Cooling Tower Makeup Water and Cycles of Concentration

Calculate cooling tower evaporation, drift, blowdown and makeup water. Compare cycles of concentration with an LSI scaling screen, range and approach.

#blowdown #cooling towers #cycles of concentration #Langelier saturation index #water balance #water efficiency

Cooling towers replace water lost by evaporation, drift and controlled blowdown. This cooling tower makeup water calculation helps facility engineers, operators and students estimate those flows, compare cycles of concentration and explore a calcium carbonate scaling constraint. Use it for a steady operating condition in the evaporative water circuit of an open tower or the spray circuit of a closed-circuit unit.

Enter recirculating water flow, hot and cold water temperatures, and entering-air wet-bulb temperature. Flow fields accept explicit units, such as 1000 gal/min (US gallons). Rate cards show both m³/h and US gpm; use the SI/US switch for temperatures and volumes. The cooling range is hot minus cold water; approach is cold water minus wet bulb. In estimate mode, evaporation follows the SPX planning approximation of 0.0008 times circulating flow times range in °F, equivalent to 0.00144 per kelvin. For operating decisions, select the known-rate option and use a measured balance or a manufacturer’s detailed evaporation estimate. Weather, humidity and sensible heat transfer can make actual evaporation differ substantially.

Enter drift as a percentage of circulating flow, then choose requested and baseline cycles. Evaporation leaves dissolved salts behind; drift droplets and blowdown carry circulating-water salts out. The calculator therefore uses total liquid discharge equal to evaporation divided by cycles minus one, and subtracts drift to find cooling tower blowdown. A negative required blowdown means the selected cycles cannot be maintained with that drift rate. It is an input error rather than a zero-blowdown operating solution. Both water-demand curves stop at the drift-compatible ceiling, one plus evaporation divided by drift. The chart marks that boundary when it lies in view, and a result card gives its value; zero drift imposes no such ceiling.

For the scaling screen, enter makeup TDS, calcium hardness and alkalinity. Both hardness and alkalinity must be reported as CaCO₃. Enter circulating-water pH and the hottest relevant wetted temperature. The Langelier saturation index is evaluated assuming these constituents concentrate without precipitation or chemical addition. The tool caps requested cycles at the lowest of the selected LSI ceiling, your separately established site ceiling and its own TDS scope boundary. The default LSI allowance and site ceiling are illustrative assumptions, not approved operating limits.

Positive LSI indicates calcium carbonate supersaturation; it does not quantify scale mass or prove a treatment program effective. Negative LSI does not establish a corrosion rate. Review silica, chloride, sulphate, materials, inhibitors and microbial control separately. The charts show diminishing water savings and rising LSI as cycles increase; portions beyond your screening ceiling are exploratory.

Volumes apply the entered rates over the entered hours. Compare equivalent loads, and sum separate periods for seasonal operation. At fixed evaporation and negligible drift, increasing cycles from three to six cuts makeup by 20% and blowdown by 60%. DOE BMP #10 gives the same makeup saving but quotes 50% blowdown; the equations and published SPX balances support 60% under those assumptions.

This tool does not solve the Merkel heat-and-mass-transfer integral, size fill or fans, certify approach, prescribe chemical doses, or assess Legionella safety. Use its balance alongside measured chemistry, a specialist-approved treatment program and the site’s water management plan.

How it is calculated

For a steady basin inventory, makeup M=E+D+BM=E+D+B. A conservative dissolved-solids balance gives Mcm=(D+B)ccM c_m=(D+B)c_c, so cycles N=cc/cm=M/(D+B)N=c_c/c_m=M/(D+B). Combining these balances gives

B=EN−1−D,M=ENN−1.B=\frac{E}{N-1}-D,\qquad M=\frac{EN}{N-1}.

Drift is concentrated liquid, not pure evaporated water. The implemented balance follows SPX Evaporation and Water Usage (2019), PDF p. 3.

Cooling range is Th−TcT_h-T_c and approach is Tc−TwbT_c-T_{wb}. These describe boundary conditions used in Merkel's evaporative cooling framework; this tool does not evaluate the Merkel integral. Estimated evaporation uses E=0.00144RΔTE=0.00144 R\Delta T with RR and EE in the same volume/time units and range in K. This is SPX Cooling Tower Fundamentals, 2nd ed. (2009), printed p. 31 / PDF p. 32: 0.0008 per °F of range. Select a known evaporation rate when better operating data are available.

The simplified Langelier screen follows WRC TT 874/2/21 (2022), PDF pp. 81 and 97:

pHs=9.3+A+BT−C−DA,LSI=pH−pHs.pH_s=9.3+A+B_T-C-D_A,\qquad LSI=pH-pH_s.

