Heat Pump Buffer Tank, Low-Loss Header & Plate Exchanger Calculator

Compare heat-pump hydraulic layouts, mixing and plate-exchanger temperature penalties, COP and seasonal cost. Size active water volume for minimum run time and defrost.

#buffer tanks #COP #defrost #flow limits #heat pumps #low-loss headers #NTU #plate heat exchangers

A heat pump buffer tank calculator should answer three separate questions: is there enough active water for reliable operation, do the pumps need hydraulic separation, and must the two fluids be isolated? This tool screens those needs and estimates the temperature and electricity penalties of a proposed arrangement. It is for engineers, installers, students and owners comparing a design before commissioning.

Select direct connection, a series buffer, a low-loss header, a four-pipe buffer or a counterflow plate exchanger. Enter the heating duty, the required emitter supply temperature and its supply-to-return drop. The tool calculates the heating-circuit flow. Enter the manufacturer's minimum and maximum flow: direct and series candidates must satisfy both limits at the calculated operating flow and entered valve-closed flow. For a separator or exchanger, also enter the primary flow. The schematic shows the required heat-pump supply and return temperatures. A separate result shows the secondary supply if the heat-pump setting were left at the original emitter target.

Low loss header heat pump efficiency depends on flow balance. When secondary flow exceeds primary flow, cool return water mixes into the heating supply. Maintaining the required emitter temperature then requires hotter heat-pump water. When primary flow exceeds secondary flow, some hot water bypasses to the return. This ideal model predicts no extra leaving-temperature lift in that case; it does not claim that real tanks have no mixing, control or cycling losses.

For plate heat exchanger heat pump flow temperature, enter the supplier's overall conductance, UA, at the intended flows and fluid properties. A counterflow effectiveness–NTU calculation determines the approach temperature. A plate exchanger provides fluid isolation but does not automatically provide the storage or guaranteed flow needed for defrost.

Storage sizing uses minimum stable thermal output, the smallest concurrent load, minimum run time, usable temperature swing, net defrost energy and the manufacturer's connected-volume requirement. Only count water that remains accessible when valves close. The added tank volume allows for an entered usable fraction. A series return buffer adds water without deliberately mixing supply and return; a four-pipe buffer can also separate the pumps.

The COP fit uses two data-sheet points at the same source condition. Replace the illustrative Vaillant points with your equipment data. Enter annual useful heat, baseline seasonal COP, extra pump power, tank loss and your electricity tariff to obtain a conditional annual energy and cost estimate. The tariff is a user scenario, not a current price quotation.

The calculation assumes steady heating, one heat pump and one circuit. It excludes dynamic stratification, short-cycle losses, detailed defrost control and emitter response. With two circuits at different temperatures, analyse each branch and its controls separately. Check available pump head, approved layouts and the exact manufacturer's instructions. Installation and commissioning belong to a qualified person.

How it is calculated

1. Flow and adiabatic mixing

The equations below are derived here from conservation of mass and energy. The heating-circuit capacity rate is Cs=Q/ΔTsC_s=Q/\Delta T_s, and the primary rate is Cp=ρcpV˙pC_p=\rho c_p\dot V_p. Direct and series arrangements have one common flow. A low-loss header and an ideal four-pipe buffer share the same steady separator balance.

For the same liquid, let r=Cp/Csr=C_p/C_s. If r<1r<1, the secondary supply is Ts,out=Tr+r(Tp,in−Tr)T_{s,out}=T_r+r(T_{p,in}-T_r). To maintain the emitter target, the heat pump must therefore supply an extra ΔTmix=max⁡(Q/Cp−ΔTs,0)\Delta T_{mix}=\max(Q/C_p-\Delta T_s,0). If r>1r>1, the secondary supply equals the primary supply, while bypass raises the primary return: Tp,out=Tp,in−Q/CpT_{p,out}=T_{p,in}-Q/C_p. Caleffi idronics 15, pp.40–42 gives published supply- and return-mixing examples; both are reference checks here.

Direct and series assessments require both the calculated common operating flow and the entered valve-closed flow to be inside the manufacturer's minimum–maximum window. Separated layouts apply the window to primary flow. The direct annual-energy baseline is flagged as hypothetical if its calculated flow is outside that window. At the illustrative 4.5 kW / 5 K default, common water flow is approximately 0.775 m³/h.

The unchanged-setting result holds secondary return fixed and leaves the heat-pump setting at the original emitter target. It illustrates under-temperature; it is not an emitter or building response simulation.

