EV Wallbox Cable Size & Load Management: 11 kW vs 22 kW

Compare 11 kW and 22 kW wallboxes, house connection headroom and load management. Check copper feeder voltage drop, entered ampacity and German installation requirements.

#§14a EnWG #cable sizing #DIN VDE 0100-722:2019-06 #load management #NAV §19 #RCD #voltage drop #wallbox

An EV wallbox adds a sustained load to a house connection. This EV charger circuit size calculator helps engineers, students and installers compare 11 kW and 22 kW charging, estimate available connection capacity, and check a proposed copper feeder before detailed installation design. It covers balanced three-phase AC wallboxes on a nominal 400 V supply.

Start with the wallbox rating, number of simultaneous charging vehicles and the vehicle's onboard AC current limit. An 11 kW vehicle cannot use the extra capacity of a 22 kW wallbox. Enter the usable connection current and the design peak of other loads on the busiest phase. Use the continuous rating allowed by the complete connection, including the meter and upstream wiring.

Choose no load management, a static shared current cap, or dynamic allocation. Static management reserves a fixed EV budget and must accommodate the design peak of other loads. Dynamic management uses the present load snapshot; a real controller must measure all phases continuously. Available current is divided equally between the modelled vehicles. If the share falls below 6 A, the model pauses all of them rather than assuming unsupported low-current charging. Vehicle sequencing and phase switching are outside this model.

For the feeder, select a copper conductor size, enter the one-way route length and set the remaining voltage-drop budget after upstream circuits. The tool shows drop and conductor loss at the full wallbox rating, even when load management reduces present demand. It also identifies the smallest listed cross section that meets the voltage-drop budget. This is a voltage-drop candidate, not a complete cable recommendation.

Enter the corrected ampacity established for your actual installation and choose the branch breaker rating. The illustrative ampacity default is not tied to the selected cable. Recheck it whenever the cable or installation changes. This distinction answers the common “Wallbox Kabelquerschnitt” question: route length alone cannot establish a safe cross section. The comparison table helps resolve “Wallbox 11 kW oder 22 kW” by showing both alternatives under the same connection and vehicle limits.

German regulatory guidance is checked as of 25 October 2026. Notify the grid operator before commissioning every EV charger; prior consent is required when total installed charger nameplate rating exceeds 12 kVA under NAV §19. New private low-voltage wallboxes above 4.2 kW fall under §14a EnWG rules from 1 January 2024. Local load management does not replace that grid-control obligation.

RCD guidance follows DIN VDE 0100-722:2019-06 and the DKE's 2025 FAQ: suitable 30 mA Type A protection with certified 6 mA DC disconnection, or suitable Type B protection when that DC function is absent. Check against the standard in force and the equipment instructions. Installation, protective-device selection, fault protection and commissioning belong to a qualified electrician. This calculator does not design earthing, short-circuit protection, public charging, single-phase charging or US NEC installations.

How it is calculated

Balanced three-phase AC input is P=3ULLIP=\sqrt{3}U_{LL}I at unity power factor. ABB's 11 kW and 22 kW wallbox classes use 16 A and 32 A per phase. Their rounded nameplate classes are used for NAV screening; physical power is calculated at the entered voltage.

Connection headroom is Ih=Imain−Iother−IreserveI_h=I_{main}-I_{other}-I_{reserve} on the busiest phase. Without load management the bank demands all vehicle-limited branch currents. Static control divides a fixed bank cap between vehicles; check that cap against the design peak of other loads. The static-cap safety screen limits possible bank demand to the smaller of the cap and installed wallbox hardware capacity; it does not rely on the vehicles' present current limits. Dynamic control uses the entered present snapshot of other loads. Equal sharing gives Ishare=min⁡(Irated,Icar,Ibank/N)I_{share}=\min(I_{rated},I_{car},I_{bank}/N). Below 6 A per vehicle, all modelled chargers pause. Schneider Electric's load-management guide defines the two control methods; its commissioning guide documents the IEC 61851 minimum of 6 A. The dynamic chart uses exact full-current and 6 A pause thresholds. Its repeated pause coordinate draws a vertical drop to zero; below-minimum charging powers are not interpolated across that transition. A negative other-load threshold means that operating region is already unavailable with no other loads. A real controller must measure each phase and handle communications loss safely.

