125 hp, 460 V Code G motor; references NEMA MG 1-2011 §10.37.2. https://www.baldor.com/our-profile/news/company-news/detail?id=%7B0585DDBC-9DF7-49BC-A1C3-9BDAE434D06A%7D
  • US Energy Information Administration, US Gasoline and Diesel Retail Prices, annual series, 2025 regular gasoline 3.097 USD/US gal including taxes; accessed 2026-10-25. https://www.eia.gov/dnav/pet/PET_PRI_GND_DCUS_NUS_A.htm
  • CDC, What to Do to Protect Yourself During a Power Outage, generator carbon-monoxide precautions; accessed 2026-10-25. https://www.cdc.gov/natural-disasters/response/what-to-do-protect-yourself-during-a-power-outage.html
  • OSHA, Grounding Requirements for Portable Generators, transfer switch and qualified-electrician guidance; local rules in force govern. https://www.osha.gov/sites/default/files/publications/GROUNDING_PORT_GENERATOR.pdf

Inputs

InputSymbolUnitDefault
Show detailed equipment assumptions
Reveal motor efficiencies, source reactance, derating slopes and replacement assumptions. Hidden fields use the documented defaults.
advancedfalse
Background electrical load
Lights, electronics and resistive loads that are already on. Exclude the three motors below.
P_basekW0.7
Background power factor
Lagging power factor; use 1 for purely resistive loads.
pf_base0.95
Motor 1 rated shaft power
Mechanical nameplate rating, not electrical input watts. Set zero to omit this motor; use manufacturer data for your equipment.
H_1hp0.75
Motor 1 locked-rotor code value
Enter the numeric kVA per horsepower from the nameplate NEMA code-letter band, preferably its upper bound. Default 6.29 is a Code G example. No standard table is reproduced.
K_1kVA/hp6.29
Motor 1 efficiency
Electrical running kW equals rated shaft power divided by efficiency. A planning assumption; replace with nameplate efficiency.
eta_10.8
Motor 1 running power factor
Lagging running power factor from the motor data sheet.
pf_10.8
Motor 2 rated shaft power
Mechanical nameplate rating, not electrical input watts. Set zero to omit this motor; use manufacturer data for your equipment.
H_2hp0.5
Motor 2 locked-rotor code value
Enter the numeric kVA per horsepower from the nameplate NEMA code-letter band, preferably its upper bound. Default 6.29 is a Code G example. No standard table is reproduced.
K_2kVA/hp6.29
Motor 2 efficiency
Electrical running kW equals rated shaft power divided by efficiency. A planning assumption; replace with nameplate efficiency.
eta_20.75
Motor 2 running power factor
Lagging running power factor from the motor data sheet.
pf_20.75
Motor 3 rated shaft power
Mechanical nameplate rating, not electrical input watts. Set zero to omit this motor; use manufacturer data for your equipment.
H_3hp0.25
Motor 3 locked-rotor code value
Enter the numeric kVA per horsepower from the nameplate NEMA code-letter band, preferably its upper bound. Default 6.29 is a Code G example. No standard table is reproduced.
K_3kVA/hp6.29
Motor 3 efficiency
Electrical running kW equals rated shaft power divided by efficiency. A planning assumption; replace with nameplate efficiency.
eta_30.65
Motor 3 running power factor
Lagging running power factor from the motor data sheet.
pf_30.65
Motor start order
A selected order requires enforced load control. Check All together if thermostats or pumps can restart together.
order1 → 2 → 3
Delay between motor starts
Cummins T-030 uses 5–10 s between stabilized load steps. Shorter delays can overlap the entered inrush duration.
gaps5
Motor inrush duration
Rectangular locked-rotor envelope for the animation. Enter measured or manufacturer acceleration time; this does not solve motor acceleration.
t_starts0.8
Locked-rotor power factor
Illustrative lagging starting PF, shared by the three motors. Replace with manufacturer data.
pf_start0.35
Play the start sequence
Press ▶ to see motors switch from starting to running. This is a load-state envelope, not a generator transient waveform.
t_plays1.3
Selected generator continuous rating
Continuous nameplate real-power rating. Do not enter advertised peak watts.
P_genkW6.5
Generator rated power factor
Nameplate kW / kVA. Many home single-phase sets use 1; use the actual rating.
pf_gen1
Supply connection
Split-phase calculations assume balanced legs; individual 120 V circuits need a separate leg-capacity check.