Here A=(log⁡10(TDS)−1)/10A=(\log_{10}(TDS)-1)/10, BT=34.55−13.12log⁡10(TK)B_T=34.55-13.12\log_{10}(T_K), C=log⁡10(CaH)−0.4C=\log_{10}(Ca_H)-0.4, and DA=log⁡10(Alk)D_A=\log_{10}(Alk). Concentrations are numerical mg/L; calcium hardness and alkalinity are as CaCO₃. The steps normalize dimensional values by 1 mg/L or 1 K before taking logarithms. This implementation uses the SI offset 273.15 K; WRC's worked example uses the rounded 273.2, changing its LSI by less than 0.001.

Holding circulating pH and temperature fixed while all three concentrations multiply by NN gives LSI(N)=LSI(1)+1.9log⁡10(N)LSI(N)=LSI(1)+1.9\log_{10}(N). Therefore NLSI=10(LSIlimit−LSI(1))/1.9N_{LSI}=10^{(LSI_{limit}-LSI(1))/1.9}. Used cycles are the minimum of the request, that ceiling, the entered site ceiling and 10000/TDSm10000/TDS_m. No usable solution is shown if the combined chemistry ceiling is at or below 1.01 or required blowdown is negative. Baseline cycles remain unchanged for the comparison. Volumes equal rate times operating hours.

For positive drift, setting blowdown to zero gives the drift-only cycles ceiling ND=1+E/DN_D=1+E/D. Both water-demand curves are omitted where their implied blowdown is negative. A vertical line marks NDN_D when it falls within the plotted cycles range; the result card also gives this ceiling. It is a hydraulic feasibility boundary, separate from the chemistry screen. With zero drift there is no finite drift-only ceiling.

Assumptions

  • Steady operation, a well-mixed basin and approximately equal liquid densities. The circulation rate and thermal duty represent one operating condition.
  • Evaporated water contains no dissolved solids; drift and blowdown have the circulating-water concentration. Leaks, overflow, rain, airborne salt loading and other withdrawals are excluded.
  • TDS, calcium hardness and alkalinity concentrate conservatively. No precipitation, acid feed, softening or inhibitor chemistry is simulated. Circulating pH is entered independently and stays fixed across the sweep; it is not multiplied by cycles.
  • The hottest relevant wetted temperature is supplied by the user. Heat-exchanger surface temperatures can exceed bulk hot-water temperature.
  • The default +0.5 LSI allowance permits supersaturation. It and the default site limit of 6 cycles are illustrative, not safety recommendations.
  • Savings compare identical evaporation, drift and operating hours. Negative savings mean increased water use.
  • Flow-rate cards are provided in both m³/h and US gal/min. Flow inputs accept typed compatible units. The SI/US viewer switch changes absolute temperatures and operating volumes; temperature differences remain in K.

Where it applies

A planning balance for evaporative freshwater circuits, with an approximate calcium carbonate screen restricted here to pH 6.5–9.5, screening temperatures 1–90°C and projected TDS no greater than 10,000 mg/L. These are calculator scope limits, not a guarantee of accuracy or acceptable water quality. Strongly saline water, unusual buffers, treatment-altered alkalinity and chemically reactive species require a fuller chemistry model.

LSI describes thermodynamic calcium carbonate saturation, not scale quantity, deposition rate, overall corrosivity, silica scaling or microbial risk. A separate site ceiling must address other constituents, materials and treatment capability. Positive approach only checks the entered temperatures; it does not prove a tower can meet them. Range and approach are reported without fill sizing, air-flow calculation, fan selection or a Merkel-number calculation.

The SPX evaporation coefficient is an approximate operating estimate; ambient humidity and sensible heat transfer change actual evaporation. Prefer measured or manufacturer-calculated evaporation for operational decisions. Hours at one duty do not predict a seasonal load profile. Charts beyond the chemistry screening ceiling are hypothetical. Both water-demand curves omit negative-blowdown operating points; the vertical drift-limit marker denotes zero blowdown. No point to its right is a feasible steady balance at the entered evaporation and drift.

DOE BMP #10 quotes 20% less makeup and 50% less blowdown for 3 to 6 cycles. The makeup claim agrees with the fixed-evaporation balance; with negligible drift the blowdown reduction is 60%, since 1/(3−1)1/(3-1) becomes 1/(6−1)1/(6-1). The calculator retains this balance.