2. Counterflow plate exchanger

Cmin=min⁡(Cp,Cs)C_{min}=\min(C_p,C_s), Cr=Cmin/CmaxC_r=C_{min}/C_{max} and NTU=UA/CminNTU=UA/C_{min}. Integrating the two stream energy balances gives

ε=1−e−NTU(1−Cr)1−Cre−NTU(1−Cr).\varepsilon=\frac{1-e^{-NTU(1-C_r)}}{1-C_r e^{-NTU(1-C_r)}}.

At equal capacity rates use ε=NTU/(1+NTU)\varepsilon=NTU/(1+NTU). The required hot inlet is Tr+Q/(εCmin)T_r+Q/(\varepsilon C_{min}). Its excess above emitter supply is the hot-end approach. The cold-end approach is also calculated. As a conservation cross-check, Q=UA LMTDQ=UA\,LMTD, using the logarithmic mean of the two end differences. Caleffi idronics 29 section 4 supplies the LMTD method and a published temperature example. UA must come from supplier selection at the actual flows, fluids and fouling condition.

For numerical evaluation, let D=1−CrD=1-C_r and z=e−NTUDz=e^{-NTU D}. The larger end approach is G=(Q/Cmin)D/(1−z)G=(Q/C_{min})D/(1-z) and the smaller is g=Gzg=Gz. The code evaluates 1−z1-z with expm1. The hot-end approach is G when the primary is the smaller capacity stream, and g otherwise; the cold end is the other approach. At equal capacity rates both are Q/UA. This avoids subtracting nearly equal inlet/outlet differences. Separate logarithms evaluate the LMTD without overflowing an approach ratio. If the exponential underflows to zero, the LMTD, reconstructed duty and residual are intentionally unavailable, with an explanation, rather than reporting zero duty. The conservation residual is rounded to 12 decimal places only to remove floating-point subtraction noise.

3. COP and seasonal electricity

Fit inverse COP linearly between two same-source data-sheet points:

b=1/COP2−1/COP1T2−T1,COP(T)=11/COP1+b(T−T1).b=\frac{1/COP_2-1/COP_1}{T_2-T_1},\quad COP(T)=\frac{1}{1/COP_1+b(T-T_1)}.

The extra heat-pump electricity multiplier is F=COP(Ts)/COP(Ts+ΔT)F=COP(T_s)/COP(T_s+\Delta T). The default A7/W35 and A7/W55 points are from Vaillant 0020330791_03 p.46, VWL 55/6 A S2. The unused A7/W45 point checks interpolation; the 1.8% discrepancy is documented in that reference case. The interval between the two calibration temperatures is enforced.

For annual useful heat HH and baseline seasonal COP SS, temperature lift adds (H/S)(F−1)(H/S)(F-1) electricity. Unrecovered tank heat adds PlosshlossF/SP_{loss}h_{loss}F/S; net additional pumps add PpumphpumpP_{pump}h_{pump}. The sum times the entered tariff gives additional cost. Watts and hours are explicitly converted to kWh. The seasonal ratio is a screening approximation, not a measured or weather-bin seasonal performance factor.

4. Active volume

Using volumetric fluid heat capacity cvc_v:

Vcycle=max⁡(Pmin−Qlow,0)tmincvΔTstore,Vdefrost=EdefcvΔTdef.V_{cycle}=\frac{\max(P_{min}-Q_{low},0)t_{min}}{c_v\Delta T_{store}},\qquad V_{defrost}=\frac{E_{def}}{c_v\Delta T_{def}}.

The governing effective volume is the largest of cycling, defrost and the manufacturer's minimum. Credit existing guaranteed active volume, then divide any shortfall by the usable fraction of the new tank. These constraints are maxima, not additive simultaneous events. Caleffi idronics 17 p.28 distinguishes on/off output from minimum stable modulating output. Manufacturer minimum volume and guaranteed flow remain separate requirements.