phaseSingle phase / balanced 120–240 V split phase
Nominal line-to-line voltage
For 120/240 V split phase enter 240 V. Motor current assumes all listed motors use this voltage.
V_lineV240
Subtransient reactance on selected generator kVA base
Per-unit reactance is a screening assumption. Convert alternator-base reactance to the selected set base before entering it. Not valid for current-limited inverter generators.
X_pu0.12
Allowed screening voltage dip
Fraction of nominal voltage: 0.15 means 15%. Use the most sensitive connected equipment limit.
dip_limit0.15
Extra capacity above running demand
A fraction: 0.20 adds 20% running reserve. Inrush is checked separately without overload credit.
reserve0.2
Site altitude above sea level
No cold-weather or below-sea-level uprating is credited.
altitudem500
Ambient air temperature
One temperature reading; the unit switch converts this field with the correct offset.
T_air°C35
Fractional power loss per 304.8 m
Default follows the Champion 201249 manual, rev 20251223. Replace for the selected engine.
d_alt0.035
Fractional power loss per 5.6 K above 25 °C
Default follows the Champion 201249 manual. Linear losses are added; alternator site ratings must also be checked.
d_heat0.01
Fuel data reference generator rating
Default data: Honda EU7000iS gasoline, 5.5 kW continuous. The fit is scaled by rating to the selected generator; replace with two points for your actual model.
P_refkW5.5
Lower fuel-test load fraction
A fraction of the reference rating: default quarter load.
f_low0.25
Fuel use at the lower test load
Honda published 5.1 US gal per 16.0 h at quarter load, accessed 2026-10-25.
F_lowL/h1.2065994375
Upper fuel-test load fraction
Default full rated load. Must be greater than the lower test fraction.
f_high1
Fuel use at the upper test load
Honda published 5.1 US gal per 6.4 h at rated load, accessed 2026-10-25.
F_highL/h3.01649859375
Average running demand / all-on demand
Use 1 for continuous all-on demand. This estimates average fuel only; all motors still count fully for sizing.
duty0.8
Usable fuel in tank
Usable liquid fuel, excluding an unusable reserve. Shut down and cool before refueling.
tankL20
Liquid fuel price — 2025 US regular gasoline default
Dated baseline: EIA US regular gasoline annual average for 2025, 3.097 USD/US gal. Edit for local fuel and today’s price. USD/L remains a currency label when units are switched.
fuel_priceUSD/L0.8181412317291917
Generator operating time per outage day
Hours actually running, including idle periods covered by the average-load fraction.
hours_dayh4
Outage days per planning month
Annual estimates use twelve identical planning months.
days_month25
Installed generator cost
Illustrative budget, not a market quote. Include the transfer equipment and installation.
C_genUSD2000
Installed solar + battery cost
Illustrative budget. Enter a quote independently sized to supply the SAME load, outage energy and motor starts. No solar or battery sizing is performed here.
C_solarUSD9000
Generator maintenance per operating hour
Illustrative oil, filters and service allowance.
C_serviceUSD/h0.2
Generator replacement interval
Illustrative service life in operating hours, not calendar time.
L_genh6000
Generator replacement cost
Illustrative future cost, excluding reusable transfer equipment.
C_replaceUSD2000
Battery replacement interval
Illustrative calendar interval; verify cycling and climate effects.
Y_batyear10
Battery replacement cost
Illustrative installed future battery replacement cost.
C_batUSD3000
Solar + battery annual maintenance
Illustrative annual allowance. Replacement costs are separate.
C_solar_omUSD/year100
Cost comparison horizon
Undiscounted costs at constant prices, no grants, export revenue or electricity-bill savings.
horizonyear20

Results

With the default inputs above, the calc gives:

ResultValue
Selected generatorPasses this sizing screen
Minimum continuous nameplate rating5.63 kW
Minimum corresponding nameplate kVA5.63 kVA
All-on running demand2.18 kW
Peak sequenced start demand5.21 kVA
Nameplate capacity retained at site92.5 %
Voltage dip screen — no AVR recovery8 %
Fuel use at average load1.48 L/h
Time per usable tank13.5 h
Fuel cost per planning month121 USD
Solar + battery first cheaper year (conditional)Year 5

