AC Size Calculator: Cooling Load for Hot Climates
Estimate room cooling load and AC size at 40–50 °C, including roof exposure, solar gain, humidity and high-ambient capacity loss. Compare running-cost scenarios by set temperature.
If you are asking “what size AC do I need?” for a hot room, floor area alone is a weak starting point. Two rooms with the same area can have very different loads because of roof exposure, afternoon sun, leaky doors and humid outdoor air. This AC tonnage calculator estimates those contributions separately for engineers, students and homeowners comparing cooling options in India, Pakistan, the Gulf, the Philippines and similar climates.
Enter the room dimensions, then identify which cardinal walls face outdoors. Window areas belong inside their wall areas, so the calculator subtracts glazing before calculating opaque-wall conduction. Enable the exposed roof for a top-floor room. Enter U-values from the building specification when available; the defaults illustrate an uninsulated room and are not a construction survey. Walls beside equally cooled rooms contribute no heat in this model.
Choose the outdoor design temperature and its coincident humidity, then set the indoor temperature and humidity target. Add people, operating appliances, lighting and untreated outdoor air. The normal solar model uses latitude, solar declination, irradiance and shading to compare simultaneous gains over a day. Press play to move the sun around the plan and see the current-hour load. The capacity result always uses the sampled daily maximum. An expert option accepts known effective temperature differences and a known window solar gain instead.
Results separate the estimated room load from the minimum nominal AC capacity. Both appear in kW, BTU/h and refrigeration tons. The nominal requirement includes your capacity allowance and the entered high-temperature capacity-retention assumption. Chinese pi and Japanese tatami classes are manufacturer-based examples selected by nominal cooling capacity; they do not convert this room's floor area into a guaranteed coverage rating. Always compare the actual model's stated kW.
Use the set-temperature chart to explore running-cost scenarios for inverter and fixed-speed units with the ISEER values you enter. The mean-load fraction, efficiency adjustment, hours and tariff are explicit assumptions. They can change the answer substantially. Equal effective efficiencies give equal energy use in this comparison; an inverter label alone does not guarantee savings. The tariff default is illustrative as of 27 October 2026.
This BTU calculator for a room provides a preliminary cooling estimate, not an HVAC design or a heating and heat-pump sizing calculation. It omits thermal storage, detailed shading, pull-down after a hot shutdown and duct-system design. Check both sensible and latent capacity, minimum modulation, the outdoor operating limit and performance at the actual indoor and outdoor conditions. Refrigerant, electrical and installation work belongs to qualified people.
How it is calculated
Simultaneous room heat gains
The calculation follows the component energy balances taught in NPTEL IIT Kharagpur, Lessons 34–35, with a deliberately simplified, steady design-day solar model. It estimates heat gains as cooling loads: radiant cooling-load factors are 1 and thermal storage is omitted. It does not run EnergyPlus.
Opaque surfaces use . In normal mode, . This is a sol-air approximation with zero separate net long-wave correction. EnergyPlus 26.2, Outside Surface Heat Balance, explains the surface balance and sol-air reduction; its full conduction and radiation algorithms are more detailed. The user supplies U-values and the outside combined film coefficient; no construction catalogue is implied.
Solar direction is derived by projecting the solar vector onto true east, north and up, using latitude, declination and solar hour angle (15 degrees per hour from solar noon). Vertical N/E/S/W irradiance is positive beam incidence plus half the diffuse horizontal irradiance and half the ground-reflected horizontal irradiance. Ground reflectance is assumed 0.2. Roof irradiance is beam times solar-altitude sine plus diffuse. Irradiance is zero with the sun below the horizon. Window solar gain is area × SHGC × shading fraction × incident irradiance. Window conduction is separate, and glazing is removed from opaque wall area.
The entire day is sampled every 15 minutes at constant outdoor conditions, internal loads and DNI/DHI. Sizing uses the largest simultaneous sum, not the sum of individual orientation maxima. The component table reports contributions at that same peak. The sun animation uses a separate time input and does not alter sizing. In known-ETD mode, the supplied ETDs and window solar gain are one simultaneous design case, constant across the chart; a peak time has no meaning.