Assumptions

  • Steady heating, one heat pump and one heating circuit. Water on the secondary side; constant ρcp=4.18\rho c_p=4.18 MJ/(m³·K), approximated from 1,000 kg/m³ and 4.18 kJ/(kg·K). For an isolated primary circuit, enter its own volumetric heat capacity; storage then uses that primary fluid.
  • A header or four-pipe buffer has ideal mixing at its connections, no axial conduction, and no dynamic stratification. A series buffer is in the return and has no deliberate supply mixing. Direct and series flow equals heating-circuit flow.
  • The two COP points share one source condition and compatible test settings. Actual COP also depends on return temperature, compressor speed, defrost and auxiliaries; those effects are not resolved.
  • The baseline seasonal COP is entered separately. The representative fixed-condition electricity multiplier is applied to the entire entered annual space heat. Do not include extra pumps twice if using measured baseline data.
  • Run time 10 min, defrost extraction 0.30 kWh, allowable drops 5 K, usable fraction 0.90, extra pump 35 W and tank heat loss 25 W are illustrative design assumptions, not equipment ratings.
  • Vaillant defaults illustrate the 2023 VWL 55/6 A S2 manual: 400–860 L/h flow range and 40 L connected volume with the back-up heater deactivated. Replace them for the exact model, back-up-heater setting and installation. Connected volume is conservatively treated as effective volume.
  • Fluid isolation and independent-flow requirements are design inputs. The arrangement recommendation assesses the entered minimum and maximum flow limits, and assumes approved layouts, sufficient heat-pump thermal capacity and adequate pump head; these are not calculated.

Where it applies

Use for preliminary hydraulic comparison and active-volume sizing. Installation and commissioning belong to a qualified person following the manufacturer's instructions and applicable local rules.

The COP calculation is restricted to the two entered calibration temperatures. The 2023 manual is an illustrative data source, not a declaration that those requirements apply to newer products. Enter a user tariff in any currency; the default 0.30 per kWh is an illustrative scenario dated 27 October 2026, not a current quoted price.

This steady model omits cycling savings, storage charging temperatures, real tank stratification, pressure-drop selection, control hysteresis details, capacity limits, fouling evolution and dynamic defrost. It gives no extra leaving-temperature lift for primary flow above secondary flow; higher return temperatures can still affect real COP. Fraunhofer ISE WP-QS (2025), p.9, reports that actual storage temperature differences depend on flows, connection arrangement and dynamic operation, supporting this distinction between an ideal balance and field performance.

Count only water accessible during the relevant valve state; secondary water behind a plate exchanger is not automatically available for defrost. Net defrost energy must include concurrent loads and account for auxiliary heat only when guaranteed. Verify the minimum final water temperature, primary flow during defrost and available pump head separately. A non-representable exchanger approach at extreme NTU makes the LMTD cross-check unavailable; use suitable supplier software or higher-precision arithmetic to verify that case.

With two heating circuits, a common-temperature system can be reduced to combined capacity rates, but circuits with different supply temperatures need separate branch balances and mixing controls. This tool does not model them. No domestic hot-water hygiene, refrigerant safety or regulatory compliance sizing is performed.

References

  • Caleffi, idronics 15 (2014), Separation in hydronic systems, pp.40–42. https://www.caleffi.com/sites/default/files/media/external-file/Idronics_15_NA_Separation%20in%20hydronic%20systems.pdf
  • Caleffi, idronics 17 (2015), Thermal storage in hydronic systems, p.28, Formulae 6-1 and 6-2. https://www.caleffi.com/sites/default/files/media/external-file/Idronics_17_NA_Thermal%20storage%20in%20hydronic%20systems.pdf
  • Caleffi, idronics 29 (2021), section 4, Thermal characteristics of heat exchangers, LMTD and effectiveness methods. https://www.caleffi.com/en-us/blog/4-thermal-characteristics-heat-exchangers
  • Vaillant, aroTHERM plus operating, installation and maintenance instructions 0020330791_03, 6 November 2023, pp.30, 45–47. https://www.vaillant.co.uk/product-images/0020330791-03.pdf.pdf
  • Fraunhofer ISE, WP-QS im Bestand final report (2025), p.9 and section 6.4, measured storage temperatures and operating conditions. https://www.ise.fraunhofer.de/content/dam/ise/de/documents/projekte/WP-QS_Schlussbericht.pdf