References

  • U.S. DOE FEMP, Best Management Practice #10: Cooling Tower Management, accessed 2026-10-29. https://www.energy.gov/cmei/femp/best-management-practice-10-cooling-tower-management
  • SPX Cooling Technologies, Evaporation and Water Usage, AE-AS-24, September 2019, PDF p. 3, Table 1 and Eq. 1. https://spxcooling.com/wp-content/uploads/AE-AS-24-1.pdf
  • SPX Cooling Technologies, J. C. Hensley (ed.), Cooling Tower Fundamentals, 2nd edition, 2009, Section I, printed pp. 14–16 and 31. https://spxcooling.com/pdf/Cooling-Tower-Fundamentals.pdf
  • P. Moodley et al., Risk-based and Site-specific Industrial Use Water Quality Guidelines, Volume 2: Technical Support, WRC TT 874/2/21, March 2022, printed pp. 62, 68 and 78 (PDF pp. 81, 87 and 97). https://www.wrc.org.za/wp-content/uploads/mdocs/TT%20874%20Volume%202%20final%20web.pdf
  • W. F. Langelier, The Analytical Control of Anti-Corrosion Water Treatment, Journal AWWA 28 (1936), 1500–1521. https://doi.org/10.1002/j.1551-8833.1936.tb13785.x
  • F. Merkel, Verdunstungskühlung, Forschungsarbeiten auf dem Gebiete des Ingenieurwesens, Heft 275, VDI-Verlag, 1925. Historical thermal framework; no Merkel integral is implemented. Bibliographic record: https://ci.nii.ac.jp/ncid/BA86352898
  • CDC, Controlling Legionella in Cooling Towers, January 3, 2025, accessed 2026-10-29. https://www.cdc.gov/control-legionella/php/toolkit/cooling-towers-module.html

Inputs

InputSymbolUnitDefault
Recirculating water flow
Flow through the evaporative water circuit at the operating condition. You may type a compatible unit after the number, for example 1000 gal/min; gal means US gallons.
R_waterm^3/h1000
Hot water entering towerT_hot°C35
Cold water leaving towerT_cold°C27
Entering air wet-bulb temperature
Use the coincident entering-air wet bulb. Range and approach describe the entered duty; they do not predict tower capacity.
T_wb°C23
Evaporation basisevap_modeEstimate from flow and range
Known evaporation rate
From a measured balance or a manufacturer/psychrometric model at this duty. Do not enter total makeup here. You may type a compatible unit after the number, for example 1000 gal/min; gal means US gallons.
E_knownm^3/h11.52
Drift (% of circulating flow)
Enter a percentage: 0.005 means 0.005%, not a fraction of 0.005. Use the eliminator's operating drift rate.
drift_pct0.005
Requested cycles of concentration
Results use the lower of this request and the chemistry screening ceilings.
N_request4
Baseline cycles for comparison
An existing operating point, used unchanged for the comparison. Its chemistry is checked separately.
N_base3
Hours at this operating condition
Volume = rate × entered hours. For a variable load, calculate and sum separate operating periods.
t_runh4000
Makeup total dissolved solidsTDS_makemg/L180
Makeup calcium hardness (as CaCO₃)
Calcium hardness, not total hardness and not elemental calcium. If the lab reports mg/L Ca, multiply by about 2.497 first.
Ca_makemg/L30
Makeup alkalinity (as CaCO₃)
Use the carbonate/bicarbonate alkalinity appropriate to the water. Acid addition and noncarbonate buffers invalidate simple concentration.
Alk_makemg/L30
Circulating-water pH at screening temperature
Use measured or treatment-predicted circulating pH. It is held fixed across the cycles sweep; makeup pH is not concentrated.
pH_circ7.7
Hottest wetted temperature for LSI screen
Use the hottest relevant wetted surface or water temperature, at least the tower hot-water temperature. A bulk-water value can miss heat-exchanger scaling.
T_scale°C40
Selected maximum LSI
A scenario limit, not a universal safe value. +0.5 is an illustrative allowance and already indicates supersaturation; agree the value with your water treatment specialist.
LSI_limit0.5
Site maximum cycles from other limits
Enter an independently approved ceiling covering silica, chlorides, materials and treatment. The default 6 is illustrative and is not a site assessment.
N_site6

Results

With the default inputs above, the calc gives:

ResultValue
Makeup water required15.36 m³/h
Makeup — US gpm67.628 gal/min
Blowdown required3.79 m³/h
Blowdown — US gpm16.687 gal/min
Evaporation11.52 m³/h
Evaporation — US gpm50.721 gal/min
Drift0.05 m³/h
Drift — US gpm0.22 gal/min
Cycles used after screening4
Combined screening ceiling (cycles)5.99
Drift ceiling (cycles; B = 0)231.4
LSI at screening temperature0.17
Cooling range8 K
Wet-bulb approach4 K
Makeup over entered operating hours61,440 m³
Blowdown over entered operating hours15,160 m³
Makeup volume saved versus baseline7,680 m³
Makeup reduction versus baseline (%)11.11

Checked against sources

Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).

SPX Table 1: high drift replaces blowdown

Source: SPX Evaporation and Water Usage, AE-AS-24 (2019), PDF p. 3, Table 1 case 1. Published US gpm converted to m³/h using 1 US gal = 0.003785411784 m³. Evaporation is supplied by the source; this case tests the solids and water balance.