Humidity and outdoor air
FAO-56 Chapter 3 equation 11 supplies the approximate saturation-pressure curve. NPTEL Lesson 27 supplies and ideal-gas dry-air density. ACH is converted to outdoor volumetric flow, then to dry-air mass flow. Sensible gain is . Latent gain uses , where is temperature above 0 °C. Constants are 1005 and 1880 J/(kg·K), and 2501000 J/kg. Drier outdoor air receives no latent credit. Occupant sensible and latent loads, lights and appliances are added explicitly.
Capacity and cost
Capacity retention is 1 up to 35 °C and decreases linearly according to the user's retained fraction at 45 °C; the same line is extrapolated to 50 °C. This is a user scenario, not a universal AC curve. Minimum nominal capacity is room peak × (1 + allowance) / retention. One refrigeration ton is 12000 BTU/h.
The cost scenario is monthly delivered cooling divided by (entered ISEER × entered efficiency adjustment), multiplied by the entered tariff. BEE's 24 August 2016 methodology describes seasonal temperature weighting; ISEER is not an instantaneous COP at 45–50 °C. The set-temperature sweep recalculates envelope and outdoor-air gains at fixed indoor RH while retaining the same efficiency and mean-load fractions. In known-ETD mode, the supplied design gains are shifted by the change in set temperature, with negative envelope gains clipped at zero.
Assumptions
- One rectangular room with walls aligned to true cardinal directions. Adjacent surfaces disabled by the user adjoin equally cooled space. No ground-contact floor model, thermal bridges, skylights or hot adjoining rooms.
- U-values, irradiance, absorptivity, shading, infiltration and equipment performance are user inputs. Construction and weather defaults are illustrative scenarios, not measured local design data.
- Constant outdoor dry bulb and coincident RH over the sampled day. Constant DNI/DHI while the sun is up; isotropic diffuse sky and 0.2 ground reflectance. No sun obstruction, wall shading, thermal lag or radiant delay.
- People and appliance gains are simultaneous at the room peak. The default standing-person gain of 75 W sensible plus 75 W latent comes from NPTEL Lesson 35, Table 35.3, p.12.
- Untreated air is counted once as ACH at outdoor volumetric conditions. No heat recovery, exhaust imbalance, duct losses or duct-fan selection. No credit for drying by outdoor air.
- The default 85% capacity retention at 45 °C, 0.75 efficiency adjustment, 0.55 mean-load fraction, 5% allowance and tariff 8 are editable assumptions. They are not measured product performance or BEE-prescribed factors.
- Regional class lists use historical Haier product examples and Hitachi's 2026 E-series nominal capacities. They are illustrative capacity labels, with no claim about present availability or tropical suitability. Pi is a cooling class, not mechanical horsepower; tatami is a market class here, not an area conversion.
Where it applies
Preliminary cooling estimates for 30–50 °C outdoor dry bulb, 18–30 °C indoors, outdoor warmer than indoors, latitude −40° to +40°, and pressure 75–105 kPa. The intended hot-climate use is 40–50 °C. The permitted fields are calculation bounds, not a guarantee that every extreme combination represents a normal occupied room.
No prediction of indoor comfort, achievable humidity, pull-down time, compressor cycling, electrical circuit size or refrigerant selection. The steady solar model can overstate a heavy wall's instantaneous load and cannot reproduce its delayed evening peak. For detailed design, use local design-weather data and a transient heat-balance or appropriate cooling-load method.
Before purchase, verify delivered total AND sensible/latent capacity at the actual ambient temperature and indoor dry/wet bulb, minimum modulation, airflow and maximum permitted outdoor temperature. A high operating-temperature limit is not a promise of retained cooling capacity. Avoid accumulating independent oversizing allowances. Installation, refrigerant handling and electrical work belong to qualified people and must follow local rules.
ISEER comparisons use the 2016 BEE definition as background, not a current star-rating compliance assessment. No current star bands, rebate eligibility or regulated tariff are assigned. Prices are user-entered; the default tariff is illustrative as of 27 October 2026.