For each separate final circuit, class 2 plain copper resistance at 20 °C comes from the platform wires.metric data (IEC 60228:2004). Candidate resistance data come from manufacturer Damai, NYY 1. Copper temperature correction is Rθ=R20(1+0.00393ΔT)R_\theta=R_{20}(1+0.00393\Delta T), consistent with the platform copper material data (IEC 60028). Damai's independently published 70 °C values provide checks. With one-way length in kilometres, ΔULL=3IRθL\Delta U_{LL}=\sqrt{3}I R_\theta L and Ploss=3I2RθLP_{loss}=3I^2R_\theta L. These are the unity-PF, negligible-reactance form of Schneider Electric's voltage-drop equations.

Full-rating cable checks always use wallbox rated current, independently of the present vehicle limit and load management. The selected cable must meet the entered feeder drop budget, and the entered protection must satisfy Ib≤In≤IzI_b\le I_n\le I_z. The smallest listed section meeting voltage drop alone is shown separately. Its thermal suitability is not inferred from resistance.

DIN VDE 0100-722:2019-06, interpreted in DKE's 3 December 2025 FAQ, requires suitable additional RCD protection ≤30 mA per connection point. The concept shown is Type A with certified 6 mA DC disconnection (e.g. RDC-DD to IEC 62955), or Type B when that function is absent. An integrated DC sensor does not by itself replace an RCD. Coordinate upstream RCDs and follow manufacturer instructions.

Verification also checks the line-to-line drop independently as the magnitude of the difference of two phase-conductor drop phasors separated by 120°, and checks that feeder Joule loss equals the three-phase power associated with the in-phase voltage drop.

Assumptions

  • All modelled wallboxes and vehicles are identical, three-phase and balanced, at approximately unity power factor; other loads are represented conservatively by current on the busiest phase. No household diversity factor is invented.
  • Each wallbox has a separate final circuit of the same length and copper size. The number entered is the simultaneous group; include the nameplate ratings of all additional installed chargers under “other installed chargers”, even when idle.
  • Resistive voltage drop and phase-conductor Joule loss only; negligible neutral current, cable reactance, harmonics and AC skin/proximity effects. Values are AC input at the distribution board, not DC battery power.
  • Temperature rise 0–50 K corresponds to 20–70 °C copper. The default is 70 °C. Ambient temperature and grouping affect ampacity separately.
  • The 3% remaining drop budget, 5 A reserve and 32 A corrected ampacity are illustrative design inputs, not standard limits or an ampacity determination. Re-enter corrected ampacity after changing cable or installation. A passing screen relies on that entered value.
  • Dynamic allocation is an instantaneous equal-share calculation, not a daily energy forecast. No vehicle sequencing, automatic phase switching, PV surplus, battery storage, charging-time prediction or grid curtailment simulation is included.
  • Core equations are derived from balanced power, Ohm's law and Joule heating; published sources support the application, component ratings and reference values.

Where it applies

Planning tool for new private balanced three-phase AC wallbox installations, nominally 400 V, 11 or 22 kW per point; copper class 2 conductors, listed sizes 1.5–35 mm², 20–70 °C. The simplified full-rating drop must remain at or below 10%; larger calculated drops block result cards and require a revised cable study. Longer or unusual routes require a complete impedance model. A zero available charging current means paused operation.

Germany: rules checked 25 October 2026. NAV §19 requires notification before commissioning every EV charging installation, not only above 3.6 kVA. Prior consent is required when total installed charger nameplate apparent power exceeds 12 kVA per electrical installation. This tool conservatively screens nameplate sum without treating a user-entered local cap as an exemption; agree any permanently restricted connection rating with the operator. DKE FAQ s1 page 3, question 5 also confirms notification and the 12 kVA threshold. Local operator technical connection conditions still apply.