Inputs

InputSymbolUnitDefault
Arrangement to evaluate
Choose a proposed arrangement. The recommendation below independently screens the need for storage, hydraulic separation and fluid isolation.
layoutLow-loss header
Fluid or pressure isolation is required
For incompatible water chemistry, separated pressure zones or an engineered glycol circuit. A header or buffer does not isolate fluids.
isolationfalse
Independent primary and heating-circuit flows are required
Set after checking pump head, zone closures and the manufacturer's approved hydraulic layouts. A series vessel alone cannot guarantee flow.
independentfalse
Heat delivered to the heating circuit
Steady heating duty at the selected supply temperature and circuit temperature drop. The illustrative 4.5 kW / 5 K default keeps a direct or series water flow below 860 L/h.
Q_heatkW4.5
Required heating-circuit supply temperature
Emitter supply temperature after the separator or exchanger.
T_flow°C40
Heating-circuit supply-to-return drop
A temperature difference, not a return-temperature reading.
dT_emitK5
Primary volume flow
Measured or design heat-pump flow. In direct and series arrangements the primary flow equals the calculated heating-circuit flow.
v_primarym^3/h0.6
Primary fluid volumetric heat capacity
Water is approximately 4.18. For glycol enter density × specific heat at operating temperature from the fluid supplier.
cv_glycolMJ/(m^3*K)4.18
Exchanger overall conductance, UA
Use the supplier's duty-specific UA including fouling allowance; not a guessed plate count. UA changes with flow and glycol.
UA_hxkW/K3
Manufacturer minimum heat-pump flow
Illustrative Vaillant VWL 55/6 A S2 value: 400 L/h, manual p.46. Replace with your model's requirement.
v_minm^3/h0.4
Manufacturer maximum heat-pump flow
Illustrative VWL 55/6 A S2 maximum: 860 L/h, Vaillant 0020330791_03 p.46. Replace for your model and operating condition.
v_maxm^3/h0.86
Guaranteed circuit flow with zones closed
Flow that can always pass through the heat pump in a direct or series system; check the worst valve state and available pump head.
v_availablem^3/h0.6
Minimum stable heat-pump thermal output
Use output at the mild-weather cycling condition. For an on/off heat pump, use its full output. Illustrative VWL 55/6 A7/W35 minimum: 2.1 kW.
P_minkW2.1
Concurrent load during the minimum run
Smallest load actually taking heat while the heat pump runs; independent of the steady design duty above.
Q_lowkW0.8
Manufacturer / design minimum run time
10 minutes is a planning assumption, not a universal manufacturer requirement.
t_minmin10
Usable control temperature swing
Effective change of average active water temperature during charging. Control hysteresis and sensor location determine this.
dT_storeK5
Net energy drawn from water per defrost
Illustrative 0.30 kWh: replace with manufacturer or measured water-side energy per defrost, including concurrent loads. Credit auxiliary heat only when guaranteed. Zero disables this energy check.
E_defkWh0.3
Permitted water cooling during defrost
Use the manufacturer's allowable water-temperature fall. This does not check the final minimum water temperature.
dT_defK5
Existing guaranteed active water volume
Only count volume that remains connected and thermally accessible during cycling AND defrost. With a plate exchanger count the primary side only; exclude isolated emitters.
V_liveL40
Manufacturer minimum connected volume
Illustrative VWL 55/6 A S2, back-up heater deactivated: 40 L, p.46. Enabled back-up heater has a different requirement. Follow the exact model manual.
V_manualL40
Usable fraction of the added tank
0.9 is a sizing assumption for incomplete utilisation; use evidence from the tank layout and sensor arrangement. Existing active volume is already effective.
f_use0.9
Low-temperature COP data point
Both COP points must use the same source temperature and compatible test conditions. Defaults are Vaillant VWL 55/6 A S2 at A7.
T_cop1°C35
COP at the low-temperature point
Manual 0020330791_03 p.46: A7/W35 COP 4.80. Enter your heat pump's data.
COP_14.8
High-temperature COP data point
Default second point: A7/W55. Fit validity is the interval between these temperatures.
T_cop2°C55
COP at the high-temperature point
Manual p.46: A7/W55 COP 2.80. Source condition must match the first point.
COP_22.8
Baseline seasonal heat-pump COP
User scenario for the direct system before added hydraulics. The fitted point-COP ratio adjusts this estimate; it is not a bin-based seasonal simulation.
COP_season3.5
Annual useful space heat
Annual heat delivered to emitters, excluding domestic hot water and any additional tank heat loss.
H_seasonkWh12000
Net additional circulating-pump electrical power
Enter the change from the direct baseline, including primary pump changes and any secondary pump. Use measured power or hydraulic power ÷ wire-to-water efficiency.
P_pumpW35
Annual hours of additional pumping
Include off-cycle circulation if it occurs.
h_pumph3000
Unrecovered tank heat loss
Use a declared loss adjusted to actual temperature; count only heat that does not usefully heat the building. Primary return series tank assumed.
P_lossW25
Annual hours at the stated tank loss
Hours with the tank at its stated heat-loss condition.
h_lossh4000
Electricity price per kWh (your currency)
User-entered tariff, not a market price; default is an illustrative scenario dated 27 October 2026. Annual cost uses the same currency.
tariff0.3