References
- NPTEL, IIT Kharagpur, Refrigeration and Air Conditioning: Lesson 35, Cooling and Heating Loads, equations 35.3–35.12 and worked problem 10, pp.19–21 (attached s1). https://archive.nptel.ac.in/content/storage2/courses/112105129/pdf/R%26AC%20Lecture%2035.pdf
- NPTEL, IIT Kharagpur, Refrigeration and Air Conditioning: Lesson 27, Psychrometry, equations 27.5–27.6 and worked problem 5, p.15 (attached s2): https://archive.nptel.ac.in/content/storage2/courses/112105129/pdf/R%26AC%20Lecture%2027.pdf ; Lesson 34, Heat Transfer Through Buildings (attached s3): https://archive.nptel.ac.in/content/storage2/courses/112105129/pdf/R%26AC%20Lecture%2034.pdf
- FAO Irrigation and Drainage Paper 56, Chapter 3, equation 11, saturation vapour pressure (attached s4). https://www.fao.org/4/x0490e/x0490e07.htm
- EnergyPlus 26.2 Engineering Reference, Outside Surface Heat Balance, equation 3.56 and sol-air discussion (attached s6). https://energyplus.readthedocs.io/en/v26.2.0/guides/engineering-reference/3.5-outside-surface-heat-balance.html
- Government of India, Ministry of Power / BEE, 24 August 2016, ISEER seasonal methodology (attached s5). https://www.pib.gov.in/newsite/PrintRelease.aspx?lang=2®=48&relid=149154
- Hitachi Japan, 2026 E series product specifications, nominal cooling capacities and Japanese room classes (attached s14), accessed 27 October 2026. https://kadenfan.hitachi.co.jp/ra/lineup/eseries_26/spec.html
- Haier Chinese class examples (attached s10–s13 and s15), accessed 27 October 2026: 1 pi/2.6 kW https://www.haier.com/air_conditioners/20200218_122452.shtml ; 1.5 pi/3.5 kW https://www.haier.com/air_conditioners/20150204_99283.shtml ; 2 pi/5.0 kW https://www.haier.com/air_conditioners/20130802_99778.shtml ; 2.5 pi/5.6 kW https://www.haier.com/air_conditioners/20110704_99712.shtml ; 3 pi/7.2 kW https://www.haier.com/air_conditioners/20170503_99900.shtml
Inputs
| Input | Symbol | Unit | Default |
|---|---|---|---|
| East–west room length North and south walls have this length. | L_room | m | 5 |
| North–south room depth East and west walls have this length. | D_room | m | 4 |
| Room height Use the clear internal height. | H_room | m | 2.8 |
| North wall faces outdoors Clear for a wall adjoining a room at the same temperature. Hot adjoining spaces need a separate assessment. | ext_N | false | |
| North window area Total glazing area on this wall; included within the gross wall area. | win_N | m^2 | 0 |
| East wall faces outdoors Clear for a wall adjoining a room at the same temperature. Hot adjoining spaces need a separate assessment. | ext_E | false | |
| East window area Total glazing area on this wall; included within the gross wall area. | win_E | m^2 | 0 |
| South wall faces outdoors Clear for a wall adjoining a room at the same temperature. Hot adjoining spaces need a separate assessment. | ext_S | true | |
| South window area Total glazing area on this wall; included within the gross wall area. | win_S | m^2 | 1.5 |
| West wall faces outdoors Clear for a wall adjoining a room at the same temperature. Hot adjoining spaces need a separate assessment. | ext_W | true | |
| West window area Total glazing area on this wall; included within the gross wall area. | win_W | m^2 | 1.5 |
| Roof directly exposed to outdoors Clear when a conditioned room is directly above. | top_floor | true | |
| Floor over outdoor air or a ventilated basement Clear for a floor adjoining a space at the same temperature. | floor_out | false | |
| Wall U-value Overall transmittance including surface films. Default is an illustrative uninsulated wall. | U_wall | W/(m^2*K) | 1.8 |
| Roof U-value Overall transmittance, not thermal conductivity. | U_roof | W/(m^2*K) | 1.2 |
| Floor U-value No solar gain is applied to the floor. | U_floor | W/(m^2*K) | 1.2 |
| Window U-value Use whole-window data when available; default illustrates single glazing. | U_glass | W/(m^2*K) | 5.7 |
| Use known effective temperature differences Expert option for published or surveyed ETDs. Default uses a steady sol-air estimate with no thermal storage. | known_etd | false | |
| Opaque-surface solar absorptivity 0 = reflective; 1 = fully absorbing. Same value for walls and roof. | alpha_s | 0.6 | |
| Outside combined surface coefficient Sol-air approximation; use a value consistent with the U-value surface film. | h_out | W/(m^2*K) | 20 |
| Window solar heat gain coefficient Use glazing manufacturer data. Applied to beam, diffuse and reflected irradiance. | SHGC | 0.55 | |
| Window solar fraction after shading 1 = unshaded; 0 = fully blocked. A constant approximation, not an overhang model. | shade_f | 0.7 | |
| Latitude (north positive) Use local latitude; azimuths are true north. | lat_site | deg | 25 |
| Design-day solar declination About +23.45° in June, 0° at equinoxes, −23.45° in December. | dec_sun | deg | 20 |