For new private low-voltage wallboxes above 4.2 kW commissioned from 1 January 2024, §14a EnWG participation and grid-oriented controllability apply. The regulator describes a 4.2 kW minimum for direct control during a grid constraint; multiple-device EMS allocation has separate rules and is not calculated here. Local static/dynamic load management is a separate function. Older installations, exceptions, public charging and non-German rules require their own review.

Installation work and commissioning belong to a qualified electrician. Check against the standard in force. This screen does not establish compliance or select a final cable/protection system. Verify installation-method ampacity, ambient/grouping derating, continuous meter capacity, PE/neutral sizing, earthing, disconnection times, fault-loop impedance, short-circuit withstand, breaker curve/breaking capacity, RCD coordination and surge protection. No NEC 125% sizing rule or US installation approval is implied by the US unit display. Schematic and cable-candidate text retain nominal SI labels; numeric fields and charts use the catalog unit switch.

References

  • ABB Terra AC wallbox product information — 11 kW / 16 A and 22 kW / 32 A three-phase ratings: https://wallbox.de.abb.com/produktinfos/
  • Schneider Electric, Electrical Installation Guide — static/dynamic load management and the 10 × 22 kVA / 100 kVA static example: https://www.electrical-installation.org/enwiki/EV_charging_-_energy_and_asset_management
  • Schneider Electric, Calculation of voltage drop in steady load conditions — balanced three-phase method: https://www.electrical-installation.org/enwiki/Calculation_of_voltage_drop_in_steady_load_conditions
  • Schneider Electric, eMobility Infrastructure Commissioning Guide, Setting Energy Management — IEC 61851 minimum 6 A: https://productinfo.se.com/emobility-infrastructure-commissioning/evsolcg001-emobility-infrastructure-commissioning-guide/English/BM_EVSOLCG001EN_eMobility_Infrastructure_Commissioning_Guide_DD01016549.xml/%24/EVSOLCG001EN_EV_SetEnergyManagement_DD01037747
  • PT Damai Cable Indonesia, NYY 1 — resistance values at 20 and 70 °C: https://damaicable.com/nyy-1/
  • DKE, FAQ for DIN VDE 0100-722:2019-06, published 3 December 2025, PDF page 3 (attached s1): https://www.dke.de/resource/blob/2245432/a4948f97c5acd6f3e44362220e93591b/erlaeuterungen-als-pdf-download-data.pdf
  • Federal German law, NAV §19, current text checked 25 October 2026: https://www.gesetze-im-internet.de/nav/__19.html
  • Bundesnetzagentur, private wallboxes and §14a EnWG, checked 25 October 2026: https://www.bundesnetzagentur.de/DE/Vportal/Energie/E_Mobilitaet/artikel.html
  • Hager, RCD selection and 6 mA DC detection, Type B upstream coordination: https://hager.com/de/loesungen/energieverteilung/fehlerstromschutzschalter
  • Platform reference data: wires.metric, IEC 60228:2004 class 2 copper conductor resistance; materials.metals, IEC 60028 copper coefficient. Only scalar material/conductor data are used; no standards tables or figures are reproduced.