Results

With the default inputs above, the calc gives:

ResultValue
Requirements-based arrangementSeries return buffer: add active volume while retaining one circuit.
Required heat-pump supply41.46 °C
Extra supply temperature1.46 K
Heating supply if HP setting is unchanged38.87 °C
Point COP reduction (%)4.23
Estimated annual extra electricity257 kWh
Estimated annual extra cost (your currency)76.99
Minimum added nominal tank volume13 L
Active storage requirementAdd the displayed nominal volume in a guaranteed active path. A header or plate exchanger alone adds no useful storage.
Flow assessmentPrimary operating flow is within the manufacturer limits. Confirm guaranteed circulation and available pump head.

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

Caleffi separator: 25 gpm secondary, 10 gpm primary

Source: Caleffi idronics 15 (2014), pp.40–41, Formula 6-2 worked example: 160 °F primary supply, 120 °F return, 25/10 US gpm, mixed supply 136 °F. Reconstructed at the published mixed emitter target; Q is the published secondary flow × assumed water heat capacity × 16 °F. COP settings are test-only and are not being validated.

Inputs: Required heating-circuit supply temperature = 57.778 °C; Heating-circuit supply-to-return drop = 8.889 K; Heat delivered to the heating circuit = 58.604 kW; Primary volume flow = 2.271 m³/h; High-temperature COP data point = 80 °C; the others as above.

ResultSourceThis calc
Required heat-pump supply through a mixing separator71.111 °C71.111 °C
Heat-pump return through a mixing separator48.889 °C48.889 °C

Caleffi separator: 15 gpm primary, 10 gpm secondary

Source: Caleffi idronics 15 (2014), pp.41–42: 170 °F supply, 100 °F return, 15/10 US gpm, published primary return 123.3 °F. Exact mixing gives 123.333… °F; tolerance allows the published rounding. Test validates hydraulics only, at boiler temperatures.

Inputs: Required heating-circuit supply temperature = 76.667 °C; Heating-circuit supply-to-return drop = 38.889 K; Heat delivered to the heating circuit = 102.6 kW; Primary volume flow = 3.407 m³/h; High-temperature COP data point = 90 °C; the others as above.

ResultSourceThis calc
Heat-pump return through a mixing separator50.722 °C50.741 °C
Required heat-pump supply through a mixing separator76.667 °C76.667 °C
Supply lift required by ideal separator mixing0 ± 1 × 10⁻⁶ K0 K

Caleffi minimum run-time example: 45.5 US gallons

Source: Caleffi idronics 17 (2015), p.28, first Formula 6-1 worked example: 48,000 Btu/h heat source, 2,500 Btu/h load, 10 min, 20 °F swing → 45.5 US gallons. The small tolerance includes their rounded 500 water factor versus explicit SI heat capacity; formulas are not fitted to this result.

Inputs: Arrangement to evaluate = Series buffer / volumiser; Minimum stable heat-pump thermal output = 14.067 kW; Concurrent load during the minimum run = 0.7327 kW; Usable control temperature swing = 11.111 K; Net energy drawn from water per defrost = 0 kWh; Manufacturer minimum connected volume = 0 L; Existing guaranteed active water volume = 0 L; Usable fraction of the added tank = 1; the others as above.

ResultSourceThis calc
Effective volume required for minimum run time172.2 ± 0.5 L172.3 L
Minimum added nominal tank volume172.2 ± 0.5 L172.3 L

Caleffi counterflow LMTD example: 40.3 °F difference

Source: Caleffi idronics 29 (2021), section 4, Formula 4-3 example, https://www.caleffi.com/en-us/blog/4-thermal-characteristics-heat-exchangers : hot 122→104 °F, cold 68→77 °F; published LMTD = 40.3 °F difference (22.3889 K). UA is 6 kW divided by that published LMTD and flow ratio is fixed by the published stream temperature changes. The inverse NTU calculation must recover the published end temperatures within their rounding. COP inputs are test-only.

Inputs: Arrangement to evaluate = Counterflow plate exchanger; Required heating-circuit supply temperature = 25 °C; Heat delivered to the heating circuit = 6 kW; Primary volume flow = 0.5167 m³/h; Exchanger overall conductance, UA = 0.268 kW/K; Low-temperature COP data point = 20 °C; the others as above.