| Direct normal solar irradiance Constant sunny-day scenario while the sun is up; use site weather data. | DNI | W/m^2 | 750 |
| Diffuse horizontal solar irradiance Isotropic sky; ground reflectance is assumed 0.2. | DHI | W/m^2 | 120 |
| Known wall effective temperature difference Same ETD on all exposed walls; includes solar and storage effects. | ETD_wall | K | 25 |
| Known roof effective temperature difference Use an ETD appropriate to the roof construction and design hour. | ETD_roof | K | 30 |
| Known window solar gain before shading Includes glazing response, such as a published SHGF. SHGC is bypassed in this mode. | SHG_known | W/m^2 | 300 |
| Outdoor design dry-bulb temperature Use local extreme design conditions, not an annual average. | T_out | degC | 45 |
| Outdoor relative humidity (%) Humidity coincident with the outdoor dry-bulb temperature; 35 means 35%. | RH_out | 35 | |
| Room set temperature Lower settings increase envelope load and usually moisture removal. | T_in | degC | 26 |
| Target indoor relative humidity (%) This is a load calculation target; a room AC may not independently control humidity. | RH_in | 50 | |
| Local barometric pressure Use local station pressure, not the weather report corrected to sea level. | p_air | kPa | 101.325 |
| Outdoor air exchange rate Infiltration plus equivalent untreated ventilation, referred to outdoor volume. NPTEL suggests about 0.2–2 h⁻¹ for buildings; open doors can exceed this. | ACH | 1/h | 0.7 |
| People present at peak | people | 2 | |
| Sensible heat per person Adjust for activity; the default 75 W sensible + 75 W latent is NPTEL's standing-person example. | person_s | W | 75 |
| Latent heat per person Moisture from people. Use an activity-appropriate value. | person_l | W | 75 |
| Lighting heat into the room Operating electrical power including ballasts or drivers. | lights | W | 100 |
| Appliance sensible heat Heat released indoors at peak: computers, TV, refrigerator, etc. | appliances | W | 250 |
| Other latent heat Moisture from processes; commercial kitchens and cooking exhaust need detailed design. | latent_app | W | 0 |
| Capacity allowance (%) Applied after the calculated load. Avoid adding several overlapping safety factors. | margin_f | 5 | |
| Capacity retained at 45 °C (%) Illustrative assumption, not a universal product curve. Enter the selected model's capacity at 45 °C divided by its capacity at 35 °C. | retain_45 | 85 | |
| AC maximum permitted outdoor temperature Replace with the manufacturer's operating limit. This default does not certify a product. | T_limit | degC | 52 |
| Inverter AC label ISEER Cooling seasonal output divided by electrical energy, W/W. Enter the current product label; no star band is assigned. | ISEER_inv | 5 | |
| Fixed-speed AC label ISEER Use comparable seasonal ratings. Do not enter US SEER in Btu/Wh. | ISEER_fixed | 3.2 | |
| Effective efficiency / label ISEER Illustrative hot-weather adjustment, not a BEE formula. Use measured or manufacturer seasonal performance where available. | eff_f | 0.75 | |
| Mean load / calculated peak load Scenario for operating hours; includes weather and occupancy diversity. Not compressor duty cycle. | load_f | 0.55 | |
| Operating hours per day Hours in use each day. | hours_day | h | 8 |
| Operating days per month | days_month | 30 | |
| Electricity tariff (your currency per kWh) Illustrative value as of 27 October 2026; enter your local marginal tariff. Results use the same currency, excluding fixed charges and taxes. | tariff | 8 | |
| Solar time — press ▶ to move the sun Solar time differs from clock time. Animation changes the illustration and current-hour gains; sizing uses the entire sampled day. | solar_t | h | 16 |
Results
With the default inputs above, the calc gives:
| Result | Value |
|---|---|
| Estimated peak room load | 4.09 kW |
| Estimated peak room load | 13,958 BTU/h |
| Estimated room load (refrigeration tons) | 1.16 |
| Minimum nominal AC capacity at 35 °C | 5.05 kW |
| Minimum nominal AC capacity | 17,242 BTU/h |
| Minimum nominal AC size (refrigeration tons) | 1.44 |
| Assumed capacity retained at design ambient (%) | 85 |
| Room sensible heat ratio | 0.885 |
| Latent cooling requirement | 472 W |
| Chinese nominal class (pi), examples only | 2.5 pi example |
| Japanese nominal class (tatami), not room area | 18 tatami class |
| Inverter energy scenario per month | 144 kW·h |
| Fixed-speed energy scenario per month | 225 kW·h |
| Inverter monthly cost (your currency) | 1,152 |
| Fixed-speed monthly cost (your currency) | 1,800 |
| Fixed-speed minus inverter monthly cost | 648 |
Checked against sources
Each case below was calculated by this calc and agrees with the value from its source (within the tolerance where one is shown).