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

Calibration: Honda quarter-load fuel and 16 h tank

Source: Calibration endpoint reproduction, not independent predictive validation. Honda EU7000iS Specifications, accessed 2026-10-25: 5500 W rated output, 5.1 US gal tank, 16.0 h at quarter load. Fuel flow is derived from that published tank volume and runtime; these same endpoints calibrate the fit. US gal = 3.78541 L as used by the engine. https://powerequipment.honda.com/generators/models/eu7000is

Inputs: Show detailed equipment assumptions = yes; Background electrical load = 1.375 kW; Motor 1 rated shaft power = 0 hp; Motor 2 rated shaft power = 0 hp; Motor 3 rated shaft power = 0 hp; Average running demand / all-on demand = 1; Selected generator continuous rating = 5.5 kW; Site altitude above sea level = 0 m; Ambient air temperature = 25 °C; Usable fuel in tank = 19.306 L; the others as above.

ResultSourceThis calc
Fuel use at average load1.207 L/h1.207 L/h
Time per usable tank16 h16 h

Calibration: Honda full-load fuel and 6.4 h tank

Source: Calibration endpoint reproduction, not independent predictive validation. Honda EU7000iS Specifications, accessed 2026-10-25: 6.4 h at full rated 5.5 kW from a 5.1 US gal tank. These same endpoints calibrate the fit. This checks fuel calibration only: Honda is an inverter set and the synchronous-alternator voltage-dip screen is not its transient model. https://powerequipment.honda.com/generators/models/eu7000is

Inputs: Show detailed equipment assumptions = yes; Background electrical load = 5.5 kW; Motor 1 rated shaft power = 0 hp; Motor 2 rated shaft power = 0 hp; Motor 3 rated shaft power = 0 hp; Average running demand / all-on demand = 1; Selected generator continuous rating = 5.5 kW; Site altitude above sea level = 0 m; Ambient air temperature = 25 °C; Usable fuel in tank = 19.306 L; the others as above.

ResultSourceThis calc
Fuel use at average load3.016 L/h3.016 L/h
Time per usable tank6.4 h6.4 h

HOMER published worked example: fit coefficients

Source: HOMER Pro 3.7 Help Manual (2016), printed pp. 347–349; the same worked example appears in the linked HOMER Pro fuel-curve page. The published slope 0.273 and intercept coefficient 0.033 are rounded: exact two-point values are 0.2728 and 0.0332. Formulas retain exact input arithmetic. https://homerenergy.com/products/pro/docs/latest/generator_fuel_curve_intercept_coefficient.html

Inputs: Show detailed equipment assumptions = yes; Background electrical load = 25 kW; Motor 1 rated shaft power = 0 hp; Motor 2 rated shaft power = 0 hp; Motor 3 rated shaft power = 0 hp; Average running demand / all-on demand = 1; Selected generator continuous rating = 50 kW; Site altitude above sea level = 0 m; Ambient air temperature = 25 °C; Fuel data reference generator rating = 50 kW; Lower fuel-test load fraction = 0.5; Fuel use at the lower test load = 8.48 L/h; Fuel use at the upper test load = 15.3 L/h; the others as above.

ResultSourceThis calc
Fuel use at average load8.48 L/h8.48 L/h
HOMER marginal fuel consumption coefficient0.273 ± 3 × 10⁻⁴ L/kWh0.2728 L/kWh
HOMER no-load coefficient per rated kW0.033 ± 3 × 10⁻⁴ L/kWh0.0332 L/kWh

Baldor 125 hp Code G upper-end locked-rotor current

Source: Baldor-Reliance company-news worked example: a 125 hp, 460 V, three-phase Code G motor has upper-end locked-rotor current 988 A at 6.3 kVA/hp. The source writes an ungrouped division; this implementation correctly divides by the whole sqrt(3) × voltage denominator. The 6.3 example is used as printed, rather than replacing it with 6.29. https://www.baldor.com/our-profile/news/company-news/detail?id=%7B0585DDBC-9DF7-49BC-A1C3-9BDAE434D06A%7D

Inputs: Show detailed equipment assumptions = yes; Motor 1 rated shaft power = 125 hp; Motor 2 rated shaft power = 0 hp; Motor 3 rated shaft power = 0 hp; Motor 1 locked-rotor code value = 6.3 kVA/hp; Supply connection = Balanced three phase; Nominal line-to-line voltage = 460 V; Selected generator continuous rating = 1,000 kW; the others as above.

ResultSourceThis calc
Motor 1 nominal locked-rotor current988 ± 1 A988.4 A

Related Resources