ResultSourceThis calc
Required heat-pump supply through the plate exchanger50 °C49.982 °C
Heat-pump return through the plate exchanger40 °C39.982 °C
Plate exchanger log mean temperature difference22.389 K22.389 K

COP fit held-out A7/W45 point

Source: Vaillant 0020330791_03 (2023), p.46, VWL 55/6 A S2 at A7/W45: COP 3.60. This intermediate point is NOT used in the two-point fit (W35 4.80 and W55 2.80). The fit predicts 3.537, about 1.8% below the held-out point; 0.08 absolute tolerance documents this empirical model error.

Inputs: Arrangement to evaluate = Direct connection; Required heating-circuit supply temperature = 45 °C; the others as above.

ResultSourceThis calc
Fitted COP at the emitter supply temperature3.6 ± 0.083.537

Direct: 1 kW at 5 K fails minimum flow

Source: Independent review regression, checked against Vaillant 0020330791_03 p.46: at 1 kW and a 5 K water drop the calculated common flow is about 172 L/h, below the 400 L/h minimum even with 600 L/h guaranteed valve-closed flow. Both condition and direct-layout eligibility must fail.

Inputs: Arrangement to evaluate = Direct connection; Heat delivered to the heating circuit = 1 kW; Existing guaranteed active water volume = 60 L; the others as above.

ResultSourceThis calc
Selected layout passes minimum-flow assessment00
Direct or series flow eligibility00

Series buffer cannot cure deficient common operating flow

Source: Independent review regression. Vaillant 0020330791_03 p.46 requires 400 L/h minimum. Adding a series vessel changes active volume, but the same calculated 172 L/h operating flow still passes through the heat pump.

Inputs: Arrangement to evaluate = Series buffer / volumiser; Heat delivered to the heating circuit = 1 kW; Existing guaranteed active water volume = 60 L; the others as above.

ResultSourceThis calc
Selected layout passes minimum-flow assessment00
Direct or series flow eligibility00

Old 6 kW / 5 K common-flow default exceeds manual maximum

Source: Independent review regression against the VWL 55/6 A S2 maximum 860 L/h in Vaillant manual 0020330791_03 p.46. The old 6 kW / 5 K design requires about 1033 L/h; direct and series layouts are not candidates without changing flow or temperature drop.

Inputs: Arrangement to evaluate = Direct connection; Heat delivered to the heating circuit = 6 kW; the others as above.

ResultSourceThis calc
Direct or series flow eligibility00
Selected layout passes maximum-flow assessment00

Adequate operating flow does not excuse deficient valve-closed flow

Source: Flow-guarantee regression against the 400 L/h minimum in Vaillant 0020330791_03 p.46. The operating flow is acceptable but the entered 200 L/h valve-closed flow is not.

Inputs: Arrangement to evaluate = Direct connection; Guaranteed circuit flow with zones closed = 0.2 m³/h; Existing guaranteed active water volume = 60 L; the others as above.

ResultSourceThis calc
Selected layout passes minimum-flow assessment00
Direct or series flow eligibility00

Hydraulically separated primary must also respect maximum flow

Source: Maximum-flow regression against the VWL 55/6 A S2 limit of 860 L/h in Vaillant 0020330791_03 p.46. A header does not permit 1200 L/h through this heat pump.

Inputs: Primary volume flow = 1.2 m³/h; the others as above.

ResultSourceThis calc
Selected layout passes maximum-flow assessment00

Series layout checks the upper limit in the valve-closed state

Source: Flow-window regression against Vaillant 0020330791_03 p.46: a stated valve-closed flow of 1000 L/h exceeds the 860 L/h maximum, even though the calculated normal flow is acceptable.

Inputs: Arrangement to evaluate = Series buffer / volumiser; Guaranteed circuit flow with zones closed = 1 m³/h; Existing guaranteed active water volume = 60 L; the others as above.

ResultSourceThis calc
Selected layout passes maximum-flow assessment00
Direct or series flow eligibility00

Revised illustrative common flow is inside both manual limits

Source: Positive flow-window regression against the 400–860 L/h range in Vaillant 0020330791_03 p.46. The revised illustrative operating flow is about 775 L/h and valve-closed flow is 600 L/h; both are within the manual range.

Inputs: Arrangement to evaluate = Direct connection; Existing guaranteed active water volume = 60 L; the others as above.

ResultSourceThis calc
Selected layout passes minimum-flow assessment11
Selected layout passes maximum-flow assessment11
Direct or series flow eligibility11

Related Resources