NPTEL Lesson 35, worked room (43 °C)
Source: NPTEL IIT Kharagpur, Refrigeration and Air Conditioning, Lesson 35 pp.19–21, problem 10. Published sensible components sum correctly to 3811.68 W; with 476.4 W latent, the published total is 4288.08 W. Outdoor RH ≈19.8% corresponds to the quoted humidity ratio 0.0107 at 43 °C and 101 kPa; this tool accepts RH rather than wet bulb. The calculator gives approximately 4288.97 W because it calculates dry-air density and moisture-dependent specific heat, uses a saturation-pressure correlation rather than chart readings, and includes the water-vapour sensible enthalpy in the latent term instead of using hfg alone. A 15 W total tolerance allows these psychrometric, latent-enthalpy and rounding differences. The independently sourced expected values are unchanged.
Inputs: East–west room length = 6 m; North–south room depth = 3 m; Room height = 3 m; South wall faces outdoors = no; West window area = 2.25 m²; Floor over outdoor air or a ventilated basement = yes; Wall U-value = 1.78 W/(m²·K); Roof U-value = 1.316 W/(m²·K); Window U-value = 3.12 W/(m²·K); Use known effective temperature differences = yes; Window solar fraction after shading = 0.86; Outdoor design dry-bulb temperature = 43 °C; Room set temperature = 25 °C; Outdoor relative humidity (%) = 19.8; Local barometric pressure = 101 kPa; Outdoor air exchange rate = 0.5 1/h; People present at peak = 4; Sensible heat per person = 90 W; Latent heat per person = 40 W; Lighting heat into the room = 594 W; Appliance sensible heat = 600 W; Other latent heat = 300 W; Capacity allowance (%) = 25; Capacity retained at 45 °C (%) = 100; the others as above.
| Result | Source | This calc |
|---|---|---|
| Wall gain at the room peak | 300.4 W | 300.4 W |
| Roof gain at the room peak | 710.6 W | 710.6 W |
| Floor conduction from outdoor conditions | 388.8 W | 388.8 W |
| Window conduction plus solar at the room peak | 706.9 W | 706.9 W |
| Estimated peak room cooling load | 4,288 ± 15 W | 4,289 W |
| Room sensible heat ratio | 0.889 ± 0.003 | 0.8888 |
NPTEL Lesson 27, 37 °C / 50% RH air
Source: NPTEL IIT Kharagpur, Refrigeration and Air Conditioning, Lesson 27 p.15, problem 5. Independent steam-table/chart result; tolerance covers the FAO saturation-pressure approximation.
Inputs: Outdoor design dry-bulb temperature = 37 °C; Outdoor relative humidity (%) = 50; the others as above.
| Result | Source | This calc |
|---|---|---|
| Outdoor humidity ratio, kg water / kg dry air | 0.01989 ± 1 × 10⁻⁴ | 0.01987 |
| Outdoor moist-air enthalpy, dry-air basis | 88.31 ± 0.4 kJ/kg | 88.275 kJ/kg |







Responses