Inputs: Recirculating water flow = 4,542 m³/h; Hot water entering tower = 40.556 °C; Cold water leaving tower = 29.444 °C; Entering air wet-bulb temperature = 25.556 °C; Hottest wetted temperature for LSI screen = 45 °C; Evaporation basis = Enter evaporation rate; Known evaporation rate = 88.352 m³/h; Drift (% of circulating flow) = 0.2; Requested cycles of concentration = 3; the others as above.

ResultSourceThis calc
Drift9.085 m³/h9.085 m³/h
Blowdown required35.091 m³/h35.091 m³/h
Makeup water required132.5 m³/h132.5 m³/h
Makeup — US gpm583.5 gal/min583.5 gal/min

SPX Table 1: efficient drift eliminators

Source: SPX Evaporation and Water Usage (2019), PDF p. 3, Table 1 case 2. Same duty and evaporation as case 1; reducing drift changes blowdown while makeup remains 583.5 US gpm.

Inputs: Recirculating water flow = 4,542 m³/h; Hot water entering tower = 40.556 °C; Cold water leaving tower = 29.444 °C; Entering air wet-bulb temperature = 25.556 °C; Hottest wetted temperature for LSI screen = 45 °C; Evaporation basis = Enter evaporation rate; Known evaporation rate = 88.352 m³/h; Requested cycles of concentration = 3; the others as above.

ResultSourceThis calc
Drift0.2271 m³/h0.2271 m³/h
Blowdown required43.949 m³/h43.949 m³/h
Makeup water required132.5 m³/h132.5 m³/h
Makeup — US gpm583.5 gal/min583.5 gal/min

SPX Fundamentals: evaporation and blowdown worked example

Source: SPX Cooling Tower Fundamentals, 2nd edition (2009), printed p. 31 / PDF p. 32: 10,000 US gpm, 25°F range, 3 cycles, drift fraction 0.0002; published evaporation 200 US gpm and blowdown 98 US gpm. Absolute water temperatures are selected to realize the published range.

Inputs: Recirculating water flow = 2,271 m³/h; Hot water entering tower = 40 °C; Cold water leaving tower = 26.111 °C; Entering air wet-bulb temperature = 20 °C; Drift (% of circulating flow) = 0.02; Requested cycles of concentration = 3; the others as above.

ResultSourceThis calc
Evaporation45.425 m³/h45.425 m³/h
Drift0.4542 m³/h0.4542 m³/h
Blowdown required22.258 m³/h22.258 m³/h
Evaporation — US gpm200 gal/min200 gal/min

WRC worked example: LSI +0.71

Source: WRC TT 874/2/21, Volume 2 (March 2022), printed p. 78 / PDF p. 97. Published sample: 25°C, pH 7.59, TDS 4479 mg/L, calcium hardness 1139.65 and alkalinity 129 mg/L as CaCO₃; pHs 6.88 and LSI 0.71. Makeup values are one-third of the sample to reproduce it at 3 cycles. Tolerance covers two-decimal source factors; The implementation uses the SI offset 273.15 K rather than the example's rounded 273.2; the resulting LSI difference is below 0.001.

Inputs: Hot water entering tower = 25 °C; Cold water leaving tower = 20 °C; Entering air wet-bulb temperature = 15 °C; Hottest wetted temperature for LSI screen = 25 °C; Makeup total dissolved solids = 1,493 mg/L; Makeup calcium hardness (as CaCO₃) = 379.9 mg/L; Makeup alkalinity (as CaCO₃) = 43 mg/L; Circulating-water pH at screening temperature = 7.59; Selected maximum LSI = 1; Requested cycles of concentration = 3; the others as above.

ResultSourceThis calc
Saturation pH at used cycles6.88 ± 0.0156.883
LSI at screening temperature0.71 ± 0.0150.7068
Projected circulating dissolved solids4,479 mg/L4,479 mg/L
Projected circulating calcium hardness as CaCO₃1,140 mg/L1,140 mg/L

DOE BMP 10: 3 to 6 cycles saves 20% makeup

Source: DOE FEMP BMP #10, Cooling Tower Management, accessed 2026-10-29, reports 20% makeup reduction from 3 to 6 cycles. This check uses its fixed-evaporation interpretation and negligible drift. The same page's claimed 50% blowdown reduction is inconsistent with M = E + B and N = M/B: B/E changes from 1/2 to 1/5, a 60% reduction. The calculator retains the conservative-solute balance rather than reproducing that inconsistent percentage.

Inputs: Requested cycles of concentration = 6; Site maximum cycles from other limits = 10; Selected maximum LSI = 1; Drift (% of circulating flow) = 0; the others as above.

ResultSourceThis calc
Makeup reduction versus baseline (%)2020