Inputs

InputSymbolUnitDefault
Wallbox nameplate rating
Balanced three-phase AC charging. Nameplate rating is used for German registration screening.
rating11 kW — 16 A per phase
Identical wallboxes charging simultaneously
All are installed in this electrical installation and share the EV current budget equally. Each has its own final circuit.
N_ev1
Vehicle AC current limit per phase
Use 16 A for an 11 kW three-phase onboard charger. All vehicles are assumed identical and balanced.
I_carA32
Certified 6 mA DC detection and disconnection
Select only if the charger manufacturer confirms suitable DC residual-current protection, e.g. an RDC-DD to IEC 62955. A DC sensor alone is insufficient.
dc_detectiontrue
Supply line-to-line voltageU_llV400
Usable house connection current per phase
Use the lowest permitted continuous current of the service, meter, upstream cable and agreed connection capacity, not just the service fuse marking.
I_mainA63
Other loads: design peak on the busiest phase
Exclude the wallboxes modelled here. Include all other loads and existing chargers; do not convert an unbalanced household kW total into a balanced current.
I_peakA32
Connection current reserve per phase
Engineering allowance for measurement error and controller response. This reserve is not a regulatory percentage.
I_reserveA5
Local load management
None uses the vehicle-limited bank demand. Static applies a fixed shared cap. Dynamic tracks remaining connection headroom. Local control does not replace grid-oriented control under section 14a EnWG.
managementDynamic cap
Other loads now: busiest phase
A snapshot for the dynamic calculation. A real controller must continuously measure every phase and fail safely.
I_nowA20
Static EV bank current cap per phase
Shared cap for all modelled wallboxes. The safety screen uses the smaller of this cap and the installed bank's hardware current, without relying on present vehicle limits.
I_staticA32
Selected copper feeder conductor
Class 2 plain copper. Resistance comes from the platform conductor data. The candidate size is checked for voltage drop only; verify thermal capacity separately.
wire6 mm²
One-way cable route length
Distribution board to wallbox. Do not double this length for a balanced three-phase circuit.
L_runm25
Conductor temperature rise above 20 °C
50 K means a conductor temperature of 70 °C, the conservative design temperature used here for PVC cable. This is conductor temperature, not ambient temperature.
dT_cuK50
Remaining voltage-drop budget for this feeder
Enter the share remaining after upstream voltage drop. The 3% default is a design choice, not a universal VDE limit.
drop_budget%3
Chosen branch breaker rated current
Must be at least the full wallbox branch design current and no greater than corrected cable ampacity. Choose type, curve, poles and breaking capacity from manufacturer instructions and fault calculations.
I_breakerA20
Corrected ampacity of the selected cable
Enter a value verified for the selected cross section, installation method, ambient temperature, grouping, insulation and loaded cores. Default 32 A is illustrative, not an ampacity lookup; re-enter after changing cable.
I_zA32
Other installed chargers: total nameplate rating
Chargers outside the identical bank above, including those not charging now. Used only for the total rating under NAV section 19. Include their operating load in other-load inputs.
S_otherkVA0

Results

With the default inputs above, the calc gives:

ResultValue
Available AC power per wallbox11.09 kW
Charging current per wallbox16 A
Available AC power of EV bank11.09 kW
Connection screenWithin the entered connection budget
Selected cable and breaker screenPasses entered checks; verify site design
Feeder voltage drop at full wallbox rating0.64 %
Maximum route length — voltage drop only117.5 m
Smallest listed voltage-drop candidate (SI)1.5 mm² — voltage drop only
Feeder conductor loss at full rating70.8 W
EV bank budget at other-load peak26 A
RCD concept per charging pointType A ≤30 mA + certified 6 mA DC disconnection
Germany · NAV §19Notify grid operator before commissioning
Germany · new private LV installation§14a EnWG applies above 4.2 kW; arrange grid-oriented control

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

ABB 11 kW three-phase wallbox at 16 A

Source: ABB Terra AC product information, max. charging power: three-phase 11 kW / 16 A, https://wallbox.de.abb.com/produktinfos/ (attached s2). Manufacturer power is a rounded class rating. The ideal unity-PF formula at exactly 400 V gives about 11.085 kW; 0.10 kW tolerance accommodates that published rounding.

Inputs: Local load management = None; the others as above.

ResultSourceThis calc
Branch design current at full wallbox rating16 A16 A
Power per wallbox at its full branch rating11 ± 0.1 kW11.085 kW
Available AC power per wallbox11 ± 0.1 kW11.085 kW

ABB 22 kW three-phase wallbox at 32 A

Source: ABB Terra AC product information, max. charging power: three-phase 22 kW / 32 A, https://wallbox.de.abb.com/produktinfos/ (attached s2). Rounded manufacturer rating; ideal 400 V unity-PF power is about 22.170 kW. The formula is not adjusted to force an exact 22 kW.

Inputs: Wallbox nameplate rating = 22 kW — 32 A per phase; Local load management = None; Chosen branch breaker rated current = 40 A; Corrected ampacity of the selected cable = 48 A; the others as above.

ResultSourceThis calc
Branch design current at full wallbox rating32 A32 A
Power per wallbox at its full branch rating22 ± 0.2 kW22.17 kW
Available AC power per wallbox22 ± 0.2 kW22.17 kW

Published 6 mm² copper resistance at 70 °C

Source: PT Damai Cable Indonesia, NYY 1 manufacturer data, 6 mm² row: maximum DC resistance at 20 °C 3.08 Ω/km; maximum AC resistance at 70 °C 3.685 Ω/km. https://damaicable.com/nyy-1/ (attached s3). At these small sizes the simple DC temperature model differs by only about 0.00022 Ω/km, within the table's rounding; it does not model AC skin/proximity effects.

Inputs: the default inputs above.

ResultSourceThis calc
Selected copper conductor resistance at 20 °C3.08 Ω/km3.08 Ω/km
Selected conductor resistance at design temperature3.685 Ω/km3.685 Ω/km

Published 10 mm² copper resistance at 70 °C

Source: PT Damai Cable Indonesia, NYY 1, 10 mm² row: 1.83 Ω/km at 20 °C and 2.190 Ω/km at 70 °C. https://damaicable.com/nyy-1/ (attached s3). A 0.001 Ω/km tolerance covers table rounding and the negligible small-conductor AC/DC difference.

Inputs: Selected copper feeder conductor = 10 mm²; the others as above.

ResultSourceThis calc
Selected copper conductor resistance at 20 °C1.83 Ω/km1.83 Ω/km
Selected conductor resistance at design temperature2.19 Ω/km2.19 Ω/km

Schneider 10 × 22 kVA chargers on a 100 kVA static cap

Source: Schneider Electric Electrical Installation Guide, EV charging – energy and asset management, static example: 10 × 22 kVA charging points regulated to a 100 kVA EV setpoint. https://www.electrical-installation.org/enwiki/EV_charging_-_energy_and_asset_management (attached s4). Published bank cap 100 kVA, evaluated at unity PF. Input cap is its independently converted 400 V balanced three-phase current; expected result is the published 100 kVA, not a value generated by this calculator.

Inputs: Wallbox nameplate rating = 22 kW — 32 A per phase; Identical wallboxes charging simultaneously = 10; Local load management = Static cap; Static EV bank current cap per phase = 144.3 A; Usable house connection current per phase = 400 A; Other loads: design peak on the busiest phase = 100 A; Connection current reserve per phase = 0 A; Chosen branch breaker rated current = 40 A; Corrected ampacity of the selected cable = 48 A; the others as above.

ResultSourceThis calc
Available AC power of EV bank100 kW100 kW

DKE per-point RCD residual-current requirement

Source: DKE FAQ DIN VDE 0100-722, 3 December 2025, attached s1 page 3, answers 4 and 6: each point needs ≤30 mA protection; Type A or F with an IEC 62955 RDC-DD is an alternative to Type B. This checks the guidance constants and branch, not the complete installation.

Inputs: the default inputs above.

ResultSourceThis calc
Maximum RCD residual operating current30 mA30 mA
RCD selection code: 1 = Type A with DC; 2 = Type B11

NAV consent boundary: exactly 12 kVA

Source: NAV §19(2) requires prior consent when the sum of installed charger ratings exceeds 12 kVA. At exactly 12 kVA the strict exceedance test is false; notification remains required. https://www.gesetze-im-internet.de/nav/__19.html. DKE FAQ attached s1, page 3, answer 5 confirms the threshold.

Inputs: Other installed chargers: total nameplate rating = 1 kVA; the others as above.

ResultSourceThis calc
Total installed charger nameplate apparent power12 kVA12 kVA
German prior consent required: 1 = yes, 0 = no00

NAV consent boundary: above 12 kVA despite low local cap

Source: NAV §19(2), https://www.gesetze-im-internet.de/nav/__19.html: prior consent is triggered above 12 kVA installed nameplate sum. This tool does not let an arbitrary local current cap remove that trigger. DKE FAQ attached s1, page 3, answer 5 confirms the threshold.

Inputs: Other installed chargers: total nameplate rating = 1.01 kVA; Local load management = Static cap; Static EV bank current cap per phase = 6 A; the others as above.

ResultSourceThis calc
Total installed charger nameplate apparent power12.01 kVA12.01 kVA
German prior consent required: 1 = yes, 0 = no11